Generator Protection
A generator could be part of:
Generator Protection
Generator Protection
Generator Protection
Electrical Circuit of the Generator
Electrical Circuit of the Generator
Generator is never solidly grounded:-
If it were solidly grounded, the single line-to-ground fault current would be dangerously high. Apart from the high value of fault current, the resulting asymmetry in the rotating magnetic field inside the generator would cause unacceptably large vibrations and result in mechanical damage to the rotor.
In order to limit the short-circuit current, the neutral of the generator is grounded through a resistance. In order to get a practicable value of the grounding resistor, it is connected through a step-down transformer, known as grounding transformer.
Electrical Circuit of the Generator
Electrical Circuit of the Generator
The power plant has a sizeable auxiliary electrical load of its own, of the order of 10% of the power rating of the generator, which is supplied through the unit auxiliary transformer (UAT). It is to be noted that these auxiliaries require power even before the generator can be started, run up to speed and synchronized with the grid. Hence, there is the switching facility to energize the UAT directly from the grid.
Electrical Circuit of the Generator
The rotor of the generator houses the field winding. A separate dc generator, which is mounted on the turbo-alternator shaft, feeds the field. The dc system is kept floating with respect to the ac ground, i.e. neither the +ve nor the –ve terminal is grounded.
Electrical Faults and abnormal operating conditions
Stator Faults
Stator Phase and Ground Faults
Longitudinal percentage differential protection.
Stator Phase and Ground Faults
This gives rise to a larger spill current, during normal load and external faults, in case of the transformer differential protection than in case of the generator differential protection. Normally, the percentage bias setting of 5–10% is adequate for longitudinal differential protection of the generator stator winding whereas a setting of 20–40% may be required in case of power transformers.
Transverse Differential Protection
Rotor Faults
Abnormal Operating Condition
Abnormal Operating Condition
Over-speeding
Loss of Excitation�
There are several possible causes due to which field excitation may be lost, namely:
Loss of Excitation�
Protection against Loss of Excitation Using Offset Mho Relay
Loss of Prime Mover
Directional relay for protection against loss of prime mover
Induction motor protection
Various Faults and Abnormal Operating Conditions
Starting Current
Electrical Faults�
Electrical Faults�
Electrical Faults�
Ground Faults Inside the Motor�
Inter-turn Faults�
Abnormal Operating Conditions from Supply Side
Unbalanced Supply Voltage
Abnormal Operating Conditions from Supply Side
Unbalanced Supply Voltage
Abnormal Operating Conditions from Supply Side
Unbalanced Supply Voltage
Single Phasing
Reduction in Supply Voltage
Reversal of Phases
Abnormal Operating Conditions from Mechanical Side
Failure of Bearing and Rotor Jam
Overload
Resistance temperature detector relays (RTDs)
Thermal replica relays
Data Required for Designing Motor Protection Schemes