POWER POINT PRESENTATION
ON
ELECTRIC POWER SYSTEM PROTECTION
B.TECH 6TH SEMESTER
ELECTRICAL ENGINEERING
GANDHI INSTITUTE FOR EDUCATION AND TECHNOLOGY
BANIATANGI, BHUBANESWAR - 752060
UNIT-I
CIRCUIT BREAKERS
WHAT IS A CIRCUIT BREAKER?
Operating Principle
Two contacts called electrode remains closed under normal operating conditions. When fault occurs on any part of the system, the trip coil of thecircuit breaker get energized and contacts are separated.
Operating Principle
Two contacts called electrode remains closed under normal operating conditions. When fault occurs on any part of the system, the trip coil of the circuit breaker get energized and contacts are separated.
Arc Phenomenon
upon the
Methods of Arc Extinction
High Resistance Method Low Resistance Method
TYPES OF CIRCUIT BREAKER
OIL CIRCUIT BREAKER
AIR BLAST CIRCUIT BREAKER
SF6 CIRCUIT BREAKER
VACCUM CIRCUIT BREAKER
Bulk Oil Circuit breaAirker
cushion
Low Oil Circuit Breaker
Consists of two parts.
Supporting Chamber.
Circuit-Breaking
chamber( consist of fixed and moving contact)
Vacuum Circuit Breaker
SF6 Circuit Breaker
Arc control device
Air break circuit breaker
UNIT - II ELECTROMAGNETIC AND STATIC RELAYS
electromechanical
static
Static Relays
Static Comparators as Relays
Comparison vs Computation
Numerical Relays
is the software.
Block Diagram of Numerical Relay
Transmission Line Protection
Distance Relays: -
Introduction:
Additional Features in distance schemes: -
Switch onto fault: -
Types of Auto-reclosing schemes (based on
phase):
a) Three phase Auto-reclosing:
b) Single Phase Auto-reclosing:
to the remote end
tripping is termed
of the feeder for as transfer trip
inter- under-
reaching scheme. To avoid mal-operation due to receipt of false signal, the receiving end relay operation is inter-locked with its Zone-3/starter operation i.e. the scheme operates either by its own Zone-1 relay operation or by receipt of carried and its Zone-3/starter operation.
Transfer trip is of two types:- Under-reaching scheme:-
Over-reaching scheme:-
b) Blocking schemes:-
Factors affecting distance relay operation:-
Fault resistance:-
Fault resistance has two components:-
In a fault between phases, only arc resistance is involved.
For a fault at F, the actual line impedance
= R + JX = ZL
Due to the presence of fault resistance, the impedance measured by the relay
= R + JX + RF = ZR (where ZR > ZL)
Fault arc resistance is given by Warrington's formula: Rarc = 8750 X l / I 1.4
where
l = length of arc in ft
I = fault current in Amps
UNIT - III GENERATOR AND
TRANSFORMER PROTECTION
Kinds of Faults Generators are Subjected to
Stator Ground Fault Protection
Methods of Limiting Erath Fault Currents
Generator Directly Connected to the Power System
directly to the busbars
Directional relays
Generators Connected Through a Stepping Up Transformer
⚫
Distribution Transformer Method of Earthing Generator Neutral
100% Protection of Generator Stator Winding
Third Harmonic Method – 100% Stator Earth Fault Protection
Generator Backup Protection
Stator Inter-turn Faults
Loss of Excitation
Loss of Excitation Protection
Negative Sequence Protection
Negative Sequence Protection
Rotor Earth Faults
⚫
Over Voltage Protection
Reverse power
OPEARTION
HIGH BUS FAULT CURRENTS DUE TO LARGE NUMBER OF CIRCUITS CONNECTED:
FALSE TRIP BY BUS PROTECTION MAY CREATE SERIOUS PROBLEMS:
WITH BOTH DEPENDABILITY AND SECURITY IMPORTANT, PREFERENCE IS ALWAYS GIVEN TO SECURITY.
51
ESEC= IPRIM*XM - SECONDARY VOLTAGE ON RELAY TERMINALS IR= ΣIPRIM*XM /(ZR+ΣZC) – MINIMUM OPERATING CURRENT WHERE,
IPRIM – PRIMARY CURRENT IN EACH CIRCUIT
XM–LINER COUPLER MUTUAL REACTANCE (5V PER 1000AMPS => 0.005Ω @ 60HZ ),
ZR – RELAY TAP IMPEDANCE
ΣZC – SUM OF ALL LINEAR COUPLER SELF IMPEDANCES
0 A
2000 A
2000 A
0 A
4000 A
40 V
59
0 V
10 V
10 V
0 V
20 V
RELAYS TO LIMIT ENERGY DURING FAULTS.
59
CANNOT EASILY BE APPLIED TO RECONFIGURABLE BUSES AND OFFERS NO ADVANCED FUNCTIONALITY
51
TO COPE WITH CT SATURATION AND
87
OTHER ERRORS.
IDIF
= I1 + I2 +... + In
IRES = I1 + I2 +...+ In
IRES
= max(I1 , I , ..., In )
2
PERCENT
INDIVIDUAL CURRENTS SAMPLED BY PROTECTION AND SUMMATED DIGITALLY.
MONITORING OF EACH CIRCUIT
copper
fiber
ALL DATA FROM
AND CPU OVER FIBRE USING PROPRIETARY PROTOCOL.
copper
LINE) IS MUCH MORE DUE TO THEIR GREAT LENGTH AND EXPOSURE TO THE ATMOSPHERIC CONDITIONS. THEREFORE, VARIOUS PROTECTION SCHEMES HAVE BEEN DEVELOPED WHICH MAY BE CLASSIFIED AS:
INVERSE DEFINITE MINIMUM TIME LAG RELAYS. THE RELAYS ARE SO SET THAT THE MINIMUM TIME OF OPERATION DECREASE FROM THE POWER
STATION TO THE REMOTE SUB-STATION AS SHOWN IN FIG. IN NEXT SLIDE.
IF A FAULT OCCURS BETWEEN STATION E AND F, IT WILL BE CLEARED IN 0.1 SECOND BY THE RELAY AND CIRCUIT BREAKER OF SUBSTATION E BECAUSE ALL OTHER RELAYS HAVE HIGHER OPERATING TIME. IF THE RELAY AT SUB STATION E FAILS TO TRIP, THE RELAY AT D WILL OPERATE AFTER A TIME DELAY OF 0.5 SECONDS I.E. AFTER 0.6 SECONDS FROM THE OCCURRENCE OF FAULT.
WHERE CONTINUITY OF SUPPLY IS ABSOLUTELY NECESSARY, TWO FEEDERS ARE RUN IN PARALLEL. IF A FAULT OCCURS ON ONE FEEDER, THE SUPPLY CAN BE MAINTAINED FROM THE OTHER FEEDER, DISCONNECTING THE FAULTY FEEDER. FOLLOWING FIG. SHOWS THE SYSTEM WHERE TWO FEEDERS ARE CONNECTED IN PARALLEL BETWEEN GENERATING STATION & SUB-STATION.
IF AN EARTH FAULT OCCURS ON FEEDERS AT POINT F AS SHOWN IN FIG. THE
FAULT IS FED;
THIS CLEARLY SHOWS THAT DIRECTIONAL RELAY P CARRIES THE CURRENT IN NORMAL DIRECTION WHERE AS DIRECTIONAL RELAY Q CARRIES THE CURRENT IN REVERSE DIRECTION MOMENTARILY. THIS OPEARATES THE RELAY Q INTANTANEOUSLY. THE RELAY B HAVING INVERSE TIME CHARACTERISTICS ALSO OPERATES BECAUSE OF HEAVY FLOW OF CURRENT .
WHENEVER THE FAULT OCCURS ON ANY OF THE SECTION ONLY CORRESPONDING RELAYS WILL OPERATE WITHOUT DISTURBING THE OTHER RELAYS OF THE NETWORK, THUS, THE FAULTY SECTION IS ISOLATED AND SUPPLY IS MAINTAIN.
What do I need to know about neutral handling in Eaton transformer-less UPS applications?
C
B
A
3W + Gnd Source
N
To the UPS
Installation practices
SOURCE X FMR
SAFETY GND TO FRAME
The neutral from the source transformer is not run to load-side equipment, AND it may not be necessary to run a neutral to the UPS.
FUSE
PDU
FUSE
FUSE
FUSE
A
B
N
B
A
N
C
N
B
A
C
C
FUSE
G
GND
G
SSW
Neutral and Ground: What does the UPS require?
3-Phase UPS Output
A
C
B
Center Point Reference
Battery Operation with ungrounded output
What does it mean that my UPS output is an ungrounded system? Is it safe? Will it work? What about faults?
Battery Operation - continued
Is my load at risk?
What about faults?
FUSE
208 OR 400V LOAD PANEL
FUSE
FUSE
FUSE
B
FUSE
G
GND
G
G
Return current can NOT flow; IGBTs are off when utility has failed
SAFETY GND TO FRAME
Fuse will not clear. UPS will enter current limit at 300% nominal
for 20 cycles
Phase to Gnd Fault
SSW
OK, wise guy, what happens if I have a fault while on battery in a 9390 208V UPS with no PDU?
ON BATTERY 208/120V OR 415/240V
SOURCE X FMR
What if I have a parallel system?
Parallel Systems—Distributed Bypass
If there are NO phase to neutral loads (more typical), we still need a full-rated 4th wire from each UPS E12 to a common tie point in the tie cabinet.
9395
Pull an E12 wire from
each UPS
9395
DC/AC
AC/DC
Bypass
DC/AC
AC/DC
Bypass
Tie Cabinet
∆
UNIT - V
PROTECTION AGAINST OVER VOLTAGES
Causes for Voltage Surge
Basic Impulse Levels
GENERATOR FAULTS
●
●
LOSS OF EXCITATION
LOSS OF INPUT TO TURBINE LOSS OF SYNCHRONISM
TRANSFORMER FAULTS
INSTRUMENT TRANSFORMERS
TYPES OF RELAYS
TYPES OF RELAYS
Ph-Ph
APPLICATION OF CTs & PTs
AMMETER CT CONNECTION VOLT METER PT CONNECTION
WATT METER & VAR METERS BOTH CT & PT CONNECTION FREQUENCY METER – PT CONNECTION
ESSENTIAL REQUIREMENTS OF RELAYS
Lightning Protection
Facts about Lightning
Lightning Doesn’t Go Straight Down
Use The Five Second Rule
Four Main Features of Lightning Protection
Grounding Rod
Surge Protection Is A Must
Effects Of Lightning