EID PBIL Presentation
PLAN B
By: Koh Liang Yong Christopher (p2042750)
Nabyl Asyraf Bin Abdul Aziz(p2042817)
Sng Teck Chuen Garrick(p2043243)
Contents
Design Plan
Balcony
Master bedroom
Guestroom
Living Room
Kitchen
Single Line Diagram
List of Appliances likely to be used
Guest Room | Master Bedroom | Bathroom | Kitchen | Living Room |
|
|
(Instant) |
|
|
Maximum Demand
Description | Connected Load | D.F | Maximum Demand |
12 nos filament lamps each rated at 40W | 12x40/230= 2.087A | 66% of total current demand | 1.38 A |
10 nos 13A SSOs(est demand 2kW)(largest cct) | 2000/230 = 8.7 A | 100% | 8.7 A |
2 nos 13A SSOs(est demand 2kW)(smallest circuit) | (2x2000)/230 = 17.39A | 40% | 6.956A |
1 nos air con motor rated at 4.5kW,3-phase,p.f of 0.75 lagging with efficiency of 90% | 4500/√3 x 400 x 0.75 x 0.9 = 9.62 A | 100% | 9.62 A |
1 nos of 2kW Instant water heater | 1x2000/230 = 8.7A | 100% | 8.7A |
7kW stove without SSO | 7000/230= 30.43 30.43-10=20.43 | 10A + 30% | 10 A 6.129 A |
2 nos 15A SSO(est demand to be 1 kW) | 1000/230=4.35A | 100% + 40% | 4.35 + ((4.35/100)*40) = 6.09A |
Maximum Demand
=57.58A
Main Breaker Size
(120%)= 1.2 * 57.58
=69.1A
Recommended
Breaker Size
=75A TPN
Number of circuits used
46.926 m²≈47m²
From Table 5A,the max area that can be served by a Radial A2 circuit is 50m².
Therefore,minimum no of circuits required ≥ 47/50
≥ 0.94
= 1 circuit
Cable Sizing
From Table 5A,for type A2 Radial circuit,recommended cable size is 4mm²