1 of 23

Pole Top Control Cubicle

Operation and Features

2 of 23

Single LV Auxiliary Power Supply

Single Pole Battery Circuit Breaker

110V or 240V AC from LV Supply on same pole or nearby

3 of 23

Dual LV Auxiliary Power Supply

Single Pole Battery Circuit Breaker

110V or 240V AC from LV Supply on same pole or nearby

Alternate 110V or 240V AC Supply from other side of switch

4 of 23

Integrated plus LV Auxiliary Power Supply

Single Pole Battery Circuit Breaker

110V or 240V AC from LV Supply on same pole or nearby

27V AC Supply from Voltage Transformer on Pole

5 of 23

Single Integrated Power Supply

Single Pole Battery Circuit Breaker

27V AC Supply from Voltage Transformer on Pole

6 of 23

Pole Top Control Cubicle Operation

PTCC operation is primarily via the Operator Control Panel Module (OCPM)

  • The OCPM can be used to:

    • Trip and Close the switchgear.
    • Isolate the Trip and Close circuits.
    • Change Operator Settings such as Auto Reclose ON/OFF, Local/Remote mode etc.
    • Change configuration settings for protection, communications, metering etc.
    • Check the status of the switchgear.
    • View system analogue values.
    • View the event history.
    • View maximum demand records.

7 of 23

Operator Control Panel

8 of 23

PTCC Control Panel Navigation

System Status

Event Log

Measurement

Protection

9 of 23

System Status display group

Communications Parameters

Loop Automation Configuration

IOEX Status

WSOS Port P8 Communications

Quick Key Map

Selection

Options 1-3

Capability

Switchgear Wear and General Details

Switchgear Type and Ratings

Radio and Time Set

Switchgear Terminal Designation

Phase Voltage and�Power Flow

Live/Dead Indication

Switchgear Status

Operator Settings

Loop Automation

Fault Flags

10 of 23

Event Log display group

Oldest

Continue

Most Recent

Event Log

11 of 23

Measurement display group

Configurable History�OR�Average Demand

Weekly Maximum Demand

Monthly Maximum Demand

Supply Outages

Power System Voltages

Pages 1 - 2

System Measurements

Instantaneous Demand

12 of 23

Protection display group

U/O Voltage Protection Page 1 - 3

NPS Work Tag Protection

NPS Single Shot Protection

NPS Protection�Trip Number 1 - 4

Earth Work Tag Protection

Earth Single Shot Protection

Earth Protection�Trip Number 1 - 4

Phase Work Tag Protection

Phase Single Shot Protection

Phase Protection�Trip Number 1 - 4

Under/Over Freq�Prot Pages 1 - 2

Directional Blocking�Pages 1 - 3

Protection Settings�Page 2 - 5

Protection Settings�Page 1

13 of 23

OCPM Menu navigation

EVENT LOG

MENU

SYSTEM STATUS

MEASUREMENT

PROTECTION

MENU

MENU

MENU

PANEL�ON/OFF

14 of 23

Pole Top Control Cubicle Hardware Features

Features of the CAPM card include:

    • 16Mhz 68332 Microprocessor
    • Run time workspace
      • 1 MB volatile memory
    • Program, Configuration, History
      • 2 MB non-volatile Flash – CAPM4
      • 4 MB non-volatile Flash – CAPM5
    • A-D conversion
      • 10 bit CAPM4
      • 12 bit CAPM5
    • Electronics rated for 80ºC
    • Real time Microprocessor technology
    • Inbuilt Switch Mode Power Supplies.
    • Inbuilt Radio Modem and RS232 port.
    • No DIP switches to break or corode.
    • All contained in sealed stanless steel enclosure. ❒

15 of 23

CAPM – Flow diagram

RADIO

MODEM

REMOTE�I/O

OPERATOR�SUB SYSTEM�PANEL

WSOS�OPERATOR�PC

TRIP�CAPACITOR

UNINTERRUPTIBLE�POWER SUPPLY

SOLENOID�POWER�SUPPLY

ANALOGUE TO�DIGITAL�CONVERTER

ANALOGUE �FRONT END

MODEM

SERIAL�INTERFACE

MICRO�PROCESSOR

DIGITAL INTERFACE

V23 FSK

RS232

SPI

RS232

CLOSE�CAPACITOR

BATTERY

CAPM

CONTROL CUBICLE

AUXILIARY POWER SUPPLY

TRIP�SOLENOID

CLOSE�SOLENOID

MEMORY

AUXILIARY�SWITCHES

VACUUM�INTERRUPTER

PRESSURE�SENSOR

CVT

CT

CVT

HV LINE 3 PHASES

CIRCUIT BREAKER

CONTROL CUBICLE ENTRY MODULE

CONTROL�CABLE

16 of 23

Pole Top Control Cubicle Software Features

  • Operational

  • Protection

  • Communications

  • Metering

  • Event Logging

  • Automation

17 of 23

Operational Features

The PTCC has a number of operational features that can be activated from the control panel.

  • Local or Remote mode can be selected.

  • Auto Reclose or Single Shot modes.

  • Work Tag can be applied during live line work.

  • Protection On/Off control.

  • Separate Earth and Sensitive Earth Fault On/Off control.
  • Protection Group Selection.

  • Compensation for high loads following an outage.

18 of 23

Protection Features

The PTCC has protection elements for:

  • Overcurrent, Earth Fault and SEF
  • Directional O/C, Earth and SEF
  • Negative Phase Sequence
  • Under/Over Frequency
  • Under/Over Voltage
  • Loss of Phase

As well as the following features:

  • High Current Lockout
  • Inrush Restraint
  • Cold Load Pickup
  • Sequence Control
  • Live Load Blocking
  • Dead Lockout

% Setting Current

time [s]

100

1

10

100

19 of 23

Communications Features

The PTCC incorporates the following communications features.

  • Inbuilt RTU for radio telemetry

  • RS-232 Port for connection of telephone or radio modem

  • Industry standard SCADA protocol emulation
    • DNP3, IEC-870, PGE-2179, Conitel 2020

  • Provision for external RTU or substation control with IOEX (Input Output Expander)

20 of 23

Metering Features

The PTCC measures:

    • Phase Current
    • Bushing Voltage

  • Calculation and display of:
    • Earth Current
    • Negative Phase Sequence Current
    • Frequency
    • Phase to Phase voltages
    • Power (Real, Reactive and Apparent)
    • Power Factor

  • Demand Logging (Average, Weekly and Monthly)
  • Supply Outage measurement

An�a�l�o�g�u�e

Di�g�i�t�a�l

Co�n�v�e�r�t�e�r

2000:1

2000:1

2000:1

CTs

IP

IP

IP

ACR/LBS

CAPM

IS

IS

IS

A

B

C

IC + IA + IB = 0

21 of 23

Event Recording

The PTCC (CAPM5) can store and display in excess of 5000 events.

  • 40 standard event types

  • 14 maintenance event types

  • 10 msec time resolution

  • Maximum RMS fault current detected during a fault episode

  • Retrieval by PC or telemetry using WSOS

22 of 23

Automation Features

The PTCC has four separate automation features:

    • Automatic Protection Group Selection

    • Generator Control

    • Auto - Changeover Scheme

    • Loop Automation

23 of 23