Maximum Demand & Diversity Factor As Per National Electrical Code
Diversity Factor
Types of load at final circuit | Household installations | Small shop, offices and building premises | Small hotels, boarding houses |
Lighting load | 66% of the total current demand | 75% of the total current demand | 85% of the total current demand |
Heating and Power | 100 % of total current up to 10 Amp | 100% of full load current for largest appliances | 100% of full load current for largest appliances |
| + 50% of current if current demand exceed 10 A | + 75% for remaining appliances | + 80% for second largest appliances |
|
|
| + 60% for remaining appliances |
Cooking Appliances | 10 A | 100% of full load current of largest appliance | 100% of full load current of largest appliance |
| + 30% of full load current in excess of 10 Amp + 6 Amp if socket outlet is also considered | + 80% of full load of second largest appliance | + 80% of full load of second largest appliance |
|
| + 60% of full load of remaining appliances | + 60% of full load of remaining appliances |
Water Heater | 100% of full load current of largest appliance | 100% of full load current of largest appliance | 100% of full load current of largest appliance |
| + 100% full load current of second largest appliance | + 100% full load current of second largest appliance | + 100% full load current of second largest appliance |
| + 25% of full load of remaining appliances | + 25% of full load of remaining appliances | + 25% of full load of remaining appliances |
Final arrangement | 100% current demand of largest point | 100% current demand of largest point | 100% current demand of largest point |
| + 40% current demand of every other point | + 75% of current demand of every other point | + 75% of current demand of every point in main rooms |
|
|
| + 40% of current demand of every other points |
The Estimation of maximum demand is carried out as below. ( only for single tariff )
Connected load | Approximately maximum demand |
Lighting load | 66% of installed load |
Heating appliances | 100% of first 10 A |
| + 50% of excess of 10 A |
Connected load | Approximately maximum demand |
General socket outlet | 100% current demand of largest socket |
| + 40% current demand of other socket |
If any cooking appliances | 10 A |
| + 30% current demand of remaining connected appliances |
| + 6 A for socket outlet |