Fire Inspection and�Code Enforcement
8th Edition�Inspector II
Chapter 13 — Special-Agent Fire Extinguishing Systems and Portable Extinguishers
�Learning Objective 1
Identify the appropriate evaluation and testing methods for special-agent fire extinguishing systems.
13–1
Know the duties required for inspecting dry-chemical systems.
13–2
Evaluate the application methods, agents, components
Evaluate inspection and testing requirements
NFPA® 17 recommends that qualified personnel perform monthly procedures.
13–3
Check all parts of the system to verify that they are in their proper locations and connected
Inspect manual actuators for obstructions
Inspect the tamper indicators and seals to note that they are intact
Check the maintenance tag or certificate for proper placement
Examine the entire system for any obvious damage
Check the pressure gauges to verify that they read within their operable ranges
The inspector should be able to review records of inspections and maintenance.
13–4
Problems should be corrected immediately
In most cases, this situation requires notification of the organization responsible for the maintenance
Verify that hydrostatic testing is �up-to-date for storage containers.
13–5
Containers (cylinders) less than 150 pounds (75 kg) must be hydrostatically tested every 12 years
Larger storage cylinders have no hydrostatic test requirements
Inspectors also need to check all auxiliary functions.
13–6
Audible/visible alarms
Power shutdowns for process equipment
Functionality of ventilation fans
REVIEW QUESTION
Describe the inspection requirements for dry-chemical systems.
13–7
Know the duties required for inspecting wet-chemical systems.
13–8
Basically the same as those used for dry-chemical extinguishing systems
NFPA®17A, Standard for Wet Chemical Extinguishing Systems, contains detailed requirements
Verify system maintenance
Verify all manufacturer-required system checks
Courtesy of Rich Mahaney
Review several items when inspecting wet-chemical systems.
13–9
System parts are in their correct location
Manual actuators are unobstructed
Tamper indicators and seals are intact
Maintenance tags are in place and up-to-date
Obvious damage is noted
Gauges are within operational limits
Equipment modifications or repairs are noted
REVIEW QUESTION
What is included in an inspection of wet-chemical systems?
13–10
Know where to find inspection and testing requirements for clean-agent systems.
13–11
NFPA® 2001, Standard on Clean Agent Fire Extinguishing Systems
NFPA® 12A, Standard on Halon 1301 Fire Extinguishing Systems
Become familiar with some of the inspection requirements for �clean-agent systems.
13–12
Annual inspections by qualified personnel are required for all system components
Quantity and pressure of the clean-agent must be checked semiannually
Records on all tests and inspections must be maintained and available for review
(Cont.)
Become familiar with some of the inspection requirements for �clean-agent systems.
13–13
Types of agents used in the systems
System components
Inspection and testing requirements
Know inspection requirements for various parts of clean-agent systems.
13–14
Containers
Hoses
Protected enclosures
REVIEW QUESTION
List some of the items an inspector should verify when inspecting clean-agent systems.
13–15
Understand the complexities of CO2 systems.
13–16
Only fire suppression system contractors, licensed by the manufacturer, should perform maintenance and testing
Inspectors need to be familiar with the requirements for servicing a CO2 system.
13–17
Physical damage to components
Excessive corrosion
Change in hazard
Enclosure integrity
Up-to-date records
Cylinders checked semiannually
Hydrostatic testing requirements are the same as for clean-agent systems
REVIEW QUESTION
What should inspectors look for when inspecting CO2 systems?
13–18
Foam systems require specially trained personnel for inspections, servicing, and testing.
13–19
Highly complex systems
NFPA® 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems
Procedures described by the manufacturer of the system must be followed
Because some state governments may modify standards, inspectors need to check those regulations as well
Know what duties an inspector has regarding foam systems.
13–20
Concentrate tank
Semiannually
Annually
REVIEW QUESTION
What items do inspectors need to verify when inspecting foam fire suppression systems?
13–21
�Learning Objective 2
Describe proper selection, distribution, inspection, and maintenance of portable fire extinguishers.
13–22
Understand the factors that influence proper selection and distribution of fire extinguishers.
13–23
Nature of the hazard to be protected
Extinguisher size
Travel distances
Understand additional factors that influence proper selection and distribution of fire extinguishers.
13–24
Potential severity (size, intensity, and rate of fire spread) of any resulting fire
Personnel available
Environmental conditions
(Cont.)
Understand additional factors that influence proper selection and distribution of fire extinguishers.
13–25
Any anticipated adverse chemical reactions
Any health and occupational safety concerns
Inspection and service required to maintain the extinguishers
The nature of hazards dictate the type, size, number and location of fire extinguishers.
13–26
Some hazards may require additional extinguishers beyond the distribution required by the locally adopted code
General method for locating or distributing extinguishers
Inspectors need to know the characteristics of a light-hazard occupancy.
13–27
Amount of ordinary combustible material or flammable liquids present is such that a small incipient fire may be expected
Includes classrooms, churches, assembly halls
Some parts of an occupancy that are classified as light hazard may actually be ordinary hazard
Inspectors need to know the characteristics of an ordinary-hazard occupancy.
13–28
Amount of ordinary combustibles and flammable liquids present would likely result in a moderate incipient fire
Fire growth would not be so rapid as to be beyond the control of fire extinguishers if discovered quickly
Includes mercantile storage and display, light manufacturing facilities, parking garages, some warehouses
Courtesy of Ron Moore, McKinney (TX) Fire Department
Inspectors need to know the characteristics of an extra-hazard occupancy.
13–29
Amount of ordinary combustible materials and flammable liquids present are high and a rapidly spreading fire may develop
Includes automotive repair shops, painting facilities, manufacturing operations that use flammable liquids, restaurants with deep fat fryers, and locations with high-piled storage of combustibles
Courtesy of Rich Mahaney
Understand fire extinguisher size and location requirements for Class A fuels.
13–30
Class A fuels
(Cont.)
Understand fire extinguisher size and location requirements for Class A fuels.
13–31
Understand fire extinguisher size and location requirements for Class B fuels.
13–32
Class B fuels
Understand special considerations for Class B fuels.
13–33
Special considerations
Understand fire extinguisher size and location requirements for Class C fuels.
13–34
Class C fuels
Understand fire extinguisher size and location requirements for Class D fuels.
13–35
Class D fuels
Placement analysis
Understand fire extinguisher size and location requirements for Class K fuels.
13–36
Class K fuels
REVIEW QUESTION
What are the main factors that influence the proper distribution of portable fire extinguishers?
13–37
Effectiveness of portable fire extinguishers is limited by the ability of the building occupants to use them.
13–38
Inspectors are not responsible for this type of training
Inspectors can inquire about how well and how often the occupants are trained
Training is a service that the fire department can provide if no other source is available
Inspectors can recommend that training be given and provide information on who to contact
Without regular inspections, fire extinguishers can be rendered useless.
13–39
Stolen, misplaced, or obstructed
Damaged as a result of being struck by a vehicle
Low in pressure
Used on a fire and replaced without being recharged
Clogged with solid agent
Courtesy of Rich Mahaney
Periodic fire extinguisher inspections are very important to fire and life safety in a facility.
13–40
Simply checking to verify that they have not been stolen or vandalized is an important part of industrial plant protection
Usually performed by building or facility personnel but may be performed by fire suppression or inspection personnel
Important to consult local or state licensing/certification requirements for servicing
Courtesy of Rich Mahaney
NFPA® 10 recommends monthly fire extinguisher inspections.
13–41
Owner/occupant is responsible for keeping accurate records
Extinguisher inspection tag
Be sure to check the inspection tag and the service collar tag.
13–42
Service collar tag
Inspectors need to check the same items the owner/occupant did.
13–43
Make sure the extinguisher is properly located
Verify that access is not obstructed
Check that the extinguisher is suitable for the hazard protected
Check the inspection tag to determine if maintenance is due
Examine the nozzle or horn for obstructions
Verify that lock pins or tamper seals are intact
(Cont.)
Inspectors need to check the same things the owner/occupant did.
13–44
Check for signs of physical damage
Check that the extinguisher is fully charged with expellant and agent
Check that the pressure gauge indicates proper operating pressure
Check collar tag for current information and/or damage
Check that required signage is in place
Check to see if the operating instructions on the extinguisher nameplate are legible
Inspectors need to know when to perform fire extinguisher maintenance and who should do it.
13–45
When
Who
For more information on maintenance intervals and fire extinguisher inspection, see NFPA®10
REVIEW QUESTION
What should an inspector look for when inspecting portable fire extinguishers?
13–46