Differential Relay
Differential Relay
Differential Relay
Differential Relay
Simple Differential Protection or Circulating current differential protection.
Simple Differential relay under normal conditions
The currents transformed by the two CTs, being equal in magnitude as well as in phase, just circulate on the secondary side.
There is no tendency for the current to spill into the over-current relay. The over-current relay connected in the spill path is wired to trip the two circuit breakers on either side of the equipment being protected.
Simple Differential relay during external fault or Through faults
Simple Differential relay during Internal fault
If, min = (CT ratio) (Plug setting of the OC relay) = nI ps
Simple Differential relay Double end fed system
Zone of protection
Problems in Circulating current differential protection.
Problems in Circulating current differential protection.
Actual behaviour of simple differential scheme
CTs are subject to ratio and phase angle errors. Both these errors depend upon the burden on the CTs, which in turn depends on the lead lengths and the impedance of the relay coil. CT saturation and Unequal lead length
Through fault stability and stability ratio
As the ‘through fault’ current goes on increasing, various imperfections of the CTs get magnified. This causes the spill current to build up.
When relay trips it is said to have lost stability
Through fault stability and stability ratio
The minimum internal fault current required for the scheme to operate, correctly in this case, is decided by pick-up value of the over-current relay in the spill path. To signify the spread between the minimum internal fault current at which the scheme operates and the maximum ‘through fault’ current beyond which the scheme (mal)operates, we define a term called stability ratio.
The higher the stability ratio, the better is the ability of the system to discriminate between external and internal faults. The stability ratio can be improved by improving the match between the two CTs.
Equivalent Circuit of CT
Differential scheme considering CT equivalent circuit
Since the magnetizing currents of the two CTs will generally vary widely, there is a substantial spill current during ‘through fault’ conditions.
This results into loss of stability and maloperation of the simple differential scheme.
Thus, the simple differential scheme, which looks attractively simple, cannot be used in practice without further modifications.
Why not simple Differential scheme?
Transformers:- Close match cannot be obtained
Currents on the two sides of the transformer are, in general, different, the ratios of transformation of the CTs are also different.
Their designs are therefore different, making it impossible to get a close match between their characteristics. This explains why the spill current goes on increasing as the ‘through fault’ current increases.
Busbars:- Subjected to very high fault current on secondary will magnify the difference between CTs.
Percentage Differential Relay
Percentage Differential Relay
Spill current must be greater than a definite percentage of the ‘through fault’ current for the relay to operate. Hence, the name percentage differential relay.
The slope of the relay is customarily expressed as a percentage. Thus, a slope of 0.4 is expressed as 40% slope.
Percentage Differential Relay
The percentage differential relay does not have a fixed pick-up value. The relay automatically adapts its pick-up value to the ‘through fault’ current. As the ‘through fault’ current goes on increasing, we are in effect asking the relay to take it easy, by introducing a restraining torque proportional to the circulating current.
‘Through fault’ stability and the stability ratio of the percentage differential relay is substantially better than that of the simple differential relay.
Percentage Differential Relay
The restraining winding is also known as the biasing winding because we bias the relay towards restraint. The slope of the characteristic is also known as percentage bias.
For Internal Fault
Thus, during internal faults the spill current will be two times the circulating current, giving a slope of 2, which is expressed as 200%.
Percentage Differential Relay
The ratio of minimum internal fault current below which the scheme will not respond and the maximum ‘through fault’ current above which the scheme will maloperate is stability factor
The percentage differential relay can be made more immune to maloperation on ‘through fault’ by increasing the slope of the characteristic.
Relay setting
Block diagram of percentage differential relay
The relay has two settings: the slope setting and the minimum pick-up setting.
The slope is adjusted by changing the tapping on the restraining coil.
The minimum pick-up is adjusted by changing the tension of the restraining spring.
Earth Leakage Protection
Earth Leakage Protection
Earth Leakage Protection of single phase load
Earth Leakage Protection of three phase load