Which Inverter Is Source of Oscillation?
Point-on-wave side-bands reveal the oscillation source, with no topology, models or grid data
2026 Point On Wave Applications (POWA) Conference
Platinum Sponsors
Gold Sponsors
Silver Sponsors
Bronze Sponsors
1
The Problem
Inverters are replacing machines
Lower inertia and fast controls make grids oscillation-prone.
Sub-synchronous oscillations (SSO)
SSO events have been observed worldwide.
Find the source, fix the problem
IEEE PES task force highlights source isolation as the most effective mitigation.
Why is the source hard to find?
Model-based
Need small-signal models and control parameters for every inverter
Energy-flow
Need the full network topology
2
Why Point-on-Wave?
Phasors compress the waveform. Point-on-wave preserves the signature.
Phasor FFT: an oscillation exists.
Waveform FFT: which device.
Side-band asymmetry lives only in waveform data.
3
Recreation of a Real-World Event
Kaua‘i, Hawai‘i · 21 Nov 2021
An oil-fired unit tripped on the islanded grid, triggering 18–20 Hz oscillations at every bus.
4 IBRs EPRI grid-following models
3 synchronous plants
57.1 kV network
Full EMT model in PSCAD
Ground truth: IBR A is tuned to create the 20 Hz mode, so the true source is known.
4
PoW Oscillation Detection
Generator trip at t = 1.5 s and oscillations observed across all buses.
Normalized current waveform
2
Reference cycle
3
3-cycle window slides →
1
Segment
Normalise and extract one cycle (16.67 ms)
2
Compare
Moving window average vs. a fixed healthy reference
3
Smooth
Mean absolute deviation over a 3-cycle window
4
Flag
Alarm when deviation exceeds 5% of amplitude
Detection accuracy of three methods
39.1%
Cycle vs. next cycle
67%
Fixed reference vs next cycle
98%
Fixed reference vs 3-cycle moving window
5
Identify the Source Signature
FFT the point-on-wave current at each inverter’s point of interconnection.
SOURCE · IBR A, Bus 1
Upper side-band at 80 Hz
NOT SOURCE · IBR B, Bus 2
Nothing at 80 Hz
6
Validation 1: Change the Mix
IBR A’s generation share was cut: 73% → 35% → 18%.
Generation mix (%)
IBR A at 80 Hz
Case 1
73
20
23.5 A
Case 2
35
21
22
20
57.8 A
Case 3
18
21
39
20
57.8 A
IBR A
IBR B
IBR C
IBR D
Oil plant
Less output, bigger side-band; IBRs B–D stay at 0 A.
7
Validation 2: Change Source Location
IBR A was swapped with B, C and D, placing the source at four different buses.
Bus 1
Bus 2
Bus 4
Bus 5
Source at Bus 1 · original placement
Source at Bus 2 · swapped with IBR B
Source at Bus 4 · swapped with IBR C
Source at Bus 5 · swapped with IBR D
The 80 Hz side-band follows IBR A wherever it goes, pinpointing the oscillation source.
Every IBR shows 40 Hz lower sideband
Only the source IBR shows 80 Hz upper sideband
Point-on-wave side-bands reveal the oscillation source
SOURCE IBR
40
60
80 Hz
EVERY OTHER IBR
40
60
80 Hz
8
Implementation
IN PROGRESS:
The algorithm is being implemented on FNET point-on-wave devices, using data collected by FNET.
Muhammad Umar Afzaal Hash1, Yayu yang1, Yilu Liu1,2, Chanaka Keerthisinghe3, David Raschka3
1University of Tennessee, Knoxville (CURENT) 2Oak Ridge National Laboratory 3G&W Electric Co.