JHARKHAND URJA SANCHARAN NIGAM LIMITED

​

VOCATIONANAL TRAINING

AT

220/132KV GSS HATIA-II & 132/33KV GSS HATIA-I

​

2 of 29

Study of Design and Working of the Grid Sub-station Hatia-l and Hatia- ll.�

Project Report

On

Vocational Training

During the period from 2nd August, 2021 to 16th August, 2021

By

Juhi Sinha, Kumar Saurav, Shalini Kumari, Rishav Gupta, Akansha Josphin Kindo, Vishnu Deo Jha, Anjali Priya, Adit Raj, Akansha Dubey

2nd year B. Tech (Electrical Engineering)

Birsa Institute of Technology, Sindri

​

3 of 29

ACKNOWLEDGEMENT

In the present world of competition there is a race of existence in which those who are willing to come forward succeed. There are people around you who help you realize your dream. We acquired this opportunity with much pleasure to acknowledge the invaluable assistance of all the people who have helped us through the course of our journey in successful completion of this project. We would like to express our deepest gratitude to the engineers of Hatia Grid I & Il Substation for their active support and continuous guidance without which it would have been difficult for us to complete this project. They were generous enough to take time out of their regular work to lend a helping hand whenever we needed one and enabling us to complete this project. Their guidance helped us to successfully complete the project within the relatively short time frame of 2 weeks, from 2nd of August 2021 to 16th of August 2021.

4 of 29

INDEX

Sr. No.

Topic

1.

Abstract

2.

Hatia Sub-Station

3.

Description Of Grid Sub-Station Hatia-I

4.

Single Line Diagram Of 132kV/33kV GSS Hatia-I

5.

Description Of Grid Sub-Station Hatia-II

6.

Single Line Diagram Of 132kV/33kV GSS Hatia-II

7.

Representation Of How Power Is Generated & Supplied To Industries & Household

8.

Main Equipment Used In a Sub-Station

9.

Control Room Equipment

10.

Transformer

11.

Current Transformer

12.

Potential Transformer

13.

Bus Bar

14.

Isolators

5 of 29

6 of 29

INDEX

Sr. No.

Topic

15.

Relays

16.

Circuit Breaker

17.

Wave Trap

18.

Lightning Arrestor

19.

Bus Coupler

20.

DC System

21.

PLCC

22.

Earthing

23.

Conclusion

7 of 29

ABSTRACT

  • Working of GSS Hatia-1 – The incoming power is of 132KV which is fed to Bus Bar (132 Main Bus) through LA, isolator, circuit breaker (CB), current transformer (CT) combination. The power from main is fed to different 132KV Outgoing Line and also into 4x50MVA Power Transformer which is stepped down to voltage of 33KV and fed to bus bar (33KV Main Bus) from which different loads is tapped to distribution substations.
  • Working of GSS Hatia-2 – The incoming power is of 220KV which is fed to Bus Bar (220KV Main Bus) through LA, Isolators, Circuit Breaker, Current Transformer combination. The power from main is fed to different 220KV Outgoing Line and also into 3x150MVA Power Transformer which is stepped down to voltage of 132KV and fed to bus bar (132KV Main Bus) from which different loads is tapped to grid (Hatia-1) substation.

8 of 29

HATIA SUB-STATION

  • The Sub-station consists of Grid 1(132/33 KV) and Grid 2(220/132 KV) capacity with the total transformation capacity: 3x150 MVA= 450 MVA.
  • The Sub-Station is responsible for supplying power to various parts of Ranchi as well as Lohardaga and various parts of Jharkhand.

​

9 of 29

DESCRIPTION OF GRID SUB-STATION�HATIA-I

  • Type: Grid sub-station Hatia-l is outdoor type of sub-station
  • Rating: The rating of GSS HATIA-I is 132/33 KV.
  • Capacity: The capacity of GSS HATIA-I is 200 MVA. In this GSS there are four transformers and each power is 50 MVA.
  • Main Source of incoming Power: There are three main source of incoming power. 1. Sub-station Hatia-2 (220/132 KV) 2. Patratu thermal power station GSS (220/132 KV) 3. Sikidiri Hydro power plant (220/132 KV)
  • 132KV Incoming/Outgoing (Bidirectional) Transmission Line: There are nine incoming/outgoing transmission lines: 1.Hatia-2 Circuit-I / Hatia –I GSS 2.Hatia-2 circuit-2 3.Hatia-2 circuit-3 4.Namkum GSS 5.PTPS (9C) 6.Kamdara 7.Tamar(Chandil) 8.Sikidri 9.Kanke(8C)
  • 132KV Outgoing Transmission Line: There are four outgoing transmission line: 1.HEC (8C) Line 2.HEC (9C) Line 3. Railway Circuit-1 4.Railway Circuit-2.
  • 33KV Outgoing Feeder: There are eleven outgoing feeder: 1.Rajbhawan Line 2.Vidhansabha Line 3.Harmu Line 4.Ratu Line 5.Bero Line 6.Tatisilwai Line 7.Brambe Line 8.Kanke Line 9. Dhurwa Line 10.D Sail Line 11.Argora Line.

​

​

​

​

​

​

​

​

​

​

10 of 29

SINGLE LINE DIAGRAM OF 132/33KV GSS HATIA-1

11 of 29

DESCRIPTION OF GRID SUB STATION �HATIA-2

  • Type: Grid sub-station Hatia-2 is outdoor type of sub-station
  • Rating: The rating of GSS HATIA-II is 220/132 KV.
  • Power Capacity: Total 3 auto-power transformers, i.e. Inter-connecting transformers ICT l, ICT Il and ICT Ill, of 150 MVA rating each are installed in the GSS HATIA-II. Thus, the apparent power capacity is 3*150MVA=450MVA. The real power capacity of the sub-station is 3*120MW=360MW.
  • Main Source of incoming Power: 1.220kV Power Grid Corporation of India Limited I or PGCIL I 2.220kV PGCIL-II 3.220kV PGCIL-III 4. 220kV Patratu Thermal Power Station I 5.220kV PTPS-II
  • 132kV Outgoing feeders: 1.Lohardaga-I 2.Lohardaga-II 3.Namkumb 4.Kanke-I 5.Kanke-II 6.Hatia-I 7.Hatia-II
  • In the 220 kV side of the HATIA-II GSS, there are total 3 Bus Bars. 2 main Bus Bars and 1 auxiliary bus/transfer bus, to ensure power continuity without interruption in case of fault in the main buses. The isolators connected to the Bus Bar is in sequence, but for other, it is in diagonal owing to space congestion. The transfer of power/line from either of the main bus to transfer bus is accomplished by transfer bus coupler. If the maintenance of the equipment’s associated with one of the main buses is to be carried out, then Bus Bar coupler is used to couple one bus to the other without any interruption in power supply and without creating hazardous arcs.

​

​

​

​

​

​

​

​

12 of 29

SINGLE LINE DIAGRAM OF 132/33KV GSS HATIA-2

13 of 29

REPRESENTATION OF HOW POWER IS GENERATED & SUPPLIED TO INDUSTRIES & HOUSEHOLD.�

14 of 29

MAIN EQUIPMENTS USED IN A SUBSTATION

A substation is an assembly of various electrical equipment’s connected to step down electric power at higher voltages and to clear faults in the system. The various electrical equipment’s used in the substation are as follows: - 1. Power Transformers (ICT)

2. Instrument Transformers i.e., CT and CVT

3. Bus Bars

4. Isolators

5. Relays

6. Circuit Breakers

7. Lightening Arrestors

8. Wave Trap

​

15 of 29

CONTROL ROOM EQUIPMENTS

  • Indicating and Metering Instruments - Ammeters, Voltmeters, Wattmeter, kWh meters. KVARH meters, power factor meters, reactive volt-amperes’ meters are installed in substations to control and maintain a watch over the current flowing through the circuits and over the power loads.
  • Batteries - In electric power stations and large capacity substations, the operation and automatic control circuits, the protective relay system, as well as emergency lighting circuits, are supplied by station batteries. Storage batteries are two types lead acid battery and acid-alkaline batteries. Lead acid battery is most commonly used in power stations and substations because their voltage is high and very cheap low voltage.
  • Relay - The relay is a sensing device which senses the fault, then determines its location and finally, it sends tripping commands to the circuit. The circuit breaker after getting the command from the relay disconnects the faulted element. Relays protect the equipment from damage and hence subsequent hazards like fire, the risk to the life are reduced by removing the particularly faulted section.
  • Control Panel - The substation control is design to form automated control systems (SCADA) of the traction substations, using digital protection programmable logic controllers.

16 of 29

TRANSFORMER

  • A transformer is a passive component that transfers electrical energy from one electrical circuit to another circuit, or multiple circuits.

​

17 of 29

CURRENT TRANSFORMER

The Current Transformer (C.T.), is a type of "instrument transformed that is designed to produce an alternating current in its secondary winding which is proportional to the current being measured in its primary. Current transformers reduce high voltage currents to a much lower value and provide a convenient way of safely monitoring the actual electrical current flowing in an AC transmission line using a standard ammeter. The principal of operation of a basic current transformer is slightly different from that of an ordinary voltage transformer.

Function - Current transformers perform the following functions:

1. Current transformers supply the protective relays with the currents of magnitude proportional to those of power circuit but sufficiently reduced in magnitude.

2. The measuring devices cannot be directly connected to high magnitude supplies. Hence current transformers are used to supply those devices with currents of magnitude proportional to those of power.

3. A current transformer also isolates the measuring instruments from high voltage circuits.

 

​

​

18 of 29

POTENTIAL (VOLTAGE) TRANSFORMER

The potential transformer may be defined as an instrument transformer used for the transformation of voltage from a higher value to the lower value. This transformer steps down the voltage to a safe limit value which can be easily measured by the ordinary low voltage instrument like a voltmeter, wattmeter and watt-hour meters, etc.

The secondary voltage of the PT is generally 110 V. In an ideal potential transformer or voltage transformer, when rated burden gets connected across the secondary; the ratio of primary and secondary voltages of transformer is equal to the turns ratio and furthermore, the two terminal voltages are in precise phase opposite to each other.

Function - The function of potential transformer is just like a theory of general purpose step-down transformer. Primary of this transformer is connected across the phase and ground. Potential transformer has lower turns winding at its secondary.

19 of 29

BUS-BAR

In electrical power distribution, a bus bar is a thick strip of copper or aluminium that conducts electricity within a switchboard, distribution board, substation, or other electrical apparatus. Bus bars are used to carry very large currents, or to distribute current to multiple devices within switchgear or equipment. Bus bars are typically either flat strips or hollow tubes as these shapes allow heat to dissipate more efficiently due to their high surface area to cross sectional area ratio. The size of the bus bar is important in determining the maximum amount of current that can be safely carried.

Bus bar may either be supported on insulators, or else insulation may completely surround it. Bus bars are protected from accidental contact either by a metal enclosure or by elevation out of normal reach. Bus bars may be connected to each other and to electrical apparatus by bolted or clamp connections.

​

​

20 of 29

ISOLATOR

In electrical systems, an isolator switch is used to make sure that an electrical circuit is completely de-energized for service or maintenance. Such switches are often found in electrical distribution and industrial applications where machinery must have its source of driving power removed for adjustment or repair. High voltage isolation switches are used in electrical substations to allow isolation of apparatus such as circuit breakers and transformers, and transmission lines, for maintenance.

An isolator can open or close the circuit when either a negligible current has to be broken or made or when no significant voltage change across the terminals of each pole of isolator occurs. It can carry current under normal conditions and can carry short circuit current for a specified time. They can transfer load from one bus to another and also isolate equipment’s for maintenance. Isolators guarantee safety for the people working on the high voltage network, providing visible and reliable air gap isolation of line sections and equipment. They are basically motorized i.e., motor does the closing and opening of the isolator. Isolators are distinguished as "off load" and "on load" isolator.

​

21 of 29

RELAYS

A relay is an electrically operated switch. Many relays use an electromagnet to operate a switching mechanism mechanically, but other operating principles are also used. Relays are used where it is necessary to control a circuit by a low-power signal (with complete electrical isolation between control and controlled circuits), or where several circuits must be controlled by one signal. Relays with calibrated operating characteristics and sometimes multiple operating coils are used to protect electrical circuits from overload or faults; in modem electric power systems these functions are performed by digital instruments still called "protective relays".

Types of Relays –

  1. Electromagnetic Attraction Relay
  2. Electromagnetic Induction Relay
  3. Thermal Relay
  4. Buccolz Relay
  5. Numerical Relay
  6. Over Current Relay

22 of 29

CIRCUIT BREAKER

A circuit breaker is an automatically operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit. Its basic function is to detect a fault condition and, by interrupting continuity, to immediately discontinue electrical flow. Unlike a fuse, which operates once and then has to be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation. Circuit breakers are made in varying sizes, from small devices that protect an individual household appliance up to large switchgear designed to protect high voltage circuits feeding an entire city.

The type of the Circuit Breaker is usually identified according to the medium of arc extinction. The classification of the Circuit Breakers based on the medium of arc extinction is as follows:

  • Air break Circuit Breaker.
  • Oil Circuit Breaker (tank type of bulk oil)
  • Minimum oil Circuit Breaker.
  • Air blast Circuit Breaker.
  • Vacuum Circuit Breaker.
  • Sulphur hexafluoride Circuit Breaker. (Single pressure or Double Pressure).

23 of 29

WAVE TRAP

It is an inductor having tuned LC circuit, which is mainly used for PLCC purpose. It offers very high impedance to high frequency PLCC signals does not allow them to enter in S/Y and offers very low impedance for frequency currents.

​

24 of 29

LIGHTNING ARRESTOR

A lightning arrester is a device used on electrical power systems and telecommunications systems to protect the insulation and conductors of the system from the damaging effects of lightning. The typical lightning arrester has a high-voltage terminal and a ground terminal. When a lightning surge (or switching surge, which is very similar) travels along the power line to the arrester, the current from the surge is diverted through the arrestor, in most cases to earth.

If protection fails or is absent, lightning that strikes the electrical system introduces thousands of kilovolts that may damage the transmission lines, and can also cause severe damage to transformers and other electrical or electronic devices. Lightning-produced extreme voltage spikes in incoming power lines can damage electrical home appliances.

25 of 29

BUS COUPLER

Bus coupler is a device which is used to couple one bus to the other without any interruption in power supply and without creating hazardous arcs. Bus coupler is a breaker used to couple two busbars in order to perform maintenance on other circuit breakers associated with that busbar.

It is achieved with the help of a circuit breaker and isolators.

​

26 of 29

DC SYSTEM

The term DC is used to refer to power systems that use only one polarity of voltage or current, and to refer to the constant, zero-frequency, or slowly varying local mean value of a voltage or current.

Power substation can have one or several DC systems. Factors affecting the number of systems are the need of more than one voltage level and the need of duplicating systems.

The DC system is the most important component of a high voltage industrial/utility substation. It supplies the energy needed to manage the protective devices and high voltage components and allows electrical faults to be safely isolated. Most high voltage substations house either a sealed or flooded cell battery bank.

​

27 of 29

PLCC

Power-Line Communication Carrier (also known as power-line carrier or PLCC) carries data on a conductor that is also used simultaneously for AC electric power transmission or electric power distribution to consumers. Wave trap is used for this purpose.

A wide range of power-line communication technologies are needed for different applications, ranging from home automation to Internet access which is often called broadband over power lines (BPL). Most PLC technologies limit themselves to one type of wires (such as premises wiring within a single building), but some can cross between two levels (for example, both the distribution network and premises wiring). Typically, transformers prevent propagating the signal, which requires multiple technologies to form very large networks. Various data rates and frequencies are used in different situations.

​

28 of 29

EARTHING

We connect all the points to be earthed with the earthing grid with corrosion resistance mild steel rods. We bury the connection rods a minimum 600mm below the ground level. If these horizontally buried rods cross a cable trench, road, underground pipework, or rail track the rods should cross the barriers at least 300 mm below the bottom of the barriers.

The points we must earth in an electrical substation should include:

1. The neutral point of different voltage levels.

2. The metallic enclosure of all the current carrying equipment.

3. The framework of all the current carrying equipment.

4. All the metallic structure even not associated with current carrying equipment.

​

29 of 29

CONCLUSION

The past fortnight of our training has been very enlightening for us. JUSNL GSS HATIA-I and II gave us opportunities to learn and develop our self in many areas. We gained a lot of experience, especially in the substations, switchgears, equipment and protection field. A Lot of the tasks and activities that we worked on during our VT, we were already familiar with what we are studying at the moment.

There is a big difference in the college projects and the tasks and activities during the actual work, in college we learn how to describe the work in projects where in work we learn how to implement them in reality. This VT was definitely an introduction to the actual work field for us.

We learned a lot from the engineers at Hatia I & Il during our internship. They have lot of knowledge of the working area and were very helpful and always willing to give us advice, which I appreciate. The way in which they related the actual components in the yard, to the elements in the SLD, made everything crystal clear.