1 of 13

AY: 2021 – 22 �BRANCH : ELECTRICAL ENGINEERING�SEMESTER : 4TH �SUBJECT : ENERGY CONVERSION – I

Chapter : 05�Topic : Instrument TransformerPREPARED BY : ER Subhalaxmi Rout

2 of 13

contents

  • Current Transformer
  • Ratio Error
  • Phase angle Error
  • Burden

  • Potential Transformer
  • Ratio Error
  • Phase angle Error
  • Burden

3 of 13

Current Transformer

  • Primary winding has single turn winding and carries full load current.
  • Secondary winding has large number of turns.
  • Ratio of the primary current and secondary current is known as current transformer (CT) ratio.

4 of 13

Current Transformer

Phasor diagram:

  • The main flux is taken as reference.
  • The primary and secondary voltages are lagging behind the main flux by 90 degrees.
  • The magnitudes of the primary and secondary voltage s depend on the number of turns in the windings.

5 of 13

Current Transformer

Ratio Error:

6 of 13

Current Transformer

Phase angle Error:

  • The phase angle between primary and secondary of the current transformer must be 180 degree.
  • The primary and secondary current must be out of phase. The deviation in the phase angle of the primary and secondary current is called the phase angle error.
  • The phase angle between primary and secondary current of the CT is denoted by angle θ.

7 of 13

Current Transformer

  • As high current is stepped down to lower value, open CT secondary will cause 0A current in secondary, which will ultimately lead to a high voltage which may burn the CT secondary winding and can damage the system.
  • So it is necessary to load the CT secondary continuously and ultimately it acts a burden on CT, and that’s why the load on CT is named as a burden.

8 of 13

potential Transformer

  • It is an instrument transformer used for the transformation of voltage from a higher value to the lower value. This transformer step down the voltage to a safe limit value which can be easily measured by the ordinary low voltage instrument like a voltmeter, wattmeter and watt-hour meters, etc.

9 of 13

potential Transformer

  • The main flux is taken as a reference. The primary current is the vector sum of the excitation current Io and the current equal to the reversal secondary current Imultiplied by the ratio of 1/kt. The Vp is the voltage applied to the primary terminal of the potential transformer.
  • The voltage drops due to resistance and reactance of primary winding due to primary current is given by IpXp and IpRp.
  • This primary emf of the transformer will transform into secondary winding by mutual induction and converted into secondary induced emf Es. This emf will drop by the secondary winding resistance and reactance, and the resultant voltage will appear across the secondary terminal voltage Vs..

10 of 13

potential Transformer

Ratio Error –

  • The ratio error is the change in the voltage ratio due to the variation in load. Varying load changes the magnetizing current & the core losses that affect the secondary voltage of the PT.
  • In simple words, its nominal ratio differs from its actual ratio. Ratio error is given by

Ratio Error = (Nominal Ratio – Actual Ratio) / Actual Ratio

Ratio Error = (Kn – R)/R

% Ratio Error = {(Kn – R)/R} x 100

Where

Kn = Nominal Ratio (Rated Ratio)

R = Actual primary to secondary voltage Ratio

The nominal ratio is the ratio of rated primary voltage to rated secondary voltage.

11 of 13

potential Transformer

Phase angle error:

  • The phase angle error is the difference between the phase of primary voltage & the reversed secondary voltage.
  • Ideally, the primary voltage is in phase with the secondary voltage in reverse.
  • But practically, there is the reactance of the windings that shifts the phase of the secondary voltage creating phase angle error.
  • The increases in the number of instruments in the relay connected to the secondary of the potential transformer will increase the errors in the potential transformers.

� �

12 of 13

potential Transformer

Burden:

  • The burden is the total external volt-amp load on the secondary at rated secondary voltage.
  • The rated burden of a PT is a VA burden which must not be exceeded if the transformer is to operate with its rated accuracy.
  • The limiting or maximum burden is the greatest VA load at which the potential transformer will operate continuously without overheating its windings beyond the permissible limits.
  • This burden is several times greater than the rated burden.�

13 of 13

THANK YOU