Conveyors and Continuous Transport
CHAPTER 5
Automation of continuous transport mechanisms: conveyors, escalators, ropeways, excavators
Electrical Control of Industrial Mechanisms
Master 1, Semester 3 · 2025–2026 · Prof. Z. TIR — University of El Oued
Photo: Leonhard Lenz, CC BY-SA 4.0, Wikimedia Commons
What you will be able to do
CHAPTER 5 · LEARNING OUTCOMES
1
Size a conveyor drive from its belt pull, and its take-up tension
2
Design a start that respects the elastic belt
3
Design a master–slave or droop load-sharing scheme
4
Analyse escalators and ropeways: safety chain, limits, power
5
Match a bucket-wheel excavator to its conveyors
Lectures, Fig. 5.1
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 2
Meet the reference conveyor of the chapter
5.1 · REFERENCE CONVEYOR
Quantity | Value | Remember it as |
Length, speed | 400 m horizontal, 2.5 m/s | a plant or quarry conveyor |
Mass per metre | material 90, belt 25, idlers 20 kg/m | 64 t moving in total |
Resistance (DIN 22101) | 17.3 kN, 48 kW | twice the lumped estimate |
Belt stiffness | EA = 15 MN → c = 306 m/s | natural period 5.2 s |
Drives | 2 × 30 kW, head + intermediate | master–slave or droop |
!
The same conveyor is simulated in Simscape and sized in Tutorial Exercise 5.1
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 3
A constant-torque load sized from the belt pull
5.1 · CONVEYOR DRIVES
Lectures, Fig. 5.1
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 4
Sizing an inclined conveyor drive
5.1 · WORKED EXAMPLE
GIVEN
L = 120 m, lift H = 14 m, v = 1.6 m/s; belt 22 kg/m, material 55 kg/m; f = 0.022; η = 0.9
FIND
The effective pull and the standard motor rating
Photo: Leonhard Lenz, CC BY-SA 4.0, Wikimedia Commons
SOLUTION
✓
Check. Lift = potential-energy rate (55 × 1.6) × 9.81 × 14 ≈ 12.1 kW, nearly four times the friction term.
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 5
Where the resistance really comes from
5.1 · DIN 22101
Lectures, Fig. 5.2
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 6
Short conveyors are power-hungry per tonne
5.1 · DIN 22101
Lectures, Fig. 5.2
→
Secondary resistance: about one third of the total at 20 m, barely 1 % at 2 km (C falls from 3.0 to 1.05)
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 7
The belt is an elastic body
5.1 · STARTING AND STOPPING
Photo: byrev, CC0, Wikimedia Commons
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 8
How long must the start ramp be?
5.1 · STARTING
Lectures, Fig. 5.3
→
Ramp several belt periods long. Below ta/Tn ≈ 2 the S-curve is worse than a linear ramp: its peak acceleration is 1.5× the mean
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 9
The tension wave, simulated along the belt
5.1 · STARTING
Lectures, Fig. 5.4
→
2 s ramp: the tail moves 1.31 s after the head (c ≈ 306 m/s) and the head peaks near 7× running. 16 s S-curve: below 2×
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 10
Starting the reference conveyor
5.1 · WORKED EXAMPLE
GIVEN
Reference conveyor: 64 t moving, 17.3 kN running pull, two 30 kW drives (10.8 kN each at the belt, 150 % short-time); 16 s S-curve to 2.5 m/s
FIND
The ramp in natural periods, the peak starting force, the drive overload
SOLUTION
✓
Check. An 8 s ramp would double the inertial force (47 kN in total, 2.2× rated per drive): too short for the drives and for the belt.
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 11
Control of multi-motor systems
5.2
Several motors on one belt will fight each other unless the controller tells them how to share.
Lectures, Fig. 5.5
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 12
Master–slave or droop
5.2 · LOAD SHARING
Lectures, Fig. 5.5
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 13
Choosing a droop setting
5.2 · WORKED EXAMPLE
GIVEN
Two 30 kW drives on one belt, kd = 0.03 (3 % droop). A mismatch loads drive 1 to 110 % and drive 2 to 90 %. Belt 2.5 m/s.
FIND
The corrective speed difference, and the price paid at full load
SOLUTION
✓
Check. 2.5 × (1 − 0.03) = 2.425 m/s; the simulation shows 2.44 m/s because each drive is a little below rated torque.
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 14
Both schemes simulated, including a fieldbus failure
5.2 · LOAD SHARING
Lectures, Fig. 5.6
→
Healthy bus: both share 50/50. Bus lost at 35 s: master–slave drifts to 42/58, droop stays 50/50 — but runs at 2.44 m/s
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 15
Protection distributed along the belt
5.2 · PROTECTION
Lectures, Fig. 5.7
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 16
Start against the flow, stop with it
5.2 · SEQUENCE INTERLOCKING
Lectures, Fig. 5.8
→
Start from the discharge end, each belt proven at speed. Normal stop from the feed end with run-on. Emergency stop: all at once
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 17
Screws, bucket elevators, chains and air
5.2 · OTHER MECHANISMS
Lectures, Fig. 5.9
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 18
Passenger transport systems
5.3
Escalators and ropeways: the drive is subordinate to safety.
Photo: Stig Nygaard from Copenhagen, Denmark, CC BY 2.0, Wikimedia Commons
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 19
Escalator: seven devices, one series chain
5.3 · ESCALATORS
Photo: Stig Nygaard from Copenhagen, Denmark, CC BY 2.0, Wikimedia Commons
Lectures, Fig. 5.10
→
All contacts NC and in series: any one — or a broken wire — removes the enable and applies the brake
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 20
Power of a busy escalator
5.3 · WORKED EXAMPLE
GIVEN
Rise 6 m at 30°, 0.5 m/s; 4500 passengers an hour of 75 kg; no-load losses 3 kW
FIND
The power upwards, and what changes downwards
Photo: Stig Nygaard from Copenhagen, Denmark, CC BY 2.0, Wikimedia Commons
SOLUTION
✓
Check. 12 m incline at 0.5 m/s = 24 s per passenger: about 30 people, 2.2 t, on the steps at once — the load the brake must stop.
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 21
Ropeways: redundancy because nobody can get off
5.3 · ROPEWAYS
Lectures, Fig. 5.11
Photo: PetrS., CC BY-SA 3.0, Wikimedia Commons
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 22
Integrated systems: the bucket-wheel excavator
5.4
Every mechanism of the course in one machine, coordinated so the material won matches the material carried.
Photo: byrev, CC0, Wikimedia Commons
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 23
Coordinating many high-power drives
5.4 · BUCKET-WHEEL EXCAVATOR
Lectures, Fig. 5.12
Photo: byrev, CC0, Wikimedia Commons
→
Output 60·z·n·Vb·φ must fit the conveyors; the cut thins as cos φ, so the slew speeds up as 1/cos φ
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 24
Common mistakes with conveyors
WATCH OUT
✗
MYTH
“Two identical motors on one belt share the load equally.”
✓
WHAT IS TRUE
Small differences in slip, gear ratio or pulley diameter make one take more — even motor while the other generates. Sharing needs master–slave or droop.
✗
MYTH
“Droop is inferior because it lets the speed sag.”
✓
WHAT IS TRUE
The sag is the sharing mechanism, and it needs no communication. Speed regulation against robustness: neither scheme is always better.
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 25
Two more traps
WATCH OUT
✗
MYTH
“More motor torque cures a slipping drive pulley.”
✓
WHAT IS TRUE
Slip is set by the tension ratio T1/T2 ≤ eμθ. More torque makes it worse; the cure is take-up tension, wrap, lagging or a second drive.
✗
MYTH
“Starting a loaded conveyor is like starting it empty.”
✓
WHAT IS TRUE
A loaded belt has a large breakaway torque and huge inertia; an abrupt start sends a splice-damaging tension wave. Ramped, jerk-limited starts are a mechanical need.
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 26
Quick check — try before you look
SELF-CHECK 5.1–5.6
5.1
17.3 kN over a pulley with eμθ = 3.39: slack-side tension the take-up must supply?
5.2
What keeps the belt from slipping on the drive pulley, and which sensor detects slip?
5.3
Why does a line of conveyors start from the discharge end and stop from the feed end?
5.4
Why must the start ramp of a long belt last several times its natural period?
5.5
Two drives with 3 % droop, momentarily at 105 % and 95 %: speed-reference difference?
5.6
Why is a pull-cord switch reset at the switch, not from the control room?
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 27
Summary
CHAPTER 5 · SUMMARY
KEY EQUATIONS
Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued
Chapter 5 · 28
Practise this
CHAPTER 5 · NEXT STEPS
TD
Tutorials
Exercises 5.1–5.7: sizing and take-up, incline, start, load sharing, sequencing, escalator, excavator.
TP
Lab works
TP 5 — conveyor line and brick sorting on the PLC-200.
?
Before next week
Redo the self-check questions; then read Chapter 6 §6.1 on rolling mills.