1 of 30

Conveyors and Continuous Transport

CHAPTER 5

Automation of continuous transport mechanisms: conveyors, escalators, ropeways, excavators

Electrical Control of Industrial Mechanisms

Master 1, Semester 3 · 2025–2026 · Prof. Z. TIR — University of El Oued

Photo: Leonhard Lenz, CC BY-SA 4.0, Wikimedia Commons

2 of 30

What you will be able to do

CHAPTER 5 · LEARNING OUTCOMES

1

Size a conveyor drive from its belt pull, and its take-up tension

2

Design a start that respects the elastic belt

3

Design a master–slave or droop load-sharing scheme

4

Analyse escalators and ropeways: safety chain, limits, power

5

Match a bucket-wheel excavator to its conveyors

Lectures, Fig. 5.1

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 2

3 of 30

Meet the reference conveyor of the chapter

5.1 · REFERENCE CONVEYOR

Quantity

Value

Remember it as

Length, speed

400 m horizontal, 2.5 m/s

a plant or quarry conveyor

Mass per metre

material 90, belt 25, idlers 20 kg/m

64 t moving in total

Resistance (DIN 22101)

17.3 kN, 48 kW

twice the lumped estimate

Belt stiffness

EA = 15 MN → c = 306 m/s

natural period 5.2 s

Drives

2 × 30 kW, head + intermediate

master–slave or droop

!

The same conveyor is simulated in Simscape and sized in Tutorial Exercise 5.1

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 3

4 of 30

A constant-torque load sized from the belt pull

5.1 · CONVEYOR DRIVES

  • Belt, roller and chain conveyors: torque nearly independent of speed
  • Effective pull Fe = T1 − T2 at the drive pulley
  • No slip while T1/T2 ≤ eμθ: take-up must supply T2 ≥ Fe/(eμθ − 1)
  • Torque fixed by Fe; power proportional to belt speed — ideal for a VFD

Lectures, Fig. 5.1

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 4

5 of 30

Sizing an inclined conveyor drive

5.1 · WORKED EXAMPLE

GIVEN

L = 120 m, lift H = 14 m, v = 1.6 m/s; belt 22 kg/m, material 55 kg/m; f = 0.022; η = 0.9

FIND

The effective pull and the standard motor rating

Photo: Leonhard Lenz, CC BY-SA 4.0, Wikimedia Commons

SOLUTION

  1. Friction: 0.022 × 9.81 × 120 × 77 ≈ 1.99 kN
  2. Lift: 55 × 9.81 × 14 ≈ 7.55 kN
  3. Fe ≈ 1.99 + 7.55 = 9.54 kN
  4. P = 9540 × 1.6 / 0.9 ≈ 17.0 kW → 18.5 kW standard motor

✓

Check. Lift = potential-energy rate (55 × 1.6) × 9.81 × 14 ≈ 12.1 kW, nearly four times the friction term.

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 5

6 of 30

Where the resistance really comes from

5.1 · DIN 22101

  • Primary FH: idler friction, belt indentation and flexing, along both strands
  • Secondary FN = (C − 1)FH: loading point, skirts, cleaners, pulleys
  • Slope FSt = m'LgH: the only recoverable term
  • Special FS: tilted idlers, ploughs, extra cleaners
  • Worked example: 1.99 kN simplified, 3.06 kN by DIN

Lectures, Fig. 5.2

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 6

7 of 30

Short conveyors are power-hungry per tonne

5.1 · DIN 22101

Lectures, Fig. 5.2

→

Secondary resistance: about one third of the total at 20 m, barely 1 % at 2 km (C falls from 3.0 to 1.05)

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 7

8 of 30

The belt is an elastic body

5.1 · STARTING AND STOPPING

  • Tension changes travel at c = √(EA/m'): 306 m/s; natural period Tn ≈ 4L/c = 5.2 s
  • An abrupt start launches a tension wave: the peak damages splices
  • Huge translational inertia: ramps of tens of seconds are normal
  • Fluid coupling, wound rotor, now VFD with S-curve
  • Incline: backstop. Decline: regenerates for its whole life

Photo: byrev, CC0, Wikimedia Commons

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 8

9 of 30

How long must the start ramp be?

5.1 · STARTING

Lectures, Fig. 5.3

→

Ramp several belt periods long. Below ta/Tn ≈ 2 the S-curve is worse than a linear ramp: its peak acceleration is 1.5× the mean

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 9

10 of 30

The tension wave, simulated along the belt

5.1 · STARTING

Lectures, Fig. 5.4

→

2 s ramp: the tail moves 1.31 s after the head (c ≈ 306 m/s) and the head peaks near 7× running. 16 s S-curve: below 2×

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 10

11 of 30

Starting the reference conveyor

5.1 · WORKED EXAMPLE

GIVEN

Reference conveyor: 64 t moving, 17.3 kN running pull, two 30 kW drives (10.8 kN each at the belt, 150 % short-time); 16 s S-curve to 2.5 m/s

FIND

The ramp in natural periods, the peak starting force, the drive overload

SOLUTION

  1. 16 / 5.2 ≈ 3 natural periods: safely right of the crossover
  2. Mean a = 2.5/16 = 0.156 m/s²; S-curve peak 1.5× = 0.234 m/s²
  3. Inertial force 64 000 × 0.234 = 15.0 kN; total 32.3 kN = 1.87 × running
  4. Per drive 16.1 kN = 1.5 × rated for a few seconds

✓

Check. An 8 s ramp would double the inertial force (47 kN in total, 2.2× rated per drive): too short for the drives and for the belt.

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 11

12 of 30

Control of multi-motor systems

5.2

Several motors on one belt will fight each other unless the controller tells them how to share.

Lectures, Fig. 5.5

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 12

13 of 30

Master–slave or droop

5.2 · LOAD SHARING

  • Master–slave: one drive in speed control, the others follow its torque over the fieldbus
  • Droop: every drive in speed control, reference lowered in proportion to its own load
  • Master–slave: stiff, exact speed, but needs the bus and a master
  • Droop: no communication, degrades gracefully, small speed error

Lectures, Fig. 5.5

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 13

14 of 30

Choosing a droop setting

5.2 · WORKED EXAMPLE

GIVEN

Two 30 kW drives on one belt, kd = 0.03 (3 % droop). A mismatch loads drive 1 to 110 % and drive 2 to 90 %. Belt 2.5 m/s.

FIND

The corrective speed difference, and the price paid at full load

SOLUTION

  1. Δω*/ω*0 = kd(1.10 − 0.90) = 0.03 × 0.20 = 0.6 %
  2. Drive 2 now runs faster and picks up load until the imbalance closes
  3. Price: at full load both run 3 % slow: 2.5 × 0.97 ≈ 2.43 m/s
  4. A larger kd stiffens the sharing but worsens the speed error

✓

Check. 2.5 × (1 − 0.03) = 2.425 m/s; the simulation shows 2.44 m/s because each drive is a little below rated torque.

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 14

15 of 30

Both schemes simulated, including a fieldbus failure

5.2 · LOAD SHARING

Lectures, Fig. 5.6

→

Healthy bus: both share 50/50. Bus lost at 35 s: master–slave drifts to 42/58, droop stays 50/50 — but runs at 2.44 m/s

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 15

16 of 30

Protection distributed along the belt

5.2 · PROTECTION

Lectures, Fig. 5.7

  • Pull cords both sides, full length; reset only at the switch
  • Belt-drift switch pairs: outer alarms, inner trips
  • Zero-speed sensor on the tail (non-driven) pulley: detects slip
  • Chute-blockage and belt-tear detectors; backstop on inclines

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 16

17 of 30

Start against the flow, stop with it

5.2 · SEQUENCE INTERLOCKING

Lectures, Fig. 5.8

→

Start from the discharge end, each belt proven at speed. Normal stop from the feed end with run-on. Emergency stop: all at once

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 17

18 of 30

Screws, bucket elevators, chains and air

5.2 · OTHER MECHANISMS

Lectures, Fig. 5.9

  • Screw conveyor: sized on breakaway torque; shear pin or torque limit
  • Bucket elevator: backstop and zero-speed monitor; dust ignition risk
  • Chain: polygon effect — the speed dips once per tooth
  • Pneumatic conveying is a blower problem (Roots blower: constant torque)

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 18

19 of 30

Passenger transport systems

5.3

Escalators and ropeways: the drive is subordinate to safety.

Photo: Stig Nygaard from Copenhagen, Denmark, CC BY 2.0, Wikimedia Commons

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 19

20 of 30

Escalator: seven devices, one series chain

5.3 · ESCALATORS

Photo: Stig Nygaard from Copenhagen, Denmark, CC BY 2.0, Wikimedia Commons

Lectures, Fig. 5.10

→

All contacts NC and in series: any one — or a broken wire — removes the enable and applies the brake

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 20

21 of 30

Power of a busy escalator

5.3 · WORKED EXAMPLE

GIVEN

Rise 6 m at 30°, 0.5 m/s; 4500 passengers an hour of 75 kg; no-load losses 3 kW

FIND

The power upwards, and what changes downwards

Photo: Stig Nygaard from Copenhagen, Denmark, CC BY 2.0, Wikimedia Commons

SOLUTION

  1. Mass flow 4500 × 75 / 3600 = 93.8 kg/s
  2. Lifting 93.8 × 9.81 × 6 = 5.5 kW; with losses about 8.5 kW upwards
  3. Downwards the passengers deliver 5.5 kW > 3 kW losses
  4. The motor generates about 2.5 kW

✓

Check. 12 m incline at 0.5 m/s = 24 s per passenger: about 30 people, 2.2 t, on the steps at once — the load the brake must stop.

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 21

22 of 30

Ropeways: redundancy because nobody can get off

5.3 · ROPEWAYS

Lectures, Fig. 5.11

  • Main motor turns the bullwheel; an independent diesel-hydraulic drive backs it up
  • Service brake on the motor shaft, emergency brake on the bullwheel rim
  • Tension carriage keeps the rope tension — and the friction grip — constant
  • Continuous supervision: rope speed, rope tension, carrier spacing

Photo: PetrS., CC BY-SA 3.0, Wikimedia Commons

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 22

23 of 30

Integrated systems: the bucket-wheel excavator

5.4

Every mechanism of the course in one machine, coordinated so the material won matches the material carried.

Photo: byrev, CC0, Wikimedia Commons

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 23

24 of 30

Coordinating many high-power drives

5.4 · BUCKET-WHEEL EXCAVATOR

Lectures, Fig. 5.12

Photo: byrev, CC0, Wikimedia Commons

→

Output 60·z·n·Vb·φ must fit the conveyors; the cut thins as cos φ, so the slew speeds up as 1/cos φ

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 24

25 of 30

Common mistakes with conveyors

WATCH OUT

✗

MYTH

“Two identical motors on one belt share the load equally.”

✓

WHAT IS TRUE

Small differences in slip, gear ratio or pulley diameter make one take more — even motor while the other generates. Sharing needs master–slave or droop.

✗

MYTH

“Droop is inferior because it lets the speed sag.”

✓

WHAT IS TRUE

The sag is the sharing mechanism, and it needs no communication. Speed regulation against robustness: neither scheme is always better.

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 25

26 of 30

Two more traps

WATCH OUT

✗

MYTH

“More motor torque cures a slipping drive pulley.”

✓

WHAT IS TRUE

Slip is set by the tension ratio T1/T2 ≤ eμθ. More torque makes it worse; the cure is take-up tension, wrap, lagging or a second drive.

✗

MYTH

“Starting a loaded conveyor is like starting it empty.”

✓

WHAT IS TRUE

A loaded belt has a large breakaway torque and huge inertia; an abrupt start sends a splice-damaging tension wave. Ramped, jerk-limited starts are a mechanical need.

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 26

27 of 30

Quick check — try before you look

SELF-CHECK 5.1–5.6

5.1

17.3 kN over a pulley with eμθ = 3.39: slack-side tension the take-up must supply?

5.2

What keeps the belt from slipping on the drive pulley, and which sensor detects slip?

5.3

Why does a line of conveyors start from the discharge end and stop from the feed end?

5.4

Why must the start ramp of a long belt last several times its natural period?

5.5

Two drives with 3 % droop, momentarily at 105 % and 95 %: speed-reference difference?

5.6

Why is a pull-cord switch reset at the switch, not from the control room?

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 27

28 of 30

Summary

CHAPTER 5 · SUMMARY

  • Constant-torque load: size from the effective pull; power ∝ belt speed
  • DIN 22101 counts both strands, idlers and end losses; take-up T2 ≥ Fe/(eμθ − 1)
  • The belt is elastic: ramps of several belt periods; S-curve only beyond ~2
  • Protection along the belt; start against the flow, stop with it
  • Multi-motor: master–slave (stiff, needs the bus) or droop (robust, speed error)
  • Passenger systems: NC chains, EN 115-1 limits; excavator slews as 1/cos φ

KEY EQUATIONS

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 28

29 of 30

Practise this

CHAPTER 5 · NEXT STEPS

TD

Tutorials

Exercises 5.1–5.7: sizing and take-up, incline, start, load sharing, sequencing, escalator, excavator.

TP

Lab works

TP 5 — conveyor line and brick sorting on the PLC-200.

?

Before next week

Redo the self-check questions; then read Chapter 6 §6.1 on rolling mills.

Photo: byrev, CC0, Wikimedia Commons

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 29

30 of 30

Image credits

CHAPTER 5 · SOURCES

  • Figures and diagrams: Lectures booklet, Electrical Control of Industrial Mechanisms (computed in Python/Simscape or drawn in TikZ from the chapter's own equations).
  • Conveyor belt at surface mine Schleenhain 01 — Leonhard Lenz, CC BY-SA 4.0, Wikimedia Commons, https://commons.wikimedia.org/wiki/File:Conveyor_belt_at_surface_mine_Schleenhain_01.jpg
  • Bucket wheel excavator in winter — byrev, CC0, Wikimedia Commons, https://commons.wikimedia.org/wiki/File:Bucket_wheel_excavator_in_winter.jpg
  • Copenhagen Metro escalators — Stig Nygaard from Copenhagen, Denmark, CC BY 2.0, Wikimedia Commons, https://commons.wikimedia.org/wiki/File:Copenhagen_Metro_escalators.jpg
  • Gondola of Skalnate pleso aerial tramway 1 — PetrS., CC BY-SA 3.0, Wikimedia Commons, https://commons.wikimedia.org/wiki/File:Gondola_of_Skalnate_pleso_aerial_tramway_1.JPG
  • Licence texts: creativecommons.org/licenses (CC BY, CC BY-SA); creativecommons.org/publicdomain/zero/1.0 (CC0). Photos are shown unmodified except for cropping and scaling.

Electrical Control of Industrial Mechanisms · Prof. Z. TIR — University of El Oued

Chapter 5 · 30