Contents
9
7. Protective measures for prevention of direct electrical contact
10
8. Safety devices
11
13
11. First-aid for electric shock
18
Attachment: Inspection checklist of electrical safety 19
Note:
3
1. Introduction
As a source of power, electricity is used in all aspects of life. In the home and at work, electricity provides the power for everything from domestic appliances to industrial machines, from office equipment to electric tools. When compared to the potential dangers of machinery and chemical substances, electrical hazards can be easily overlooked. Unfortunately, this neglect often causes serious accidents and loss of property. Many of these accidents can be prevented as they are mainly caused by electricity users who lack basic safety awareness.
4
2. Electrical safety legislation
The legislation involving electrical safety is the “Electricity Ordinance (Chapter 406)” as enforced by the Electrical and Mechanical Services Department and “Factories and Industrial Undertakings (Electricity) Regulations (Chapter 59)” enforced by the Labour Department.
The Ordinance requires that people engaged in electricity work, or with contractors and electricity generation facilities, must be registered. It also stipulates the safety requirements of electricity supply, electricity wiring and electrical products, etc.
There are several subsidiary regulations of the Electricity Ordinance, including:
The Regulations apply to industrial undertakings in which electricity is generated, transformed, distributed or used. The purpose is to supervise the safety of electrical facilities and working processes, etc. of relevant industry.
These table reviews the industrial accident statistics involving electricity in the past decade.
5
3. Sources of electricity
The electricity we used is mainly supplied by local electricity companies, and is connected to our homes, working places and other areas, through distribution systems.
Frequency: 50 Hz
Voltage: Single-phase: 220 Volts (V) alternating current 3-phase: 380 Volts (V) alternating current
The electricity used in our homes and offices is single-phase alternating current, and 3-phase alternating
current normally serves the industry.
6
4. Electricity principles
Ohm’s Law
A complete electrical circuit is composed of 3 elements: Current, Voltage and Resistance.
Their correlative relationship can be shown by the following formula:
V = I x R
The above formula applies to the human body during an electric shock, provided that the voltage remains constant and there is Resistance (R) in the human body. A reduction in resistance in the human body will lead to higher electrical currents passing through it, and any injury will be more serious.
Element | Unit | Abbreviation |
Voltage (V) Current (I) Resistance (R) | Volts Amperes Ohms | V A Ω |
7
Respiratory Failure
Electric shock may affect
normal brain function and stop respiration.
Heartbeat Failure
If current passes through
the heart, it will disrupt the rhythmic pumping action and eventually stop the heart beat.
Suffocation
Most accidents due to electric
shocks are caused by current passing through the chest. When such accidents occur, chest muscles cramp, leading to suffocation and death.
Unable to get free after an electric shock
An electric shock causes con-
tinuous contraction of the forearm muscles, thus stop- ping the victim getting free from the electric source.
5. Electrical hazards
5.1 Electric shock
Electric shock refers to the electricity passing through the human body, affecting the normal function of the heart, lungs and nervous system. Ventricular fibrillation caused by electricity is the main reason for death from electric shocks. Electric shocks may indirectly lead to accidents, e.g. falling from heights and bruising due to body trauma etc.
Ventricular fibrillation involves a series of disordered contractions of the heart’s ventricular muscle fibres, which prevents regular heartbeat. Under normal conditions, the human heart rate is from around 60 to 100 times per minute. During an electric shock, heartbeat may increase up to several hundred times per minute. When the heart cannot sustain such rapid contraction and relaxation, it may stop beating and cause death.
The effect of currents passing through various parts of the body
8
During an electric shock, the current passing through the body may lead to burns on the skin, muscles or internal organs. As electric shocks and burns are closely related, preventative measures should be considered together.
High temperatures caused by currents under abnormal conditions, may result in accidental fires
and explosions. The common causes leading to high temperatures include:
electrical appliances or wiring
If flames, sparks or metallic solutions due to electric arc welding are not controlled, hazardous fires or
explosions can occur.
9
6. Special process (electric arc welding)
Electric arc welding is commonly used for metallic welding and cutting. The various hazards from welding or cutting include the following:
Hazards
Sparks or hot metal fragments from arc welding or cutting may result in serious burns. Proper
protection is essential.
If proper eye protectors are not used while welding or cutting, radiation or other objects may hurt the
welder.
Safety measures:
Wear proper personal protective equipment, e.g. approved eye protectors, hand shields, leather aprons, leather gloves and safety shoes, etc.
It is dangerous to conduct the arc welding in a wet environment or on rainy days.
Safety measures:
no-load voltage of the transformer output, reducing the chance of getting an electric shock.
Inhalation of poisonous fumes and gases during welding
or cutting may cause serious health problems.
Safety measures:
and gases.
10
7. Protective measures for prevention of direct electrical contact
The following procedures will prevent the human body from contact with electrical conductors,wiring, electrical sources, etc.
Protective measures
Shield the electrical conductor with an insulator to prevent direct contact
Place obstacles to prevent any accidental contact with the electrical conductor
Create barriers or enclosures that prevent any direct contact with the electrical conductor
This prevents accidental contact with the electrical conductor
11
8. Safety devices
Normally, a fuse is a copper wiring with a set current fusion value. If the current exceeds the set fusion value, the fuse will blow and the current is cut-off, thus preventing overloading.
A fuse must be installed on “live” wires. When replacing a fuse, the new fuse must be same current fusion value as the old one.
Circuit breakers are based on the principle of the electromagnetic field. The current entered may enable the coils of the circuit breaker to magnetise. When the current exceeds the set value (i.e., overloading), the magnetisation intensifies, switching off the circuit breaker and disconnecting the electric source.
Earthing provides a low resistance way of discharging electricity to the ground in case of current leakage. This means that during an electric shock, the current passes through the “earth” wire and is prevented from entering the human body and causing injury.
|
|
|
12
8.4 Earth leakage circuit breaker (ELCB or RCD)
Current leakage protection is also called residual current protection or earthing fault current protection. Earth leakage circuit breakers monitor the operation of the “neutral” or “live” wires in the electrical circuit. During an imbalance in the electrical circuit, or when not all the current flows to the electrical appliance through the “live” wire and returns through the “neutral” wire, part of the current flows away (leaks) into other sources. The earth leakage circuit breaker will immediately detect such an imbalance and cut-off the electrical source in 0.4 seconds. Rating of the tripping current shall not exceed 30mA.
If ELCB is not fixed in main circuit box or the worker works in high risk environment (E.g. humid condition), portable RCD(Residual Current Devices) should be installed to reduce the chance of getting an electric shock.
Portable Residual
Current Device
An electrical appliance with double insulation is protected by a supplementary insulation layer in addition to basic insulation. Electrical appliances with double insulation bear the “ “ mark. No earth connection is required for such appliances since double insulation provides sufficient protection.
Using electrical tools with an extra-low voltage of less than 50 V may minimise injury in case of electric shock. When extra-low voltage is used, an earthing connection may not be required.
13
9. Safe use of electricity
Rating | 5-Ampere plug | 13-Ampere plug | 15-Ampere plug |
Standard | BS 546 | BS 1363 | BS 546 |
(calculated by voltage 220V).
1100 2860 3300
Maximum power Watt (W)
9.1.2 Connection of plugs
Electrical and Mechanical Services Department announced the new colour code for those electrical installation works on or after 1 July 2007. From now on, new colour code should be used for all new electrical installation works.
Existing colour
New colour
14
of the cord directly into a socket.
replaced immediately.
|
|
|
|
|
|
Brown or red to Live (L) Blue or black to Neutral (N)
Yellow/green or green to Earth (E or )
15
into the same socket.
unsafe tools.
16
be used.
unplugged.
maintenance, the main switch should be turned off. The power source must be locked and labeled with warning signs, so as to avoid any confusion when reconnecting the power. Implement “Pointing and
Calling” proceedure to counter check the safety mea- sures must be properly executed.
17
10. Installation and maintenance of electrical work
The installation and maintenance of electrical work must be carried out by the registered electrical workers. “Electrical work” means the work in relation to the installation, commissioning, inspection, testing, maintenance, modification or repair of relevant projects or work of high or low voltage fixed electrical installation. Those engaged in projects of non-fixed electrical installation (e.g. repair of table lamps,televisions, refrigerators, etc.) are not required to be registered.
The classification of the license of electricians:
Means voltage between conductors or between any conductor and earth with Alternating Current (AC)
not exceeding 50 V or Direct Current (DC) not exceeding 120 V.
Means voltage normally exceeding extra-low voltage, but between conductors with AC not exceeding
1000 V or DC not exceeding 1500 V, or the voltage between conductors and earth with AC not exceeding 600 V or DC not exceeding 900 V.
Means voltage normally exceeding low voltage, but between conductors with AC exceeding 1000 V
or DC exceeding 1500 V, or the voltage between conductor and earth with AC exceeding 600 V or DC exceeding 900 V.
Grade A Electrical Work Electrical work on a low voltage fixed electrical installation not exceeding 400 Amperes (single-phase or 3-phase).
Grade B Electrical Work Electrical work on a low voltage fixed electrical installation not exceeding 2500 Amperes (single-phase or 3-phase).
Grade R Electrical Work Include any one or more of the following types of installations:
Grade C Electrical Work Electrical work on a low v ol t a ge fi xe d e l e c t r i c a l installation of any capacity.
Grade H Electrical Work Electrical work on a high voltage electrical installation.
11. First-aid for electric shock
If anyone suffers an electric shock, the electricity source should be cut off immediately. Only conduct the first-aid when the victim is in a safe place. Check the victim’s breath and pulse. If the person is unconscious but is breathing normally, he or she should be placed in a recovery position. If the victim is not breathing and has no pulse, cardiopulmonary resuscitation should be conducted.
Note: Cardiopulmonary resuscitation should be carried out only by competent first-aid personnel.
Cardiopulmonary resuscitation
Treatment:
1 Open the AIRWAY
Lift the jaw and tilt the head back to open the airway. Clear any obstacles.
2
Check the BREATHS
See : See if the chest rises and falls. Listen : Listen for breathing.
Feel : Feel breathing on your cheek.
3
Check the pulse (CIRCULATION)
Use your fingers to feel the pulse.
4
Recovery position
If the casualty is unconscious but is breathing normally, place them in the recovery position. (as shown in figure below)
5
Mouth to mouth expired air resuscitation
If the person is not breathing, mouth-to- mouth resuscitation should be used to help the resumption of breathing.
6
External chest compression
I f t h e c a s u a l t y h a s n o pulse, cardiopulmonary resuscitation should be carried out (combining the expired air resuscitation and external chest compression).
For all premises apply on Factories and Industrial Undertaking Ordinance, the treatment notice of persons receiving electric shock in Chinese and English shall be displayed in all parts of the premises where electricity is generated, transformed, or used.
18
Name of organisation:
Work place: Date: Time: Name of inspector/Signature:
The following list is a sample of regular inspections to be carried out by relevant organizations. The content is subject to appropriate modifications based on of the organisation's working environment.
1. Electrical installation
2. Electrical appliances and equipment
Inspection content | Satisfactory | Improvement required | Immediate improvement required | N/A | Follow-up action |
| | | | | |
Inspection content | Satisfactory | Improvement required | Immediate improvement required | N/A | Follow-up action |
requirement?
electrical appliances and equipment?
| | | | | |
Inspection checklist of electrical safety
19
Inspection content | Satisfactory | Improvement required | Immediate improvement required | N/A | Follow-up action |
requirements?
| | | | | |
4. Special process (electric arc welding)
5. General
Inspection content | Satisfactory | Improvement required | Immediate improvement required | N/A | Follow-up action |
| | | | | |
Inspection content | Satisfactory | Improvement required | Immediate improvement required | N/A | Follow-up action |
| | | | | |
Inspection checklist of electrical safety
3. Portable electrical tools
20