Water-mist fire suppression systems are operated at higher pressures than standard sprinkler systems.
12–0
Low-pressure system
175 psi (1 225 kPa) or less
Intermediate-pressure system
175 to 500 psi (1 225 kPa to 3 500 kPa)
High-pressure systems
500 psi (3 500 kPa) or greater
Understand characteristics of water-mist fire suppression systems.
12–1
Compressed-air, nitrogen, or high-pressure water pumps create higher pressures
System is composed of small-diameter, pressure-rated copper, or stainless-steel tubing
Small-diameter spray nozzles are spaced evenly on the tubing
Spray nozzles may be of the open or closed sprinkler variety
A product-of-combustion detection system activates the system
Should also have a means of manual operation
The most common type of water-mist system works like a deluge system.
12–2
All of the spray nozzles in a particular room or zone are open
When the detection devices activate, the water discharges from the spray nozzles
Know inspection requirements for water-mist systems.
12–3
NFPA® 25
Cylinders
Replacement components
Servicing
Know the typical serving functions required for water-mist systems.
12–4
Lubricating control valve stems
Adjusting packing glands on valves and pumps
Bleeding moisture and condensation from air compressors and air lines
Cleaning strainers
Replacing corroded or painted nozzles
Replacing damaged or missing pipe hangers
Replacing damaged valve seats or gaskets
REVIEW QUESTION
Explain how a water-mist system works.
12–5
Foam-water systems are designed to discharge foam-water solution onto fires.
12–6
Commonly employed to protect Class B fire hazards but may also be used for Class A hazards
May also be used to suppress vapors
Designed to a deliver a foam-water solution at the required design concentration over the discharge density and design area of the system
These systems can be wet-pipe, dry-pipe, preaction, or deluge systems
(Cont.)
Foam-water systems are designed to discharge foam-water solution onto fires.
12–7
NFPA® 16 details the design and construction requirements of foam-water automatic sprinkler systems
Design professional establishes the required duration for foam application; must be for at least fifteen minutes
Inspector verifies the minimum required volume of foam concentrate and the correct type of foam is being used
(Cont.)
Foam-water systems are designed to discharge foam-water solution onto fires.
12–8
All foam-water systems require a proportioner.
12–9
The proportioner may be an in-line valve or pump designed to inject and mix the foam with the water to create the foam-water solution at the correct concentration
NFPA® 25 requires an annual test of the proportioner
In certain designs, the ceiling sprinklers are used as the detection feature when the foam-water sprinklers are pre-primed with foam solution
In other cases, a fire alarm and detection system is required to activate the foam-water system
REVIEW QUESTION
Describe how a foam-water system works.
12–10
�Learning Objective 3
Describe types of standpipe and hose systems.
12–11
Know the characteristics of standpipe and hose systems.
12–12
Designed to provide a means for rapidly deploying fire hose and operating fire streams on all levels of multistory structures and at remote points in large-area structures
Intended to be used by firefighters, trained occupants, or both
(Cont.)
Know the characteristics of standpipe and hose systems.
12–13
A permanent water supply that is augmented through an FDC may supply the system
It may be a stand-alone system that requires the fire department to charge the system with water through the FDC
May also be part of or separate from an automatic sprinkler, water-spray, water-mist, or foam-water system
(Cont.)
Know the characteristics of standpipe and hose systems.
12–14
Some building codes require operational standpipes during construction
As construction progresses, the standpipe is extended to subsequent floors
The system may or may not have an attached water supply
Must have appropriate FDCs, hose discharge connections, other necessary appliances
Know what inspectors need to verify on standpipe and hose systems.
12–15
Verify the connection threads on all hose connections and the fire department connections
Systems need to be flow and hydrostatic tested every five years
At a minimum, the Inspector I should request documentation of the last test to verify system readiness
Be familiar with standpipe components.
12–16
Hose stations (defines classification of system)
Water supplies
Waterflow control valves (similar to those used in automatic sprinkler systems)
Risers (piping systems used to transfer water from the supply to the discharge)
Pressure-regulating devices
Fire department connections (FDCs)
REVIEW QUESTION
Describe standpipe and hose systems and the standard components.
12–17
Understand the three classes of standpipe systems.
12–18
Class I: firefighters
(Cont.)
Understand the three classes of standpipe systems.
12–19
(Cont.)
Class II: trained building occupants
Understand the three classes of standpipe systems.
12–20
Class III: combination
REVIEW QUESTION
Differentiate between the standpipe classifications.
12–21
Understand the five types of standpipe systems.
12–22
Automatic-wet
(Cont.)
Understand the five types of standpipe systems.
12–23
Automatic-dry
(Cont.)
Understand the five types of standpipe systems.
12–24
Semiautomatic-dry
Manual-dry
Manual-wet
NOTE
Canadian building and fire codes do not accept dry standpipes as meeting code requirements.
12–25
Automatic wet standpipe systems with automatic water supply are the most common.
12–26
Water is constantly available at the hose station
Cannot be used in cold environments; dry system, which have higher costs and maintenance, may be necessary
An inspector assessing standpipe systems must ask certain questions.
12–27
Are standpipes accessible?
Do valves work?
Are the caps in place?
Are doors closed and latched?
REVIEW QUESTION
What are the types of standpipe and hose systems?
12–28
Water supply systems for standpipe systems have specific requirements.
12–29
Amount of water required depends on the occupancy, height of the building, and the total number of standpipes
Requirements may be reduced by installed automatic sprinkler systems
Some occupancies require secondary water supplies; usually from automatic fire pumps
Be aware of multiple water supplies and verify their operational readiness
The current NFPA® 14 minimum requirement for residual pressure is 100 psi (700 kPa) at the fire hose outlet
Inspectors have specific tasks in regards to standpipe systems.
12–30
Consult the code used in the local jurisdiction for minimum requirements
Ask for inspection and maintenance records
Confirm that the water supply has not been changed and that all valves are accessible
Fire hose valves should be located so that any part of a floor is within 130 feet (40 m) of the standpipe connections.
12–31
Inspectors need to know other distance requirements for standpipe systems.
12–32
Location
Hose connections
Buildings equipped with Class I or III systems
Inspectors need to be familiar with pressure-regulating devices.
12–33
Where the discharge pressure at a hose outlet exceeds 175 psi (1 225 kPa), NFPA® 14 requires a pressure-regulating device to limit the pressure to 100 psi (700 kPa)
Use prevents pressures that make fire hose difficult or dangerous to handle
Enhances system reliability because it extends individual zones to greater heights
May improve system economy because its use may eliminate some pumps
Pressure-regulating devices make the system design more complex
Know the three basic categories of pressure-regulating devices.
12–34
Pressure-restricting devices
Pressure-control devices
(Cont.)
Know the three basic categories of pressure-regulating devices.
12–35
Pressure-reducing devices
Inspectors need to verify that requirements are met.
12–36
Verify that the required testing has been completed
Verify required pressure-reducing valves are installed and tested as specified
Standpipe systems that are equipped with pressure-regulating devices are designed so that they can be routinely tested
Systems must have dedicated drainage pipes with connections on each floor; means for determining water flow
Must be specified and/or adjusted to meet the pressure and flow requirements of the individual installation
A pressure-regulating device that is not properly installed or adjusted may result in seriously reduced available flow and impaired suppression capabilities
Know requirements for standpipe systems.
12–37
Each standpipe system requires one or more FDCs through which a fire department engine can supply water
Large buildings having two or more zones require an FDC for each zone
Standard requirements specify that there shall be no shutoff valve between the FDC and the standpipe riser
(Cont.)
Inspectors need to know hose requirements for standpipes.
12–38
(Cont.)
Hose connections to the FDC must adhere to the standards of the locally adopted code; have standard cap plugs or approved breakaway covers
Some jurisdictions require large-diameter hose (LDH) connections to supply standpipes
Hose coupling threads should conform to those used by the local fire department
Inspectors need to know hose requirements for standpipes.
12–39
The FDC may also be protected with a locking intake cap that must be removed with a special key
Local authority may regulate the use of these locking caps
A raised-letter sign on a plate or fitting reading STANDPIPE designates the FDC
If the FDC does not service the entire building, the sign must indicate which floors it does service
Courtesy of Scott Strassburg
REVIEW QUESTION
What are some of the inspection requirements for water supplies, standpipe hose valves, regulating devices, and fire department connections?
12–40
�Learning Objective 4
Explain the components and operation of stationary fire pumps.
12–41
Inspectors must be familiar with stationary (fixed) fire pumps.
12–42
Found in many commercial, institutional, and industrial facilities
Main function is to increase the pressure of the water that flows through it
Usually needed to supply a sprinkler or standpipe system
High-rise buildings or areas with low static pressure on the public or private water supply may require the installation of fire pumps
Inspectors must be familiar with types of centrifugal pumps.
12–43
Horizontal split-case
Vertical �split-case
Vertical inline
Vertical turbine
End suction
Horizontal split-case pumps are the most common type.
12–44
Referred to as a horizontal shaft pump
Drive shaft is on a horizontal plane
Pump on one end of the shaft and the driver on the other
Used to boost the pressure from an incoming, pressurized water source
Not a self-priming pump
Cannot be used to supply water from a static supply source
Not rated at a particular pressure
Vertical split-case pumps are very similar to horizontal split-case pumps.
12–45
Impeller shaft runs vertically
Almost always driven by an electric motor that sits on top of the pump
Main advantage of this pump is its compactness
Inspectors need to be familiar with vertical inline pumps.
12–46
Single-stage pump designed to fit into the intake/discharge line with the driver located above the inline impeller
Advantages include easy installation as a replacement pump; compact; easy maintenance
Has a capacity up to 1,500 gpm (6 000 L/min) and operating pressures up to 165 psi (1 150 kPa)
Vertical turbine pumps are useful for lifting water from a water source below the pump.
12–47
Commonly used as well pumps in nonfire-protection applications
Impellers are actually located within the water supply source
Water is drawn into the impeller and then discharged up through the impeller casing
Most of these pumps are multistage pumps
As the water exits one impeller, it enters the next
Volume capabilities are consistent with horizontal and vertical split-case pumps
An end suction pump is a variation of the horizontal split-case pump.
12–48
Pumps have center line suction and discharge
Advantages include ease of installation, simplified piping arrangement, and reduced pipe strain
The pumps are self-venting; eliminates the need for an automatic air-release valve
Automatic sprinkler systems may require a small-capacity auxiliary pump.
12–49
Known as pressure-maintenance pumps, jockey pumps, or make-up pumps
Located in parallel with the primary fire pump
Designed to maintain system pressure and prevent the larger main pump from starting repeatedly for a short period of time
Design may be any one of the pump types mentioned previously
REVIEW QUESTION
List the types of fire pumps that can be installed as stationary pumps for fire suppression systems.
12–50
The source of power that operates a fire pump is called the driver.
12–51
Fire pumps are commonly powered by one of three types of drivers
Other types of engine drivers such as gasoline, natural gas, and liquefied petroleum have been used in the past but are not currently recognized in NFPA® codes
Electric motor drivers are the most commonly used.
12–52
Simple, reliable, and easily maintained
Not designed specifically for fire pumps
Motors must meet National Electrical Manufacturers Association (NEMA) requirements
Must have adequate horsepower (hp)
Electric motors powerful enough to power fire pumps may require a larger electrical service to the building
Diesel motor drivers are used where a driver independent of local electric power is needed.
12–53
More complex and requires batteries to start
Also requires an on-site fuel supply
Generally more expensive and requires more maintenance than an electric motor
Required to be tested weekly by running it for at least thirty minutes
(Cont.)
Diesel motor drivers are used where a driver independent of local electric power is needed.
12–54
Use for fire pumps is tested and listed by testing laboratories
Testing agencies have several requirements
Must have a closed-circuit-type cooling system; and a fuel supply to provide at least 1 gallon (4 L) per hp
Must also have an adequate flow of air through the room where it is located
Steam turbines provide steam pressure to drive both horizontal and vertical split-case pumps.
12–55
Not as common as the electric or diesel drivers
When an uninterruptible supply of steam is available in sufficient quantities and at sufficient pressure, they are feasible options; if not, it is more economical to use electric- or diesel-driven equipment
REVIEW QUESTION
Differentiate between the types of fire pump drivers.
12–56
Understand the role of controllers when it comes to fire pumps.
12–57
Controllers make stationary fire pumps start automatically and stops them automatically
Additional requirements for testing and maintenance are a consideration when pumps are connected to an alternate power supply such as an engine-driven generator
Understand the role of pressure switches in electric motors.
12–58
Pressure-sensing switch inside the electric motor detects the drop resulting from the flow of water
The switch then energizes a circuit that starts the fire pump motor
When the water stops flowing in the system, the pressure switch detects the resulting increase in pressure and turns off the pump
Pressure switches are adjustable
Must be properly adjusted for the individual fire suppression system
Understand the role of controllers when it comes to fire pumps.
12–59
Controllers also contain a provision for starting and stopping the pump manually
Contains other operating features including a circuit breaker, a power-available indicating lamp, and a running period timer
The function of the running timer is to keep the fire pump motor running for a minimum period of time once the motor has started
The diesel fire pump controller is more complicated than an electric motor controller.
12–60
Closes the circuit for the starting motor on the diesel engine
Monitors and contains alarms for several conditions
REVIEW QUESTION
Describe different types of controllers found on stationary fire pump systems.
12–61
�Summary
12–62
(Cont.)
�Summary
12–63
(Cont.)
�Summary
12–64
(Cont.)
�Summary
12–65
(Cont.)
�Summary
12–66
(Cont.)
�Summary
12–67