Prof. Dongdong Li, Mengxian Sun (Presenter)
Shanghai University of Electric Power, Shanghai, China
18/07/2023
Dynamic Short Circuit Ratio for Stability Assessment of Grid Connected VSC-HVDC Systems Involving Wide-band Oscillatory Behaviors
System with PEDs Implemented
Generator: 50 Hz or 60 Hz AC is created from a rotating electro-magnet. Its dynamic is described by
The dynamic behaviors of power system are dominated by controls of PEDs.
Power electronic device (PED): Its dynamic is set by software (digital control). Besides, it behaves differently from a traditional generator.
The dynamic behaviors of power system are dominated by rotors of the generators.
The Wide-band Oscillations in Real World
Location | Oscillation Events in real world | Oscillation Frequency (Hz) |
Guyuan, China | SSO is resulted from the interaction between wind farm and series compensation | 3~10 |
Buffalo Rige, Canada | SSO is arisen from the interaction between wind farm and series compensation | 9~13 |
Texas, USA | SSO is caused by the interaction between DFIG and series compensation | 20 |
Hami, Xinjiang, China | SSO is arisen from the interaction between wind farm and weak receiving-end AC grid | 20~34 |
Southern Power Grid, China | The sub- or super-synchronous oscillation is caused by the interaction between STATCOM and weak receiving-end AC grid | 2.5/97.5 |
Borwin, European | The high frequency resonance is resulted from the interaction between VSC-HVDC and weak receiving-end AC grid | 250~350 |
Yunnan, China | The high frequency resonance is arisen from the interaction between VSC-HVDC and weak receiving-end AC grid | 1270 |
For the past few years, the wide-band oscillation is a concerned stability issue which stems from the complicated interaction between power electronic devices (PEDs) and weak receiving-end AC grid.
Introduction of the Short Circuit Ratio
Definition: Short Circuit Ratio (SCR) is a metric index which can be used to quantify the strength of nonlinear system which is relative to system stability. Its expression is given by
Vthi and Zthi are respectively Thevenin equivalent voltage and impedance seen from the Bus i。
Will it be okay If I connect it with experienced criterion?
Larger SCR, Stronger System Strength
SCR? Wide-band Oscillation?
Two modification of SCR:
Motivations of Our Recent Research Work
KpllI :1400 →4500
KpllP:60→600
Detailed model of the VSC-HVDC system in Simulink Library
SCR:1.9999→0.9905
Lg:0.42095H→0.85H
RTDS simulation of SCR changing[1]
[1] Y. Qi, H. Ding, Y. Zhang, X. Shi and A. M. Gole, “Identification of Sub-Synchronous Interaction in MMC Systems using Frequency Scanning,” 2020 IEEE Power & Energy Society General Meeting (PESGM), 2020, pp. 1-5.
Dynamic Short Circuit Ratio (DSCR)
The DSCR is defined as the following equation.
The diagram of grid-connected VSC-HVDC system and its control loops
where ρco is a correction factor which is relative to the system parameters.
DSCR is a modification of SCR by the correction factor.
A sensitivity factor is defined with the DSCR.
If SFDSCR >0, system stability is improved.
What is the physical meaning of DSCR?
What is the critical value of DSCR?
The relation between DSCR and Stability
Whether the system is stable or not
The stability criterion:
DSCR>1, the system is stable. Otherwise, the system is unstable.
There exist a finite-step Lyapunov function such that
Whether the general asymptotic gain matrix (GAGM) is a non-negative matrix which has shrinking property or not
Lyapunov Stability criterion: If
is satisfied, the system is stable.
[2] D. Li, M. Sun, Y. Mi, Y. Zhao and Y. Gao, “Dynamic Short Circuit Ratio for Stability Assessment of Grid Connected VSC-HVDC Systems Considering the Impact of Time-Varying Phase Shift,” in IEEE Transactions on Power Systems, doi: 10.1109/TPWRS.2023.3244788.
The relation between DSCR and Stability
The system is stable
[3] N. Noroozi and B. S. Rüffer, “Non-conservative dissipativity and small-gain theory for ISS networks,” 53rd IEEE Conference on Decision and Control, Los Angeles, CA, USA, 2014, pp. 3131-3136, doi: 10.1109/CDC.2014.7039872.
Spectral radius of Γ:
Take a two order system[3] as an example
By iterating above equation in one step, there is no one positive matrix P satisfying
The positive function V cannot be found.
By iterating the two order system in three steps and taking infinite norm as a measurement function, we can get
Is the system unstable?
The Description of the Test System
Parameter | Value | Parameter | Value |
SB | 200MVA | RT1 | 0.68124Ω |
SDN | 200MVA | RT2 | 0.375Ω |
UB | 100kV | LT1 | 0.065053H |
fgN | 50Hz | LT2 | 0.03581H |
Lc | 0.04775H | / | / |
Cf | 25.4648F | / | / |
RG | 4.7579Ω | KiP | 0.5 |
LG | 0.23 H | KiI | 0.1 |
CDC1, CDC2 | 7*10-5F, 1.2*10-5F | KpllP | 100 |
VG(swing bus) | 230kV | KpllI | 1400 |
RT-LAB Platform
TABLE I
Key System Parameters of Grid connected VSC-HVDC System
The Verification of effectiveness of DSCR
DSCR(P1):1.1805 → 1.1786;
DSCR(P2):1.1786 → 0.9339。
DSCR(P3): 1.1805 → 1.1439;
DSCR(P4): 1.1439 → 0.9909。
DSCR(P5): 1.1805 → 1.053;
DSCR(P6): 1.053 → 0.7763。
The Comparison between DSCR and SCR
|△Lg| | |△KiP| | |△KiI| | SFDSCR | SFSCR |
0.095 | 0 | 0 | -0.02 | -7.47 |
0.475 | 0 | 0 | -0.52 | -2.17 |
0 | 0.222 | 0 | -0.17 | 0 |
0 | 0.258 | 0 | -0.59 | 0 |
0 | 0 | 0.09 | -1.42 | 0 |
0 | 0 | 1.31 | -0.21 | 0 |
The expression of the sensitivity factor of SCR is given by
Table II
The Computation Results of SFDSCR and SFSCR under Different System Conditions
The Relationship between the DSCR and Oscillation Frequency
The DFT analysis of A phase instantaneous current injected into receiving-end grid under different values of Lg.
The DFT analysis of A phase instantaneous current injected into receiving-end grid under different values of KiP.
The DFT analysis of A phase instantaneous current injected into receiving-end grid under different values of KiI.
The Impacts of Outer-loops on Validation
of DSCR
KoIQ:0.1→10
KoPDC:0.1→10
KoIDC:5→20
KoPP:0.1→5
KoIP:5→200
KoPQ:0.1→3
TABLE III
The Computation Results of DSCR with Changes of Parameters of Various Outer-Loop Controls
Case | Modified Parameter | Initial Value | Modified Value | DSCR (Before 1s) | DSCR (After 1s) |
1 | KoPP | 0.1 | 5 | 1.0559 | 0.982 |
2 | KoIP | 5 | 200 | 1.0559 | 0.8387 |
3 | KoPQ | 0.1 | 3 | 1.0559 | 0.9374 |
4 | KoIQ | 0.1 | 10 | 1.0559 | 0.9765 |
5 | KoPDC | 0.1 | 10 | 1.0158 | 0.9951 |
6 | KoIDC | 5 | 20 | 1.0158 | 0.8835 |
Concluding Remarks
What we have done:
Some issues need to be solved in the future: