1 of 80

Fire Inspection and �Code Enforcement

8th Edition�Inspector II

Chapter 9 — Fire Hazard�Recognition

2 of 80

�Learning Objective 1

Evaluate hazardous conditions involving building systems.

9–1

3 of 80

Building systems present unique challenges inspectors need to research before inspections.

9–2

Heating, Ventilating, and Air Conditioning Equipment/Systems

Cooking Equipment

Industrial Furnaces and Ovens

Powered Industrial Trucks

Tents

4 of 80

Be familiar with heating, ventilating, and air conditioning (HVAC) equipment and systems.

9–3

Air heating or cooling

Air humidifying or dehumidifying

Air filtering or cleaning

5 of 80

Inspectors are responsible for verifying several HVAC items.

9–4

Qualified personnel are properly inspecting and maintaining the HVAC system

Unit clearances are maintained

Operating instructions for the equipment are provided

6 of 80

Know the major components of HVAC systems.

9–5

Heaters

Air conditioners

Fans

Ducts

Heat exchangers

Thermostatic controls

7 of 80

Know the two primary hazards HVAC systems pose.

9–6

Fire hazards from heating appliances (greater hazard)

Spread of fire and products of combustion through the air handling system

8 of 80

Inspectors need to know the common causes of fires related to heating appliances.

9–7

Improperly adjusted or worn fan drive belts

Clogged filters

Combustible lint or debris near the burners

Poorly maintained motors

9 of 80

Inspectors should take note of HVAC system rooms or mechanical equipment rooms.

9–8

Only authorized personnel should have access

Type and size of refrigeration or heating equipment will determine the fire separation requirements

Fire-resistive construction and the appropriate protective openings should be used

Look for combustible storage inside the room; generally, this storage is not permitted

Consult the appropriate codes for issues with HVAC system rooms

10 of 80

Inspectors need to understand furnaces.

9–9

    • Warm-air furnaces

Most common

    • Considered obsolete
    • Operate primarily by the circulation of air; no fans
    • Located in basements of houses

Gravity furnaces

    • Units contain plenums and ductwork that may become hot; require the use of appropriate clearances and insulation
    • Automatic controls turn off the furnace

Forced-air furnaces

11 of 80

Know the fire problems presented by warm-air furnaces.

9–10

Inadequate clearances

Lack of proper limit control

Heat-exchanger burnouts

Improper installations

Improper maintenance procedures

12 of 80

Most floor furnaces are designed and approved for installation under combustible floors.

9–11

They require temperature-limit controls and proper clearances from miscellaneous combustibles

Must have safety controls that turn off the fuel source if the pilot light is extinguished

Must be properly vented so they cannot contribute to carbon monoxide buildup

Mostly found in single-family dwellings built before the 1960s

Some commercial occupancies may use them

Warn individuals with floor furnaces not to cover the register

13 of 80

Inspectors should also be aware of wall furnaces.

9–12

Self-contained electric, indirect-fired gas, or oil heaters installed within or on a wall

Gas or oil heaters may have a direct vent to the exterior or be equipped with an indirect vent or chimney

Found in residential occupancies and small office spaces

14 of 80

A boiler is a pressure vessel used for a variety of industrial processes.

9–13

Generating steam to power machinery

Providing heat required by industrial processes

In nonindustrial applications, boilers provide heating and hot water through a system of radiators

Found in both single- and multi-family residences

More prevalent in old structures, newer, more efficient systems are on the market

15 of 80

Manufacturers must strictly adhere to all applicable codes when building boilers.

9–14

Many manufacturers use the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Codes

All boilers should meet fire and explosion prevention requirements

The entire system will include interlocks, detectors, alarms, sensors to turn off fuel

16 of 80

Know what to verify when inspecting boilers for compliance.

9–15

Check for ASME nameplate

Verify inspection history via an up-to-date inspection tag or certificate

Note the pressure relief device

17 of 80

Inspectors need to know the two common type of boilers.

9–16

Fire-tube boilers

    • Combustion gases pass through tubes that are immersed in circulating water
    • Converts to steam

Water-tube boiler

    • Steam-generating unit in which steam and water circulate through a series of small drums and tubes
    • Combustion gases pass over the outside of these steam- and water-containing elements

18 of 80

NOTE

Most large boilers are of the water-tube type.

9–17

19 of 80

Know what fuels are usually used in boilers.

9–18

    • Either supplied to the burner premixed or externally mixed
    • In a premix, the air and fuel are mixed before they reach the burner

Natural gas

    • Units deliver air and pulverized coal to the burners for combustion

Coal

    • Atomized at the burner, which causes it to mix with air and burn most efficiently

Oil

20 of 80

Understand the hazards associated with boilers.

9–19

Depend on a number of fuel and malfunction possibilities

Gases can build in the system and ignite

Main hazard in natural-gas-fired boilers is the leaking of gas and the buildup of fuel-rich mixtures if a burner fails

Coal-fired boilers present hazards when debris is mixed with coal

(Cont.)

21 of 80

Understand the hazards associated with boilers.

9–20

Oil-fired hazards come from the fuels, oil leaks, or interruptions in the oil flow caused by water or sludge in the fuel

Coal dust accumulation in areas adjacent to the unit’s fire box

Failure of the vessel

Deterioration or modification of unit exhaust

22 of 80

Operator training is an important part of any hazard reduction plan.

9–21

Workers who are educated in the process and function of the equipment around them will be better able to eliminate a potential hazardous situation

In some circumstances, workers are more knowledgeable than inspectors regarding the boilers

Workers can provide the inspectors with useful information during an inspection

Together, workers and inspectors can identify and report hazardous issues as well as promote solutions

23 of 80

Unit heaters are self-contained devices that are thermostatically controlled.

9–22

May be mounted on the floor or suspended from a wall or ceiling

Consult guidelines in NFPA® 1 Fire Code and the International Fire Code (IFC)

Model fire codes regulate the type and amount of fuel to operate the heaters

Can use propane, natural gas, kerosene, or electricity

24 of 80

NOTE

The heating element and fan are enclosed in a common operating unit. The inspector should verify that heaters are located with appropriate clearances from combustibles. An inspector should also look for proper storage and handling of the fuel source.

9–23

25 of 80

Room heaters are self-contained units designed to heat the immediate surrounding area.

9–24

They use the circulation of radiant heat as the heating medium

Usually incorporate manual or thermostatically controlled drafts

Require that nearby floors and walls be properly protected

26 of 80

Be familiar with different types of room heaters.

9–25

Wood and coal stoves

Electric and gas logs

Electric baseboard heaters

Open-front heaters

27 of 80

Understand the hazards of room heaters.

9–26

Overfiring the device

Careless handling of fuel and ashes

Inadequate clearances from fuel cans or other combustible materials

Accumulation of creosote in flues and chimneys as applicable

Use of insufficient extension cords with electric heaters

Refueling with the wrong fuel

28 of 80

Solid-fuel room heaters are free-standing appliances that vent to the exterior.

9–27

Primarily found in single-family dwellings

May also be found in restaurants, apartment clubhouses, or bars where a living-room atmosphere is desired

29 of 80

Know what to look for when inspecting room heaters.

9–28

Solid fuels for wood or coal stoves are stored a safe distance from the stoves

Provisions are made for safely removing and storing ashes and cinders

All chimneys and flues are kept clear of excessive creosote

Combustibles are stored a safe distance from heating units

All heating appliances have proper industry approvals; labeled accordingly

All heating sources are vented and provided with adequate ventilation according to manufacturer’s instructions

30 of 80

Portable heating equipment can be found in nearly every type of occupancy.

9–29

Kerosene

Electricity

Propane

Also includes natural gas and oil

31 of 80

Understand the hazards related to portable heaters.

9–30

Easily misused, placed in poor locations, damaged, poorly maintained

Heaters placed close to combustibles

Lack of adequate ventilation

Many communities have enacted laws regulating or prohibiting certain types of heaters in certain occupancies

Be familiar with the locally adopted code requirements

Be familiar with manufacturers’ requirements

If prohibited, it must be removed from service and taken from the premises

32 of 80

NOTE

The 2012 edition of the International Fire Code® (IFC) and the International Building Code® (IBC) contain requirements for the installation of CO detection in new and existing Group-R and Group-I occupancies. These would include hotels, dormitories, apartment buildings, hospitals, and nursing homes. These alarms must be installed and maintained in accordance with NFPA® 720, Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment® as well as the manufacturer’s instructions. The inspector must be familiar with these requirements and exceptions.

9–31

33 of 80

Know what to verify when portable heaters are permitted and in use.

9–32

Heater is well maintained; in safe working condition

Equipped with safety switches that turn the heating element off if the heater tips over

The appropriate fuel, if applicable, is used for the heater

(Cont.)

34 of 80

Know what to verify when portable heaters are permitted and in use.

9–33

Electric heaters are only plugged into an electrical receptacle/circuit that is designed to carry the current required to operate the heater

Located away from the route of egress from the structure

Placed a safe distance from any flammable or combustible materials

Fuel for kerosene heaters is stored outside the structure; heater is refilled outside the structure

35 of 80

Understand the hazards related to air conditioners.

9–34

Most commercial refrigerants have a classified level of toxicity and flammability as defined in American National Standards Institute (ANSI) and the American Society of Heating, Refrigeration, and Air-Conditioning Engineers (ASHRAE)

ANSI/ASHRAE Standard 34, Designation and Safety Classification of Refrigerants

Refrigerants are assigned to one of two toxicity classes (A or B) based on what would be a permissible exposure

Remember that they may be dealing with a refrigerant that is not very flammable but is very toxic

36 of 80

Ventilation systems are mechanical air-moving or air-distribution systems.

9–35

These systems are tied into both the heating appliance and the air conditioning equipment

No cooling or heating of the air occurs within the system

Quality and characteristics of the air remain unchanged

Primary fire safety concern is the potential for the transmission of fire, smoke, and products of combustion through the air distribution system

37 of 80

NOTE

An inspector must recognize the difference between an air conditioning system and a ventilation system.

9–36

38 of 80

Know the types of filters used in HVAC systems and the hazards they pose.

9–37

    • May become filled with trapped particulates
    • Particulates can generate large quantities of smoke if they become ignited

Fibrous media filters/renewable media filters

    • Can develop an electrical malfunction that ignites the filters or particulate matter inside the HVAC system

Electronic air cleaners

39 of 80

Understand the classification systems for filters.

9–38

    • UL classification
    • Flame propagation
    • Smoke development

Basis

    • When clean, will not contribute fuel to a fire
    • Emit very small quantities of smoke when flames strike them

Class 1

    • When clean, will burn moderately
    • Emit moderate quantities of smoke

Class 2

40 of 80

REVIEW QUESTION

Identify fire and life safety hazards presented by heating, ventilation, and air conditioning systems.

9–39

41 of 80

Facilities with cooking equipment represent a large percentage of occupancies inspectors will enter.

9–40

    • Ventilation hood
    • Exhaust
    • Fire protection systems installed above the cooking area
    • Systems should meet locally adopted code

Inspection focus

    • Placed over grease-producing equipment

Type I hoods

    • Over such equipment as dishwashers and ovens

Type II hoods

42 of 80

Recognize hazards associated with cooking equipment.

9–41

Cleanliness and functionality

No grease accumulation

Proper provisions for grease removal; regularly scheduled cleaning

Clearance of at least 18 inches (450 mm) from any combustible material

Fire extinguishers should be accessible and personnel should have been trained

Extinguishers should be compatible with the suppression system

43 of 80

Know what to look for when inspecting ventilation-hood systems.

9–42

Verify general cleanliness and maintenance of the cooking area and ductwork

Examine the system for any obvious damage, including mechanical damage

Verify that nozzles are properly oriented toward the protected hazard

(Cont.)

44 of 80

Know what to look for when inspecting ventilation-hood systems.

9–43

Verify all parts of the system to confirm that they are in their proper locations and connected

Inspect manual actuators for obstructions

Inspect the tamper indicators and seals to verify that they are intact

Check the maintenance tag or certificate for proper placement

(Cont.)

45 of 80

Know what to look for when inspecting ventilation-hood systems.

9–44

Verify that a detector or fusible link is provided for each protected cooking appliance located under the hood

Fusible links that control the activation of the fire extinguishing system should be replaced at least annually

Fusible links that appear to be distorted from frequent exposure to heat may need to be replaced more often

46 of 80

Know safety requirements for solid-fuel cooking equipment like grills and smokers.

9–45

Becoming very common in many restaurants

Includes wood-fired brick ovens and meat grilling or smoking equipment

Must be installed on combustible floors that extend 3 feet (900 mm) from the outside of the appliance in every direction

Requires grease removal devices

Requires a ventilation hood system to exhaust smoke and gases; spark arrestors must be located inside the hoods ahead of the filter system

(Cont.)

47 of 80

Know safety requirements for solid-fuel cooking equipment like grills and smokers.

9–46

Only a one-day supply of solid fuel is allowed in the same room as the appliance

Ashes must be removed from the firebox regularly so that the buildup of ashes does not interfere with the draft

Ashes must be disposed of in an approved container separate from containers containing other combustible waste

48 of 80

NOTE

Restaurants that operate open-air patios may also have propane or butane heaters or wood-burning fireplaces. These heaters or fireplaces may be in contact with or near awnings or other combustible materials, creating an exposure hazard through radiant heat or burning embers.

9–47

49 of 80

Understand items for to look for in fire suppression systems.

9–48

Courtesy of George Apple, Cosumnes Fire Department

A vital part of commercial cooking equipment

Be familiar with the systems in use in jurisdiction

Make sure cooking appliances protected by the system have not been changed or switched out

Verify an instruction sign for manual system operation is present

Verify employees have been trained to perform manual operations

Verify system has been maintained per NFPA® standards

50 of 80

Many commercial cooking establishments utilize wet-chemical systems.

9–49

Must meet the requirements in NFPA® 17A, Standard for Wet Chemical Extinguishing Systems

Requirements for these systems are also contained in UL Standard 300, Fire Testing of Fire Extinguishing Systems for Protection of Restaurant Cooking Areas

51 of 80

NOTE

An inspector should be aware that changes in the type of cooking oil used in fryers can require that a dry-chemical system be replaced by a wet-chemical system that is designed to control Class K fires. The adopted code may allow the continued use of the dry-chemical system as long as the system can be serviced and maintained.

9–50

52 of 80

REVIEW QUESTION

List some of the conditions inspectors must look for when inspecting cooking equipment like ventilation hoods.

9–51

53 of 80

There are several reasons industrial furnaces and ovens fail.

9–52

Inadequately trained operators

Lack of proper maintenance

Improper application of equipment

54 of 80

Know how industrial ovens and furnaces are classified.

9–53

    • Operates at approximately atmospheric pressure
    • Has a potential for explosion or fire hazard when flammable volatiles or combustible materials are processed or heated

Class A

    • Operates at approximately atmospheric pressure where no flammable volatiles or combustible materials are being heated

Class B

(Cont.)

55 of 80

Know how industrial ovens and furnaces are classified.

9–54

    • Potential hazard due to a flammable material being used or if a special atmosphere is present
    • Can use any type of heating system
    • Includes a special atmosphere supply system
    • Includes integral quench furnaces and molten salt bath furnaces

Class C

    • Operates at temperatures from above ambient to over 5,000°F (2 750°C)
    • Operates at pressures normally below atmospheric using any type of heating system
    • Can include the use of special processing atmospheres

Class D

56 of 80

Understand the fire and explosion hazards of industrial furnaces and ovens.

9–55

Failing to maintain required clearances

Ventilation systems, including makeup air and exhaust systems

Heat, gas, and smoke removal systems

Temperatures required for operation

Material handling equipment

57 of 80

Be familiar with proper housekeeping techniques that reduce hazards in industrial furnaces and ovens.

9–56

Remove combustible items from the area around the oven or furnace

Remove general dirt and debris on a regular basis

Maintain required clearances

Check/verify all automated controls and alarms

58 of 80

Be familiar with components commonly found on safety controls.

9–57

Switches

Valves

Relays

Controllers

Detectors

Interlocks

59 of 80

NOTE

It is important to check the schedule and the extent of the inspection, testing, and maintenance programs.

9–58

60 of 80

Understand the importance of interlocking systems.

9–59

It is important to interlock the entire system so that in the event of a malfunction, the equipment will deactivate and remove the remaining fuel from the system

Deactivation of the heating system by any safety feature or safety device requires that an operator manually intervene to reestablish normal system operation

61 of 80

REVIEW QUESTION

Name some of the special considerations inspectors need to be aware of when it comes to industrial furnaces and ovens.

9–60

62 of 80

Be familiar with different types of powered industrial trucks.

9–61

Personnel transportation vehicles

Special material handling vehicles

Emergency response vehicles

63 of 80

Be familiar with fuels used in powered industrial trucks.

9–62

Diesel

Gasoline

Liquefied petroleum gas (LPG) �(Most common)

Compressed natural gas (CNG)

Electric batteries (Most common)

Dual fuels (gasoline/LPG)

64 of 80

Be familiar with fuels used in powered industrial trucks.

9–63

Powered vehicles are found at industrial settings as well as in malls, schools, and even golf courses

Numerous age-restricted communities are encouraging vehicle use of this type

Power lifts can be found in convention centers, in hotels, and on construction sites

Requirements for powered industrial trucks are contained in most of the model fire codes

65 of 80

Know what conditions to watch for during inspections.

9–64

    • Should be kept at least 5 feet (1.5 m) from combustible materials
    • Charging areas should not be accessible to the public
    • Charging area should be vented to prevent an accumulation of hydrogen gas

Chargers

    • Should only be fueled outside buildings
    • Fuel storage should be in compliance with locally adopted fire codes

Liquid- or gas-fueled vehicles

(Cont.)

66 of 80

Know what conditions to watch for during inspections.

9–65

    • Should be performed in areas designated for that function

Repairs

    • Should only be used in the atmosphere for which it is specified
    • Should be marked with signs indicating the class of truck and any operational restrictions
    • Must be maintained in accordance with manufacturer’s instructions

Industrial trucks

67 of 80

REVIEW QUESTION

What conditions should an inspector be alert to when inspecting facilities that use industrial trucks?

9–66

68 of 80

Understand what to look for when inspecting tents.

9–67

Tents must be made of flame-resistant materials that are approved and tagged as such

69 of 80

Inspectors need to know specifics about tent requirements.

9–68

Materials that go inside the tent or on the tent such as banners or decorations must be treated with or made of flame-retardant material

Adopted building code includes permanent tents

Temporary tents fall under the jurisdiction of the adopted fire code

(Cont.)

70 of 80

NOTE

While 180 days within a 12-month period is a typical time for a tent to be considered to be temporary; local policy or practice may differ.

9–69

71 of 80

Inspectors need to know specifics about tent requirements.

9–70

All tents must meet the requirements of the large-scale test contained in NFPA® 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films

Tents must be tagged or certified that they meet the requirements

Inspectors should not attempt to test the flammability of materials on their own

Tents must be located according to the requirements of the adopted fire and building codes

(Cont.)

72 of 80

Inspectors need to know specifics about tent requirements.

9–71

Specified distances from property lines, vehicles, and other tents

Means of egress requirements as contained in the locally adopted building and fire codes

Storage and handling of flammable or combustible liquids in accordance with fire code requirements

Electrical installments in accordance with locally adopted codes (including extension cords)

Pyrotechnics and open flames are prohibited in any tents or temporary membrane structures

Access for emergency vehicles

(Cont.)

73 of 80

NOTE

When multiple tents are put together, the increased area under consideration may involve additional safety requirements and permits.

9–72

74 of 80

Inspectors need to know specifics about tent requirements.

9–73

Combustible vegetation must be cleared both inside the tent and up to 10 feet (3 m) around the outside of the tent

The inspecting authority agrees if vegetation has been removed properly

Hay, straw, and shavings may require treatment with fire-retardant chemicals or limited to amounts sufficient for daily care and feeding of animals

Sawdust may need to be treated with fire-retardant chemicals or kept damp, depending on code requirements

75 of 80

REVIEW QUESTION

Name some of the provisions required for tents.

9–74

76 of 80

�Learning Objective 2

Distinguish among hazardous processes that contribute to increased fire risk.

9–75

77 of 80

There are a number of potential hazardous processes an inspector may encounter.

9–76

Welding

Dipping and quenching operations

Application of flammable finishes

Dry cleaning operations

Dust hazards

78 of 80

Numerous locations may house multiple hazardous processes.

9–77

Manufacturing facilities

Auto repair and painting shops

Fabrication businesses

Furniture repair shops

Dry cleaning operations

Semiconductor/electronic manufacturing

Distilleries

Construction/ demolition sites

Commercial operations

79 of 80

Some operations can generate ignition sources or hazardous atmospheres.

9–78

Welding

Cutting

Grinding

Painting

Replacing roof coverings

80 of 80

Inspectors should be aware of these processes and their potential locations.

9–79

Some will be contained at specific facilities designed for their operations

Others may be present during inspections of other types of occupancies

There are locations where these hazardous processes may exist only during the use of the process; require a permit to perform

Be familiar with the code requirements for these processes

Recognize any code infractions when they are encountered