WORKING WITH UNBALANCED POWER �FOR PUMP MOTORS
PHIL LUTHER
MIDWEST HYDRO DRILLING
SYMPTOMS OF UNBALANCED POWER
High or Low Voltage
Loss of Phase
Overload
Underload
Unbalanced Power
4 AREAS
1. System Requirements
2. Pre-Installation
3. Start Up and Operations
4. Long Term Operations
SYSTEM REQUIREMENTS
A. IS THE INCOMING POWER AND TRANSFORMERS SIZED CORRECTLY?
1. TOTAL AMPERAGE LOAD MUST BE CALCULATED FOR THE TRANSFORMERS.
2. ADD IN THE SINGLE-PHASE LOADING FOR LIGHTS, HEATERS, AND CONTROLS.
3. OBSERVE TRANSFORMER SIZES OR SIDE OF GROUND TRANSFORMERS ON POWER POLES.
4. CAN STARTING LOAD BE HANDLED BY INCOMING POWER?
SYSTEM REQUIREMENTS
B. IS THE MOTOR SIZED CORRECTLY FOR THE PUMP END?
C. IS THE STARTER SIZED FOR THE MOTOR IN THE PANEL?
D. DO YOU HAVE QUICK TRIP HEATER OR OTHER MOTOR PROTECTION?
E. IS THE MOTOR CLASS SET CORRECTLY IN THE STARTER PARAMETERS? CLASS 10
SYSTEM REQUIREMENTS
F. MOTOR PROTECTION, OVERVOLTAGE, UNDERVOLTAGE, SHORT CYCLING, LOSS OF PHASE, OVERHEAT.
1. USE A MOTOR SAVER DEVICE, FRANKLIN SUB MONITOR, GRUNDFOS MP204 OR SOMETHING SIMILAR.
2. THESE UNITS WILL RECORD AND SHOW UNBALANCED POWER SO YOU CAN IMPLEMENT CHANGES.
1. CHECK THE DEPTH RATINGS AND CABLE BEING RATED FOR SUBMERSIBLE MOTOR POWER CABLE.
PRE-INSTALLATION
1. MOTOR SIZE OR HORSEPOWER, 3-PH. 460 VOLTS OR 230 VOLTS.
2. FULL LOAD AMPS; 30 HP 460V IS 39.5 AMPS AND
30 HP 230V IS 79 AMPS= 40-AMP DIFFERENCE
3. FRANKLIN AND HITACHI MOTORS HAVE SIMILAR AMPS AND THE GRUNDFOS MOTOR HAS HIGHER AMPS.
PRE-INSTALLATION
B. MAKE SURE THE TRANSFORMERS AND KVA CODE ARE
LARGE ENOUGH TO RUN THE LOAD.
SEE THE TRANSFORMER CAPACITY CHART
TRANSFORMER CAPACITY CHART
PRE-INSTALLATION
C. IS THE INCOMING POWER A TRUE 3-PHASE, OPEN DELTA OR WYE SETUP? YOU CAN TELL BY LOOKING TO SEE IF YOU HAVE TWO OR THREE TRANSFORMERS.
D. DO YOU HAVE TOO MUCH SINGLE-PHASE LOADING ON THE SYSTEM?
START UP AND OPERATIONS
1. 480 VOLTS FOR 460V MOTOR
START UP AND OPERATIONS
B. PERCENT VOLTAGE UNBALANCE IS DEFINED BY THE NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA):
100 TIMES THE ABSOLUTE VALUE OF THE MAXIMUM DEVIATION OF THE LINE VOLTAGE FROM THE AVERAGE VOLTAGE ON A THREE-PHASE SYSTEM, DIVIDED BY THE AVERAGE VOLTAGE.
FOR EXAMPLE, IF THE INCOMING POWER MEASURED LINE VOLTAGES OF 480, 483, 476= 480 VOLTS AVERAGE.
IT IS RECOMMENDED THAT INCOMING POWER VOLTAGE AT THE MOTOR TERMINAL DOES NOT EXCEED 1%. FOR EXAMPLE, 485V (HIGH) AND 475 (LOW) AVERAGE (NEMA) WOULD BE UNBALANCED.
START UP AND OPERATIONS
CAUSES OF VOLTAGE UNBALANCE INCLUDE:
CAUSES OF VOLTAGE UNBALANCE INCLUDE:
LONG TERM OPERATIONS�SUGGESTED ACTIONS:
SUGGESTED ACTIONS:
A. VFD WILL READJUST POWER TO MOTOR. THIS MEANS ALL 3 PHASES WILL HAVE SAME VOLTAGES.
B. CHANGE THE HERTZ TO SLOW RPM OF MOTOR TO FINE TUNE YOUR PUMP TO BETTER MEET YOUR NEEDS.
CREDITS
FRANKLIN ELECTRIC
US ENERGY DEPT.
NEMA
ABB
PHASE TECHNOLOGIES
GRUNDFOS PUMPS
PHIL LUTHER
MIDWEST HYDRO DRILLING
636-629-2424
PHIL@MHDS.US