Dry Type Transformers
Tips Engineer Zone
www.tipsengineerzone.in
�
Content
Useful References
Dry Transformer Maintenance
Dry Transformer Operation
Dry Transformer Commissioning
Dry Transformer Installation
Dry Transformer Components
Standard technical features
Main advantages
What is a dry transformer?
What is a dry transformer? �
Main advantages: safe and environmental friendly
Main advantages: The most economical
Environmental, climatic and fire classes
Environment
Climate
Fire
Dry transformers VS Oil transformers
The best alternative due to:
Types and Designs
Dry Transformer Components
1
2
3
4
5
6
7
8
9
1
0
1
2
3
4
5
6
7
8
9
1
0
Wheels
Foundation
Lower clamp
High-voltage connecting rod
Insulating cylinder
iron core
Neutral bar
Low-voltage winding
High-voltage winding
Upper clamp
Dry Transformer Components
1. Magnetic Core:
The magnetic core is made from laminations of grain-oriented silicon steel insulated with 0.25- 0.3 mm thickness. The choice and grade of steel and the 45 degrees cutting pattern and method of step-lap assembly minimize the loss level and the no-load current with the effect of a very low noise level.
Dry Transformer Components
2. Low Voltage Winding:
The low voltage winding is made of aluminum or copper foil to achieve zero axial stresses under short circuit conditions; the foil is insulated by a class F or H inter-layer film, pre-impregnated with heat-activated, epoxy resin.
The ends of the winding are protected and insulated using a class F or H insulator.
The whole winding is polymerized by being placed in an autoclave for 2 hours at 130°C which guarantees:
Each LV winding terminates in a tin-plated aluminum or copper connection point, enabling connections to be made without using a contact interface (grease, bi-metal strip). Assembly is carried out according to current practices, including using spring pressure washers under nuts and screw heads.
Dry Transformer Components
3. High Voltage Winding:
The high voltage winding is usually made and wounded by series aluminum foil. This kind of wounding method is because of the high turn numbers and small cross-section in high voltage winding.
These methods are used to obtain very low stress levels between adjacent conductors. This winding is cast and moulded under vacuum in a class F or H loading and fireproofed resin
Dry Transformer Components
Spacer strips (LV)
Support and spacers (LV)
dog bones
Layer insulation (LV)
Multi-layer insulation with B-stage epoxy resin coating
Outer bandings (LV)
Insulation cylinders
Cast-resin reinforcement (HV)
Dry Transformer Components
4. Voltage regulation
Some tap voltages are designed at high voltage side to control the voltage at the low voltage side and keeping it constant.
The variation step voltages are ±2 × 2.5% according to the rated voltage.
The variation of tap voltages is done via a piece of brass or copper at the high-voltage side.
The variation of tap voltages in dry transformers is off-circuit type, and the transformer must be turned off.
Low Voltage (V) | High Voltage (V) | Tap Number | Connection Status |
400 | 21000 | 1 | 6-5 |
20500 | 2 | 7-5 | |
20000 | 3 | 7-4 | |
19500 | 4 | 8-4 | |
19000 | 5 | 8-3 |
5
4
3
7
6
8
5
4
3
7
6
8
Dry Transformer transportation guidelines
Handling
Lifting is carried out using the 4 lifting holes for a transformer without an enclosure and by 2 lifting lugs in the case of a transformer with an enclosure. The slings should not form an inside angle greater than 60°.
The lifting capacity of the fork lift truck should first be checked. If suitable, the forks should be inserted inside the base channels after removing the rollers.
Towing the transformer with or without enclosure should be done from the under base. For this purpose hole of 27 mm diameter are provided on every side of the under base. owing can be done in two directions : in the axis of the under base and perpendicular to that axis.
Dry Transformer Maintenance guidelines
Storage
The transformer should be protected in storage from water drops and dust generating work (masonry, sanding, etc.).
Dry Transformer Installation
Installation and Commissioning
It's not the dry transformer manufacturer's responsibility to install it basically, but it's recommended for commissioning to take advice from the manufacturer's professionals.
For installation, the following guidelines are followed :
the ambient temperature for the transformer to be within the following limits :
-minimum : – 25°C ;
-maximum : + 40°C (unless a higher temperature is designed for based on information provided at the time of enquiry).
Dry Transformer Installation
Installation and Commissioning
For an altitude and a daily average temperature higher than 1000 meters above the sea and 30° C respectively, the dry transformer must be de-rated according to IEC 60076 and IEEE C57.91:
Type of cooling | % of kVA rating | ||
Decrease load for each °C higher temperature | Increase load for each °C lower temperature | Decrease load per 100m (330 ft) | |
AN, AF, AN/AF | 1.0 | 1.0 | |
Installation and Commissioning
Thread size | Torques | |
steel bolts (N.m) | brass bolts (N.m) | |
M8 | 20 | 10 |
M10 | 40 | 20 |
M12 | 75 | 35 |
M12 | 140 | 70 |
Dry Transformer Installation
Installation and Commissioning (forced ventilation )
In the event of temporary overloading, to avoid overheating of the windings, it is possible to install forced ventilation.
For powers equal or greater than 1000 kVA, it is possible to install forced ventilation to achieve a temporary increase in power of 40%, without any special modification.
However, if an increase in power is requested, account must be taken of the impact of this choice on the following points :
-Sections of cables and of Prefabricated Busbar Trunking (PBT),
-The rating of the transformer's protective circuit breaker,
-The size of inlet and outlet openings for air in the transformer room,
-The life span of fans in service, which is considerably shortened compared with that of the transformer
Dry Transformer Installation
High voltage side cable connection
The cable connection holes are reserved at the upper and lower ends of the connecting rod on the high voltage side of the transformer. Taking the delta connection as an example, the phase sequence at the upper end is U-V-W and the phase sequence at the lower end is V-W-U. Attention should be paid to correct phase sequence when connecting high voltage cables. Fasteners shall be used during the connection, and loosening preventive measures shall be taken to fix the cable at the terminal of the high-voltage connecting rod of the transformer.
Dry Transformer Installation
High voltage cable junction | Corresponding connection phase sequence |
Upper terminal | U-V-W |
Lower terminal | V-W-U |
Low voltage side bus-bar or cable connections
The low-voltage terminal of the transformer has reserved cable connection holes, and fasteners with loosening preventive measures are required to fix the cable or bus bar. If it is required to be equipped with copper-aluminium composite foil (cupal) as specially specified in the contract, the copper-aluminium composite foil (cupal) shall be installed between the low-voltage terminal of the transformer and the cable, or between the low-voltage terminal of the transformer and the bus bar. Please refer to the figure.
Dry Transformer Installation
Cable installation layout (with enclosure)
For the transformer with protective enclosure, cables in its high-voltage side and low-voltage side can be imported to internal part of the enclosure through the top or bottom of the enclosure, which can be connected to the corresponding wiring site of the transformer. •
The bending radius of the cable needs noting, to prevent force on end of cable connection.
Dry Transformer Installation
Cable installation layout (without enclosure)
The high voltage side cable can be connected to the transformer after layout in the bottom cable tray or after layout the top cable tray. Cable or bus bar can used for the low-voltage side connection. If the bus bar connection is used, soft connection transition is recommended to avoid mechanical impact on the low-voltage winding and reduce noise level due to structural reasons.
• High-voltage cables are not allowed to pass through the high-voltage connecting rod (delta connection) of the transformer.
Dry Transformer Installation
Electrical safety clearance
Sufficient space must be ensured around the transformer to ensure a smooth connection of the cable and the necessary electrical distance. The minimum clearance value for flashover protection is as below.
Dry Transformer Installation
Maximum voltage of the equipment (kV) | Minimum clearance value | ||
A (mm) | B (mm) | C (mm) | |
12 | 125-150 | 50 | 40 |
24 | 225-280 | 100 | 50-70 |
36 | 325-400 | 160 | 90-110 |
Commissioning of temperature control system
The transformer may be equipped with a temperature control system to monitor the temperature of the winding to prevent abnormal temperature rise of the winding, thereby protecting the transformer.
The temperature control system includes a temperature controller and a temperature sensor (PT100). The temperature sensor (PT100) is placed in the three-phase winding of the transformer. When the temperature reaches the set value, the temperature sensor (PT100) feeds back the corresponding temperature change to the temperature controller. After the temperature controller receives the corresponding feedback signal, it corresponds to different functional responses. The over-temperature alarm and over-temperature trip functions need to be connected with the relay protection system of the front-end equipment so that the higher-level equipment can be linked when the temperature controller acts.
Dry Transformer Installation
Temperature controller function description | Parameter settings |
Over-temperature trip | 140˚C |
Over-temperature alarm | 130˚C |
Fan on | 90˚C |
Ventilation of the Transformer Room
the ventilation of the substation or of the enclosure must ensure by natural convection the dissipation of the heat produced by the transformer’s total losses.
Dry Transformer Installation
Ventilation of the Transformer Room
Forced ventilation of the substation is necessary for ambient temperatures above 20°C, or small or badly ventilated rooms for applications with frequent overloads.
The fan can be thermostat controlled and operate as an extractor in the top part of the room.
Dry Transformer Installation
Ventilation (AN) of the Transformer Room (Example)
- Transformer 1000kVA,
-Po = 2300 W ,Pcc at 120°C = 11000 W,
i.e. P= 13.3 kW. If the distance between the grills = 2 m, then S = 1.7 m2 of net surface area necessary. If we imagine a grill obstructing the air inlet by 30% ; the air inlet grill surface area should then be 1.5 m×1.5 m, and that of the air outlet should be 1.5 m×1.6 m.
Pre-commissioning test
Tips:
Dry Transformer Commissioning
Tips:
HV winding
LV winding
200 V- 380 V
Pre-commissioning test
Tips:
Dry Transformer Commissioning
Test position | Test equipment (1 min) | Test value requirements |
HV- E | 2500 V | ≥100 MΩ |
LV- E | 2500 V | ≥50 MΩ |
HV- LV | 2500 V | ≥100 MΩ |
1
2
3
4
I. Voltage regulation
If the actual grid voltage deviates from the rated voltage of the transformer, the tapping gear of the transformer can be adjusted appropriately to control the output voltage value.
Tips:
Dry Transformer Operation
II. No load operation
When large capacity no-load transformers are put into operation, visible sparks may be generated at the joints of external components (especially at the core and clamps), but this phenomenon will soon disappear. This is due to physical reasons, and will not affect the safe operation of the transformer, so it is not a product defect.
III. inrush current
There is inrush current when the transformer is switched on, and the peak value can reach 6-8 times of rated current. The setting value of current quick protection for the transformer shall be larger than the peak value of inrush current, and the time limit shall be ≤ 0. 5 s. Therefore, no-load inrush impulse test shall be carried out before operation to check whether the relevant protection of the transformer is malfunction or not. If the protection value is set improperly, it will cause the tripping phenomenon in the later closing.
IV. long-term storage or overhauled
For long-term storage (storage time more than 3 months) or overhauled transformers or transformers to be used at ambient temperature below 0 ℃, it is recommended to operate without load for 12 hours before putting the transformers into load, and the load shall be gradually increased.
Dry Transformer Operation
V. overload operation
The transformers are designed to operate at rated power at ambient temperature defined by IEC 60076 :
Dry Transformer Operation
Ambient temperature (Average Annual temperature) | Load rating |
–20 °C | 124 % |
–10 °C | 118 % |
0 °C | 112 % |
+10 °C | 106 % |
+20 °C | 100 % |
+25 °C | 97% |
+30 °C | 93 % |
+35 °C | 90% |
https://www.worldweatheronline.com/
Maintenance
Cast-resin transformers are maintenance-free. Routinely inspect and clean the windings, bolt connections, alarm devices and all fan functions once a year. If the transformer is in dusty environment or close to the pollution source, it is recommended to clean the equipment every six months. It is recommended to fully inspect and clean the transformer every 5 years. Before maintenance, the transformer must be powered off and all terminals must be short-circuited and grounded.
Blow off the transformer with dry compressed air or wipe with dry cloth and alcohol (concentrations above 85%) to prevent the formation of creepage paths and blockage of cooling air passages.
Dry Transformer Maintenance
Sediment | Cleaning method |
Oily | 2 |
Carbonaceous | 1+2 |
Metal-containing | 1+2 |
Saline | 1+2 |
Dry dust | 1+2 |
Wet dust | 2 |
Use compressed air to blow the transformer. The compressed air must be oil-free and water-free, and the air pressure ≤ 6 bar. Vacuum cleaners can also be used instead of compressed air for dust collection.
Cleaning method 2
Wipe with a dry rag and alcohol (concentrations above 85%).
Dry Transformer Maintenance
S/N | Maintenance items | Maintenance cycle (recommended) | Use Tools | Methods: |
1 | Clean the surface stains of windings, pads and cores and stains at the heat dissipation holes of the enclosure | Normally, each year or more. Every 6 months for dusty and other polluted environment | Dry compressed air, pressure ≤ 3 bar, dry rags and alcohol | Select cleaning method according to Form 1 |
2 | Check winding surface condition | Normally, each year or more. Every 6 months for dusty and other polluted environment | Visual inspection | No blackening or cracks on the surface of the winding (if any, please contact the manufacturer) |
3 | Check bolt and nut tightening status at cable connections | Each year or after maintenance | Torque wrench | According to the torque table |
4 | Check correct tapping connections and bolt tightening | Each year or after maintenance | Torque wrench | According to the torque table |
5 | Check grounding condition of transformer body and enclosure | Each year or after maintenance | Torque wrench and visual inspection | According to the torque table |
Dry Transformer Maintenance
S/N | Maintenance items | Maintenance cycle (recommended) | Use Tools | Methods: |
6 | Check whether temperature controller settings, temperature probe and PT100 are normal. | Each year or after maintenance | Heat gun, power supply | The temperature of the temperature controller can be displayed normally by blowing the temperature probe with a heat gun. |
7 | Check the cooling fan | Each year or after maintenance | Power supply | Turn on the power supply, start the operation according to the manual of the temperature controller, and observe whether it rotates |
8 | Insulation resistance test | Each year or after maintenance or 5 years | Insulation resistance tester | Refer to for test values |
Dry Transformer Maintenance
S/N | Maintenance items | Maintenance cycle (recommended) | Use Tools | Methods: |
9 | Transformation ratio test | Every 5 years or after maintenance | Transformation ratio tester | Refer to test |
10 | DC resistance test | Every 5 years or after maintenance | DC resistance tester | Refer to test |
11 | Power frequency withstand voltage test* | Every 5 years or after maintenance | Power frequency withstand voltage tester | Refer to test |
* Applied withstand voltage test: The withstand voltage strength of the transformer is tested. The on-site tested withstand voltage value is 80% of the factory test voltage value. The factory test withstand voltage value can be shown in the factory test report and nameplate.
Dry Transformer Maintenance (Frequently asked questions guidelines (chart))
S/N | Question | Possible cause | Corrective measure |
1 | Temperature controller does not display | Temperature controller power cord is not connected | Measure whether the temperature controller power interface is energized and required to reconnect the power supply (85 ~ 250 V) |
It is internal failure of temperature controller, power interface of temperature controller is energized, but panel indicator lamp is not on | Contact Service Center to replace with a new temperature controller | ||
2 | Temperature controller three phase temperature display FOC or FCC | Wrong or poor connection or loose connection of temperature sensor | Check and press the temperature sensor wiring and tighten it according to the auxiliary wire diagram on the transformer certificate of conformity |
Temperature sensor probe is damaged | Contact Service Center to replace with a new temperature controller |
S/N | Question | Possible cause | Corrective measure |
2 | Three-phase temperature display of temperature controller differs greatly | Temperature sensor probe is not fully inserted into thermometer tube (three-phase probe is inserted at different depths) | Check the position of the temperature probe and place it correctly |
Cooling fan is damaged | Contact Service Center to replace with a new temperature controller | ||
Temperature sensor probe is damaged | Contact Service Center to replace with a new temperature controller | ||
Three-phase load of transformer is not balanced | Check three-phase load and voltage, current | ||
3 | The temperature controller cannot communicate properly with the monitoring device | Wrong address setting for temperature controller | Please refer to the use manual for the temperature controller |
The communication cable of the temperature controller and the strong electric cable are arranged together, which causes the interference of the communication signal | Properly lay out the cables |
S/N | Question | Possible cause | Corrective measure |
4 | Noise is abnormal | Primary side voltage exceeds tapping rated voltage | Disconnect the power of transformer and adjust tap gear |
The bus bar is not fixed well and there is resonance. The transformer is not well fixed with the ground, and the resonance enclosure plate is not fixed tightly, and there is resonance | Bus bar, enclosure board and transformer base are well fixed | ||
There are unclamped free ends in the iron core or clamping parts, and there are high frequency vibrations during the excitation of the iron core, resulting in abnormal noise | Check the fastening core and clamping piece and press the free end tight with insulating material | ||
Within the same power distribution room, multiple devices are placed close together, causing wall reflections and noise overlapping | Reasonably lay out equipment position in power distribution room | ||
In the transformer load, equipment such as frequency converter produces large harmonics in the system, which makes the core excitation uneven and causes noise* | Filter device is designed in low voltage system | ||
Transformer is under overload operation state | Check the load and distribute the load reasonably |
*De-rating the Transformers according to non sinusoidal currents (Slide 44)
S/N | Question | Possible cause | Corrective measure |
5 | Cooling fan is not running | Temperature does not reach fan start temperature value | Refer to factory temperature setting value and setting method |
Cooling fan is damaged | Contact Service Center to replace with a new cooling fan | ||
6 | Low side output voltage is high or low | Grid input voltage is high or low | Adjust the tap gear of transformer |
7 | Transformer over-temperature alarm, trip | Transformer overload (overvoltage, over current) operation | Check transformer load |
Cooling of transformer fails | Check whether the cooling fan is working properly and check whether the cooling air duct is blocked | ||
8 | Winding surface discharge | Severe stains (dust, etc.) on the surface of the winding | Clean stains on windings, pads, etc. |
Short circuit on high and low voltage lines | Check high-voltage lines | ||
High and low voltage transmission lines suffer from overvoltage impulse | Optimize system protection functions |
S/N | Question | Possible cause | Corrective measure |
8 | Winding surface discharge | There is insufficient distance between metal structure and winding | minimum insulation clearance requirements |
9 | Winding ablation and blackening | Upon the service life of the transformer and natural damage; poor heat dissipation; long-term overload; short circuit of external wiring; system overload; wrong cable connection; metal foreign body falling into the cooling air duct of the winding; unscrewed torque of tap gear bolt; short circuit fault inside the winding, etc. | On-site inspection is required. Please contact service center for such inspection. |
Dry Transformer Maintenance (Frequently asked questions guidelines (chart))
Loading transformers with non sinusoidal currents
Dry Transformer Operation
All losses referred to the reference temperature.
When transformer supply a non sinusoidal load current with the same rms value than rated current, DC losses remain constant but winding eddy losses increase due to the higher frequency of the harmonics, as a result, winding temperature rise increases and temperature limits can be exceed.
Loading transformers with non sinusoidal currents
Dry Transformer Operation
It is a measurement of the harmonic distortion present in a signal and is defined as the ratio of the sum of the powers of all harmonic components to the power of the fundamental frequency.
K-factor defines the non-linear load a transformer can tolerate without overheating or damage. The basis for K factor is seen in the ABB Document (Loading transformers with non sinusoidal currents). This document identifies the method for correctly de-rating transformers for non-linear loads.
Loading transformers with non sinusoidal currents
Dry Transformer Operation
* Remark: this equivalence list is valid up to 3150kVA transformers
Loading transformers with non sinusoidal currents (Example)
Dry Transformer Operation
the temperature rise limit shall be guaranteed at such equivalent power as well.
Therefore, should the temperature rise test is requested, during the full load part of the test the current must be equal to the rated current multiplied by the proper Factor-K, i.e. assuming the no load voltage level on LV side is 417V (Dyn11), rated current will be
2000/ (417×√3) = 2.77kA, however test must be run at 2.77×1.28= 3.54kA (corresponding
to 2560kVA).
Excitation Transformer
Dry Transformer
Excitation Transformer
Dry Transformer
Electrostatic shielding
Excitation Transformer
Dry Transformer
Excitation Transformer
Dry Transformer
Power (kVA) | Height (m) | Temperature (°C) | THD (%) |
2410 | 1650 | 40 | 29.7 |
2770.11 | 1000 | 40 | 29.7 |
2541.39 | 1000 | 40 | 0 |
Dry Transformer
The First Indoor 110KV/35KV 31.5MVA Cast Resin Transformer (CRT) and GIS Substation Layout
Tips Engineer Zone
www.tipsengineerzone.in