Data Center Heat Re-use with Natural Refrigerant CO2 (R-744)�

Seth Chicos

M&M Carnot

seth.chicos@mmcarnot.com

2 of 21

2

AGENDA

​

  • Data Center Heat Re-use Chillers
  • Application of Natural Refrigerant CO2 R-744 for Data Center Applications
  • Natural Refrigerants for Heat Re-use
  • Future innovation for Heat Re-use with CRAC units

3 of 21

Carnot�Supermarket

Carnot�Industrial

Carnot�Chiller

AquilonTM�Data Center

A pioneer in transcritical CO2 refrigeration�and cooling systems

« See the possible where the others see the impossible »

4 of 21

4

Carnot Data Center Chiller w/ Heat Reuse

  • Downtown Office Space
    • 6 Chilled water CRAC units – Total 80 Tons (280kW)
    • (2) 80 Ton chillers w/ Synthetic Refrigerant
    • Natural Gas Boilers for Comfort HVAC
    • Chilled Water loop temperature 13.3/6.7C ~44/56F
    • 10L/s or 160gpm
    • Heat Recovery – 300kW
      • 42.8C to 55C Hot Water (109F-131F)

​

​

​

5 of 21

5

Data Center Chiller Design

6 of 21

6

7 of 21

7

HEAT RE-USE CHILLER COMPONENTS

8 of 21

8

Carbon Dioxide : History of a Refrigerant

Carbon Dioxide : History of a Refrigerant

1850

Alexander Twining proposed CO2 as a refrigerant in his British patent

1866

TSC Lowe (American) introduced CO2 compressor

1866

First refrigeration system running on R-744

1928

CFC arrival

on the market

1950

R-744 completely phased out

1920-30

Systems in subcritical operation

1989

Montreal�Protocol

1990

Renewed

Interest in

The early 90’s

9 of 21

9

Montreal Protocol and Kigali Amendment

  • January 1, 2019 marks the coming into force of the Kigali Amendment to the Montreal Protocol. It is an international treaty that aims to reduce the expected production and consumption of very powerful hydrofluorocarbons (HFCs), greenhouse gases, by more than 80% over the next 30 years. If fully supported, the amendment will allow, by the end of this century, a reduction of up to 0.4°C in global warming.��Signed at the end of 2016 in Kigali (Rwanda) by 197 states, it has already been ratified by 65 countries��

Description

  • Signing Date: October 15th 2016
  • Starting Date: January 1st 2019
  • Starting reduction of 10% (2019) to 85% (2036)
  • HFC Reduction because of their global warming potential

10 of 21

10

Carbon Dioxide :Comparative Analysis with synthetic refrigerants (compared to NH3)

11 of 21

11

AquilonTM Natural Refrigerant CRAC units

Capacity: 15TR (52 kW) 🡪 48TR (175 kW)

12 of 21

12

CO2 Advantages: Rain Cycle Free-CoolingTM

13 of 21

13

Project

  • Trois-Rivières
  • Installation: Summer 2022

​

Description

  • 2x15T CRAC Units
    • Upflow Units
  • Gas Cooler with ECM Fans
  • Orbital Welding and bended tubing

Innovations

  • Rain Cycle Free-CoolingTM

14 of 21

14

Option�CO2 / CO2

Option�CO2 / Water

02

01

  • Operational resilience
  • No oil/water in the data room
  • Energy savings over 70%

Cumulus (Natural Refrigerant In-Row system)�Capacity: 10TR (40 kW) 🡪 1 unit (40 kW)

02

15 of 21

15

CO2 Advantages: Rain Cycle Free-CoolingTM

CRAC�units

In Row�units

16 of 21

16

CO2 TC Chillers

BEFORE

AFTER

17 of 21

17

CO2 TC Chillers

  • Complete and integrated solution

— Process or HVAC chilled water loop

  • Water, glycol, brine
  • Down to -40°F process temp.

— Process or HVAC hot water loop

  • Water, glycol, brine
  • Combined EER (COP) up to 55 (16)

— Direct CO2 to Domestic hot water loop

— Reduced foot print

— Full redundancy on key components

— Optional integrated pump skid

— Optional patented Rain Cycle Free-CoolingTM

Heat Re-Use

Domestic Hot Water / Snow Melt / regeneration of desicant wheel for dehumidification / pool water heat / Comfort cooling Air Pre-heat

​

18 of 21

18

OTHER HEAT RECLAIM CHILLER DESIGNS

19 of 21

19

CO2 TO Water Heat Exchanger

  • Located above load
  • Heat is rejected to CO2 transferred to building water loop
  • Could be chilled water / heat pump loop
  • Paired with Perimeter style unit, allows CO2 system to reject heat into hot water loop, or outside to gas cooler when heat isn’t required.
  • Free Cooling allowed when heat not needed

20 of 21

20

21 of 21

21