1 of 46

Module 2

Single-phase Circuits (Continued)

Three-phase Circuits

2 of 46

����������Single-phase Circuits (Continued)�

3 of 46

A.C.Through Series R-L Circuit

  • Consider a circuit consisting of pure resistance R ohms connected in series with a pure inductance of L henries.
  • The series combination is connected

across a.c. supply given by

v =Vm sin ωt

4 of 46

  • Circuit draws a current I then there are two voltage drops,

a) Drop across pure resistance, VR=IR

b) Drop across pure inductance, VL =I XL

where XL=2πf L

I = r.m.s. value of current drawn

VR,VL= r.m.s. values of voltage drops

  • The Kirchhoff’s law can be applied to the a.c. circuit but only the point to remember is the addition of voltages should be vector addition.

V = VR + VL

V = I R + I XL

5 of 46

  • The phasor diagram and the voltage triangle are shown as follows:

6 of 46

7 of 46

  • In rectangular form the impedance is denoted as

8 of 46

Power

9 of 46

A.C. Through Series R-c Circuit

  • Consider a circuit consisting of pure resistance R-ohms and connected in series with a pure capacitor of C-Farads.
  • The series combination is connected across

a.c. supply given by v =Vm sin ωt.

  • Circuit draws a current I, then there are

two voltage drops,

a. Drop across pure resistance, VR = I R

b. Drop across pure inductance, VC = 𝐼XC

10 of 46

  • The Kirchoff’s law can be applied to the a.c. circuit but

only the point to remember is the addition of voltages should be vector addition.

V = VR + VC

V = I R + I XC

The phasor diagram and the voltage triangle

11 of 46

12 of 46

Impedance

  • Similar to R-L series circuit, in this case also, the impedance is nothing but opposition to the flow of alternating current.
  • It is measured in ohms given by

13 of 46

A.C. Through Series R-L-C Circuit

  • Consider a circuit consisting of resistance R Ohms, pure Inductance L Henries and capacitance C Farads connected in series with each other across a.c. supply. The circuit is as shown below.

14 of 46

  • The a.c. supply is given by, 𝑣 = 𝑉𝑚 𝑠𝑖𝑛𝜔𝑡
  • The circuit draws a current I. Due to current I, there are different voltage drops across R, L and C which are given by,

a. Voltage across R, VR = I R ... VR is in phase with I.

b. Voltage across L, VL = I XL ... where VL leads I by 90°.

c. Voltage across C, VC = I XC ... where VC lags I by 90°

According to Kirchoff’s law we can write

V = V 𝑅 + V 𝐿 + VC

15 of 46

  • Case(i): 𝑿𝑳 > 𝑿C

So, if 𝑣 = 𝑉𝑚𝑠𝑖𝑛𝜔𝑡, then 𝑖 = 𝐼𝑚𝑠𝑖𝑛(𝜔𝑡– 𝜙) as current lags voltage by angle 𝜙.

16 of 46

  • Case(ii): 𝐗𝐋 < XC

  • The current is said to be capacitive in nature. The phasor sum of VR and(VC − VL) gives the resultant supply voltage V. Current I leads the voltage V by 𝝓.

17 of 46

  • Case (iii): 𝐗𝐋=𝐗𝐂
  • When 𝐗𝐋= 𝐗𝐂, obviously 𝐕𝐋= 𝐕𝐂. So VL and VC will cancel each other and their resultant is zero.
  • So, 𝐕𝐑 = V in such case and overall circuit is purely resistive in nature.
  • The phasor diagram for the above case is shown

18 of 46

����Three-phase Circuits

19 of 46

Advantages of Three Phase System

  • The output of three phase machine is always greater than single phase machine of same size, approximately 1.5 times.
  • For a given size and voltage a three phase alternator occupies less space and has less cost too than single phase having same rating.
  • It is possible to produce rotating magnetic field with stationary coils by using three phase system.
  • Three phase motors are self starting.

20 of 46

Generation of Three Phase Voltage System

21 of 46

  • The ends of each coil are brought out through the slip

ring and brush arrangement to collect the induced e.m.f.

  • Let eR , eY and eB be the three independent voltages in coil R1R2, Y1Y2 and B1B2 respectively.
  • All of them will be displaced by one another by 120°.

22 of 46

23 of 46

Star Connection

  • The star connection is formed by connecting starting or terminating ends of all the three windings together.
  • The ends R1 - Y1 - B1 are connected or ends R2 - Y2 - B2 are connected together. This common point is called Neutral Point.

24 of 46

25 of 46

Delta Connection�

  • The delta is formed by connecting one end of winding to starting end of other and connections are continued to form a dosed loop.
  • The supply terminals are taken out from the three junction points.

26 of 46

27 of 46

Relation For Star Connected Load

28 of 46

  • Line voltages VL = VRY= VYB = VBR
  • While Line currents IL = IR= IY = IB
  • Phase voltages Vph= VR= VY=VB
  • Phase currents Iph=IR=IY=IB

Also, From the circuit diagram

𝐈𝐩𝐡= 𝐈𝐋

29 of 46

30 of 46

  • The three phase voltages are displaced by 120° from each other.

The phasor diagram to get VRY is shown.

  • The VY is reversed to get −VY and then it is added to VR to get VRY.

  • The perpendicular is drawn from point A on vector OB representing VL.

  • In triangle OAB, the sides OA and AB are same as phase voltages. Hence OB bisects angle between VR and −VY.

31 of 46

32 of 46

33 of 46

Relation For Delta Connected Load

34 of 46

35 of 46

36 of 46

37 of 46

38 of 46

Measurement Of Power And Power Factor By Two Wattmeter Method

  • Consider star connected load and two wattmeter connected as shown in figure.

39 of 46

  • Let us consider the RMS values of current and voltage to prove that sum of two wattmeter gives the total power consumed by the three phase load.
  • W1 = IRx VRBx cos∠IR^VRB
  • W2 = IYx VYBx cos∠IY^VYB

40 of 46

41 of 46

  • Angle between VY and IY = φ
  • Vph= VR= VY=VB and VRB= VYB= VL
  • IR= IY= IL=IPH(star)

42 of 46

  • From the vector diagram

Angle between VRB and IR = 30° - φ

Angle between VYB and IY = 30° + φ

W1 = IRVRBcos(30° - φ ) i.e. W1 = ILVLcos(30° - φ)

W2 = IYVYBcos(30° + φ) i.e. W2 = ILVLcos(30° + φ)

W1 + W2 = IL VL [cos(30° - φ ) + cos(30° + φ) ]

= 2 IL VL (√3)/ 2 cos φ

𝐖𝟏 + 𝐖𝟐= √𝟑 𝐈𝐋 𝐕𝐋 cos φ = Total 3 phase power

43 of 46

Power Factor Calculation By Two Wattmeter Method

In case of balanced load, the p.f. can be calculated from W1and W2 readings.

For balanced lagging p.f.

W1 = ILVLcos(30° - φ ),

W2 = ILVLcos(30° + φ)

𝐖𝟏 + 𝐖𝟐= √𝟑 𝐈𝐋 𝐕𝐋 cos φ (i)

𝐖𝟏 − 𝐖𝟐= 𝐈𝐋 𝐕𝐋 sin φ (ii)

44 of 46

  • Taking ratio of equation (ii) and (i)

45 of 46

Effect Of Power Factor On Wattmeter Readings

  • For balanced lagging p.f.

W1 = IL VLcos(30° - φ ), W2 = ILVLcos(30° + φ)

  • Consider different cases

Case (i) cosφ = 0 i.e. φ=90°

W1 = IL VLcos(30° - 90°) = ½ IL VL

W2 = ILVLcos(30° + 90°) = - ½ IL VL

i. e. 𝐖𝟏 + 𝐖𝟐 = 0

|𝐖𝟏| = |𝐖𝟐| but 𝐖𝟐 = - 𝐖1

46 of 46

  • Case (ii) cos φ = 0.5 i.e. φ= 60°

W1 = ILVLcos(30° - 60°) = √3/2 IL VL

W2 = ILVLcos(30° + 60°) = 0

𝐖𝟏 + 𝐖𝟐 = 𝐖𝟏 = Total Power

  • Case (iii) cosφ =1 i.e φ = 0

W1 = IL VLcos(30° - 0°) = √3/2 IL VL

W2 = ILVLcos(30° + 0°) = √3/2 IL VL

Both wattmeters read equal and positive