Page 1 of 166

MAGNUM+

TK 60275-4-MM (Rev. 1, 11/10)

Copyright© 2008 Ingersoll Rand Climate Control Technologies - European Served Area

Printed in Ireland

Page 2 of 166

2

Page 3 of 166

This manual is published strictly for informational purposes. The information so provided should

not be considered as all-inclusive or covering all contingencies. Thermo King Corporation

should be consulted if further information is required.

Sale of product shown in this manual is subject to Thermo King’s terms and conditions.

This includes, but not limited to, the Thermo King Limited Express Warranty. Such terms

and conditions are available upon request. Thermo King’s warranty will not apply to any

equipment which has been “so repaired or altered outside the manufacturer’s plants as,

in the manufacturer’s judgment, to effect its stability.”

No warranties, express or implied, are made regarding the information,

recommendations, and descriptions contained herein. This includes warranties of

fitness for a particular purpose or merchantability, or warranties arising from course of

dealing or usage of trade. The manufacturer is not responsible and will not be held liable

in contract or in tort (including negligence) for any special, indirect or consequential

damages. This includes injury or damage caused to vehicles, contents or persons, by

reason of the installation of any Thermo King product or its mechanical failure.

The maintenance information in this manual covers unit models:

Base Unit

MAGNUM+ 098203

For further information, refer to:

Parts Manuals

MAGNUM Parts List TK 54356

Operation, Diagnosis and Refrigeration Maintenance Manuals

Diagnosing Thermo King Container Refrigeration Systems TK 41166

Electrostatic Discharge (ESD) Training Guide TK 40282

Evacuation Station Operation and Field Application TK 40612

Tool Catalog TK 5955

The information in this manual is provided to assist owners, operators and service people in the proper

upkeep and maintenance of Thermo King units.

Page 4 of 166

Recover Refrigerant

At Thermo King, we recognize the need to preserve the environment

and limit the potential harm to the ozone layer that can result from

allowing refrigerant to escape into the atmosphere.

We strictly adhere to a policy that promotes the recovery and limits

the loss of refrigerant into the atmosphere.

In addition, service personnel must be aware of Federal regulations

concerning the use of refrigerants and the certification of technicians.

For additional information on regulations and technician certification

programs, contact your local Thermo King dealer.

R-404A

WARNING: Use only Polyol Ester-based refrigeration compressor oil in

R-404A. See Thermo King Parts Manual for part number.

Do not mix Polyol Ester and standard synthetic compressor oils. Keep Polyol

Ester compressor oil in tightly sealed containers. If Polyol Ester oil becomes

contaminated with moisture or standard oils, dispose of properly–DO NOT USE.

When servicing Thermo King R-404A unit, use only those service tools certified

for and dedicated to R-404A refrigerant and Polyol Ester compressor oils.

Residual non-HFX refrigerants or oils will contaminate R-404A systems.

Page 10 of 166

List Of Figures

10

Figure 59: Resistance Values for temperature sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106

Figure 60: Service Fittings Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .107

Figure 61: Service Valve Back Seated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108

Figure 62: Service Valve Open to Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108

Figure 63: Service Valve Front Seated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108

Figure 64: Balancing the Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108

Figure 65: Removing Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

Figure 66: Gauge Manifold Closed to Center Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

Figure 67: Gauge Manifold Open to Center Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .109

Figure 68: Charging the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .109

Figure 69: Purging Gauge Manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .110

Figure 70: Receiver Tank Sight Glass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111

Figure 71: Test for Refrigerant Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112

Figure 72: Typical Pressurized Gas Bottle with Pressure Regulator and Gauges . . . . . . . . . . . . . . . . . . . . . .112

Figure 73: Evacuation Station and Unit Hook-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

Figure 74: Constant Pressure Rise After Evacuation Indicates System Leak . . . . . . . . . . . . . . . . . . . . . . . . . .119

Figure 75: Pressure Rise Levels Off After Evacuation Indicates Moisture in System . . . . . . . . . . . . . . . . . . . .119

Figure 76: Scroll Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121

Figure 77: Filter Drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123

Figure 78: TXV Valve and Element Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124

Figure 79: Economizer Expansion Valve and Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125

Figure 80: Receiver Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127

Figure 81: Water-Cooled Condenser Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127

Figure 82: Vapor Injection Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127

Figure 83: Digital Control Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129

Figure 84: Mounting Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .131

Figure 85: Condenser Fan Blade Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .132

Figure 86: Evaporator Fan Blade Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .132

Figure 87: Air Exchange System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133

Page 11 of 166

11

Safety Instructions

General Precautions

• Always wear goggles or safety glasses.

Refrigerant liquid and battery acid can

permanently damage the eyes.

• Never operate the unit with the discharge

valve closed. Never close the compressor

discharge valve with the unit in operation.

• Keep your hands, clothing and tools clear of

the fans when the refrigeration unit is running.

If it is necessary to run the refrigeration unit

with covers removed, be very careful with

tools or meters being used in the area.

• Check the condition of the gauge manifold

hoses. Never let the hoses come in contact

with a fan motor blade or any hot surface.

• Never apply heat to a sealed refrigeration

system or container.

• Fluorocarbon refrigerants produce toxic gases

in the presence of an open flame or electrical

arc. The gases are severe respiratory irritants

capable of causing death.

• Firmly tighten all mounting bolts. Check each

bolt for correct length for their particular

application.

• Use extreme caution when drilling holes in the

unit. The holes may weaken structural

components. Holes drilled into electrical

wiring can cause fire or explosion. Holes

drilled into the refrigeration system may

release refrigerant.

• Use caution when working around exposed

coil fins. The fins can cause painful

lacerations.

• Use caution when working with a refrigerant

or refrigeration system in any closed or

confined area with a limited air supply (for

example, a trailer, container or in the hold of a

ship). Refrigerant tends to displace air and can

cause oxygen depletion. This can result in

suffocation and possible death.

• Use caution and follow the manufacturer’s

suggested practices when using ladders or

scaffolds.

Refrigerant Oil Precautions

Observe the following precautions when working

with or around refrigerant oil:

• Do not allow refrigerant oil to contact your

eyes.

• Rubber gloves are recommended when

handling Polyol Ester based refrigerant oil.

• Do not allow prolonged or repeated contact

with skin or clothing.

• Immediately wash all exposed skin after

handling refrigerant oil.

Use the following First Aid practices if needed.

Eyes: Immediately flush eyes with large amounts

of water. Continue flushing for at least 15 minutes

while holding the eyelids open. Get prompt

medical attention.

Skin: Remove contaminated clothing. Wash

thoroughly with soap and water. Get medical

attention if irritation persists.

Inhalation: Move victim to fresh air. Restore

breathing if necessary. Stay with victim until

arrival of emergency personnel.

Ingestion: Do not induce vomiting. Contact a

local poison control center or physician

immediately.

Electrical Precautions

The possibility of serious or fatal injury from

electrical shock exists when servicing a

refrigeration unit. Extreme care must be used

when working with a refrigeration unit that is

connected to its power source. Extreme care must

be used even if the unit is not running. Lethal

voltage potentials can exist at the unit power cord,

inside the control box, inside any high voltage

junction box, at the motors and within the wiring

harnesses.

Precautions

In general disconnect the units power cord before

repairing or changing any electrical

components.

Note that even though the controller is turned off,

one of the phases is still live and represents

Page 12 of 166

Safety Instructions

12

a potential danger of electrocution

Where turning of the unit is not possible (for

example at voltage measuring or troubleshoot- ing), follow safety precautions below.

• Turn the unit On/Off switch to Off before

connecting or disconnecting the unit power

plug. Never attempt to stop the unit by

disconnecting the power plug.

• Be certain the unit power plug is clean and dry

before connecting it to a power source.

• Use tools with insulated handles. Use tools

that are in good condition. Never hold metal

tools in your hand if exposed, energized

conductors are within reach.

• Do not make any rapid moves when working

with high voltage circuits. Do not grab a

falling tool or other object. People do not

contact high voltage wires on purpose. It

occurs from an unplanned movement.

• Treat all wires and connections as high

voltage until ammeter and wiring diagram

show otherwise.

• Never work alone on high voltage circuits on

the refrigeration unit. Another person should

always be standing by in the event of an

accident to shut off the refrigeration unit and

to aid a victim.

• Have electrically insulated gloves, cable

cutters and safety glasses available in the

immediate vicinity in the event of an accident.

First Aid

IMMEDIATE action must be initiated after a

person has received an electrical shock. Obtain

immediate medical assistance.

The source of shock must be immediately

removed. Shut down the power or remove the

victim from the source. If it is not possible to shut

off the power, the wire should be cut with either

an insulated instrument (e.g., a wooden handled

axe or cable cutters with heavy insulated handles).

A rescuer wearing electrically insulated gloves

and safety glasses could also cut the wire. Do not

look at the wire while it is being cut. The ensuing

flash can cause burns and blindness.

Pull the victim off with a non-conductive material

if the victim has to be removed from a live circuit.

Use the victim’s coat, a rope, wood, or loop your

belt around the victim’s leg or arm and pull the

victim off. Do not touch the victim. You can

receive a shock from current flowing through the

victim’s body.

Check immediately for the presence of a pulse and

respiration after separating the victim from power

source. If a pulse is not present, start CPR (Cardio

Pulmonary Resuscitation) and call for emergency

medical assistance. Respiration may also be

restored by using mouth-to-mouth resuscitation.

Low Voltage

Control circuits are low voltage (24 Vac and 12

Vdc). This voltage potential is not considered

dangerous. Large amount of current available

(over 30 amperes) can cause severe burns if

shorted to ground. Do not wear jewelry, watch or

rings. These items can shortcut electrical circuits

and cause severe burns to the wearer.

Electrostatic Discharge

Precautions

Precautions must be taken to prevent electrostatic

discharge while servicing the MP-3000a

microprocessor and related components. The risk

of significant damage to the electronic

components of the unit is possible if these

precautionary measures are not followed. The

primary risk potential results from the failure to

wear adequate electrostatic discharge preventive

equipment when handling and servicing the

controller. The second cause results from electric

welding on the unit and container chassis without

taking precautionary steps.

Electrostatic Discharge and the

Controller

You must avoid electrostatic discharges when

servicing the controller. Solid-state integrated

circuit components can be severely damaged or

destroyed with less than a small spark from a

finger to metal object. You must rigidly adhere to

the following statements when servicing these

units. This will avoid controller damage or

destruction.

Page 13 of 166

Safety Instructions

13

• Disconnect all power to the unit.

• Avoid wearing clothing that generates static

electricity (wool, nylon, polyester, etc.).

• Do wear a static discharge wrist strap (refer to

Tool Catalog) with the lead end connected to

the controller's ground terminal. These straps

are available at most electronic equipment

distributors. Do not wear these straps with

power applied to the unit.

• Avoid contacting the electronic components

on the circuit boards of the unit being

serviced.

• Leave the circuit boards in their static proof

packing materials until ready for installation.

• Return a defective controller for repair in the

same static protective packing materials from

which the replacement component was

removed.

• Check the wiring after servicing the unit for

possible errors. Complete this task before

restoring power.

Welding of Units or Containers

Electric welding can cause serious damage to

electronic circuits when performed on any portion

of the refrigeration unit, container or container

chassis with the refrigeration unit attached. It is

necessary to ensure that welding currents are not

allowed to flow through the electronic circuits of

the unit. The following statements must be rigidly

adhered to when servicing these units to avoid

damage or destruction.

• Disconnect all power to the refrigeration unit.

• Disconnect all quick-disconnect wire

harnesses from the back of the controller.

• Disconnect all wire harnesses from the

Remote Monitor Modem (RMM).

• Switch all of the electrical circuit breakers in

the control box to the Off position.

• Weld unit and/or container per normal

welding procedures. Keep ground return

electrode as close to the area to be welded as

practical. This will reduce the likelihood of

stray welding currents passing through any

electrical or electronic circuits.

• The unit power cables, wiring and circuit

breakers must be restored to their normal

condition when the welding operation is

completed.

Removing Refrigerant Properly

Use a refrigerant recovery process that prevents or

absolutely minimizes refrigerant escaping to the

atmosphere. Fluorocarbon refrigerants are

classified as safe refrigerants when proper tools

and procedures are used. Certain precautions must

be observed when handling them or servicing a

unit in which they are used.

Fluorocarbon refrigerants evaporate rapidly,

freezing anything they contact when exposed to

the atmosphere in the liquid state. In the event of

frost bite, attempt to protect the frozen area from

further injury, warm the affected area rapidly, and

maintain respiration.

• Eyes: For contact with liquid, immediately

flush eyes with large amounts of water and get

prompt medical attention.

• Skin: Flush area with large amounts of

lukewarm water. Do not apply heat. Remove

contaminated clothing and shoes. Wrap burns

with dry, sterile, bulky dressing to protect

from infection/injury. Get medical attention.

Wash contaminated clothing before reuse.

• Inhalation: Move victim to fresh air and use

CPR or mouth-to-mouth ventilation, if

necessary. Stay with victim until arrival of

emergency medical personnel.

Page 14 of 166

Safety Instructions

14

Nameplate and Warning Locations

1. Controller Nameplate

2. Unit Nameplate

3. Compressor Nameplate

2

BEN074

AXA0214

AXA0215

AXA0218

AXA0217

AXA0216

1

3

Page 15 of 166

Safety Instructions

15

Identifying Unit Safety and

Warning Decals

Serial number decals, refrigerant type decals and

warning decals appear on all Thermo King®

equipment. These decals provide information that

may be needed to service or repair the unit.

Service technicians should read and follow the

instructions on all warning decals. See Figure .

Locating Serial Numbers

Serial numbers can be found on the component’s

nameplate.

• Electric Motor Nameplate: Attached to the

motor housing.

• Compressor Nameplate: On front of the

compressor.

• Unit Nameplate: On unit frame in power cord

storage compartment.

• MP-4000 Controller Nameplate: On back of

controller.

Page 16 of 166

Safety Instructions

16

Page 17 of 166

17

Service Guide

Service Guide

A closely followed maintenance program will help to keep your Thermo King unit in top operating

condition.

The following service guide table should be used as a guide when inspecting or servicing components on

this unit.

NOTE: If a unit has been carrying cargo which

contains a high level of sulphor or phosphorous

(e.g. garlic, salted fish etc.), it is recommended

that clean evaporator coil after each trip.

Pretrip

Every

1,000

Hours

Annual/

Yearly Inspect/Service These Items

Electrical

• Perform a controller pretrip inspection (PTI) check.

• • • Visually check condenser fan and evaporator fan.

• • • Visually inspect electrical contacts for damage or loose connections.

• • • Visually inspect wire harnesses for damage or loose connections.

• • Download the data logger and check data for correct logging.

• Check operation of protection shutdown circuits.

Refrigeration

• • • Check refrigerant charge.

• • Check for proper discharge and suction pressures.

• Check filter drier/in-line filter for a restriction pressures.

Structural

• • • Visually inspect unit for damaged, loose or broken parts.

• • • Tighten unit, compressor and fan motor mounting bolts.

• • Clean entire unit including condenser and evaporator coils, and defrost drains.

Page 18 of 166

Service Guide

18

Page 19 of 166

19

Specifications

System Net Cooling Capacity— Full Cool

Evaporator Airflow Specifications

MAGNUM+ Model — Air Cooled

Condensing*

Return air to

evaporator coil

inlet

460/230V, 3 Phase, 60 Hz Power

Net Cooling Capacity Power

Consump

60 Hz

Capacity

B/hr

60 Hz

Capacity

kW

60 Hz Power

kW

21.1 C (70 F) 56,700 16.603 11.55

1.7 C (35 F) 40, 945 11.990 11.03

-17.8 C (0 F) 24,785 7.258 7.57

-29 C (-20 F) 17, 215 5,041 6.6

-35 C (-31 F) 14,000 4.104 6.03

*System net cooling capacity with a 38 C (100 F) ambient air

temperature and R-404A.

System Net Heating Capacity*

460/230V, 3 Phase, 60 Hz Power 380/190V, 3 Phase, 50 Hz Power

Heating Capacity Heating Capacity

Watts Kcal/hr BTU/hr Watts Kcal/hr BTU/hr

MAGNUM+ 5,250 4,515 17914 3,900 3,353 13,300

*System net heating capacity includes electric resistance rods and fan heat.

MAGNUM+

External Static

Pressure (water

column)

460/230V, 3 Phase, 60 Hz Power 380/190V, 3 Phase, 50 Hz Power

High Speed Low Speed High Speed Low Speed

m3/hr ft3/min m3/hr ft3/min m3/hr ft3/min m3/hr ft3/min

0 mm (0 in.) 6,560 3,860 3,170 1,865 5,480 3,225 2,710 1,595

10 mm (0.4 in.) 5,820 3,425 1,770 1,040 4,530 2,665 930 545

20 mm (0.8 in.) 5,000 2,940 — — 3,750 2,205 — —

30 mm (1.2 in.) 4,430 2,610 — — 2,930 1,725 — —

40 mm (1.6 in.) 3,520 2,070 — — 1,870 1,100 — —

Electrical System Specifications

Compressor Motor:

Type 460/380V, 60/50 Hz, 3 Phase

Kilowatts 4.48 kW @ 460V, 60 Hz

Horsepower 6.0 hp @ 460V, 60 Hz

RPM 3550 RPM @ 460V, 60 Hz

Locked Rotor Amps 70 amps @ 460V, 60 Hz

Condenser Fan Motor:

Type 460/380V, 60/50 Hz, 3 Phase

Page 20 of 166

Specifications

20

Kilowatts 0.55 kW @ 460V, 60 Hz

Horsepower 0.75 hp @ 460V, 60 Hz

Number: All Models 1

Motor:

RPM 1725 RPM @ 460V, 60 Hz

Full Load Amps 1.0 amps @ 460V, 60 Hz; 1.0 amps @ 380V, 50 Hz

Locked Rotor Amps 3.9 amps @ 460V, 60 Hz; 3.7 amps @ 380V, 50 Hz

Evaporator Fan Motors:

Type 460/380V, 60/50 Hz, 3 Phase

Kilowatts 0.75 kW @ 460V, 60 Hz

Horsepower 1.0 hp @ 460V, 60 Hz

Motor:

RPM (Each): High Speed 3450 RPM @ 460V, 60 Hz

Low Speed 1725 RPM @ 460V, 60 Hz

Full Load Amps (Each): High Speed 1.6 amps @ 460V, 60 Hz

Low Speed 0.8 amps @ 460V, 60 Hz

Locked Rotor Amps: High Speed 10.5 amps @ 460V, 60 Hz

Low Speed 9.0 amps @ 460V, 60 Hz

Electrical Resistance Heater Rods:

Type 460/380V, 60/50 Hz, 3 Phase

Number 6

Watts (Each) 680 Watts @ 460V, 60 Hz

Current Draw (Amps) 5 amps total @ 460V across each phase at heater contractor

Control Circuit Voltage:

29 Vac @ 60 Hz

Refrigeration System Specifications

Compressor:

Model No.: ZMD18KVE-TFD-277, Scroll

Refrigerant Charge:

MAGNUM+ 4.0 Kg (8.0 lb.) R-404A

Compressor Oil Capacity 1.77 liter (60 oz.)*

Compressor Oil Type: Polyol Ester Based Type (required), (refer to Tool Catalog)**

*When the compressor is removed from the unit, oil level should be noted or the oil removed from the compressor should be

measured so that the same amount of oil can be maintained in the replacement compressor.

**Do not use or add standard synthetic or mineral oils to the refrigeration system. If Ester based oil becomes contaminated

with moisture or with standard oils, dispose of properly — Do Not Use!

High Pressure Cutout Switch:

Cutout 3240 ± 48 kPa, 32.4 ± 0.5 bar, 470 ± 7 psig

Cutin 2586 ± 262 kPa, 25.9 ± 2.6 bar, 375 ± 38 psig

Low Pressure Cutout Switch:

Cutout -17 to -37 kPa, -0.17 to -0.37 bar, 5 to 11 in. Hg vacuum

Cutin 28 to 48 kPa, 0.28 to 0.48 bar, 4 to 7 psig

High Pressure Relief Valve:

Relief Temperature 99 C, 210 F

Electrical System Specifications

Page 21 of 166

Specifications

21

Vapor Injection Control:

Modulation Cool or Power Limit

Vapor injection valve is energized (open) continuously when

the compressor duty cycle (ON time) is 100 percent (Full

Cool). High compressor discharge temperature may cause

the vapor injection valve to energize (open) but only while

the Compressor Digital Control valve is not energized

(closed).

Compressor Discharge Temperature Control:

Vapor Injection Valve Energizes (Opens) 138 C (280 F)

Vapor Injection Valve De-energizes (Closes) 6 C (10.7 F) below energize temperature

(132 C [123 F])

Compressor Shutdown (Auto Reset) 148 C (298 F)

Vapor Injection Valve (Compressor):

Voltage 24 Vac

Current 0.85 amps

Cold Resistance 5.6 ohms

Compressor Digital Control Valve:

Voltage 24 Vac

Current Draw 0.85 amps

Normal R-404A System Operating Pressures (Scroll Compressor)

Container Temp. Operating

Mode

Ambient

Temp. Suction Pressure Discharge Pressure

21 C (70 F) Cool

27 to 38 C, 80

to 100 F

410 to 670 kPa, 4.10 to 6.70

bar, 59 to 97 psig

2140 to 2650 kPa, 21.40 to

26.50 bar, 310 to 385 psig

16 to 27 C, 60

to 80 F

400 to 600 kPa, 4.00 to 6.00

bar, 58 to 87 psig

1725 to 2140 kPa, 17.25 to

21.40 bar, 250 to 310 psig

2 C (35 F) Cool

27 to 38 C, 80

to 100 F

385 to 425 kPa, 3.85 to 4.25

bar, 56 to 62 psig

1860 to 2380 kPa, 18.60 to

23.80 bar, 270 to 345 psig

16 to 27 C, 60

to 80 F

345 to 385 kPa, 3.45 to 3.85

bar, 50 to 56 psig

1450 to 1860 kPa, 14.50 to

18.60 bar, 210 to 270 psig**

-18 C (0 F) Cool

27 to 38 C, 80

to 100 F

214 to 228 kPa, 2.14 to 2.28

bar, 31 to 33 psig

1515 to 2035 kPa, 15.15 to

20.35 bar, 220 to 295 psig**

16 to 27 C, 60

to 80 F

200 to 215 kPa, 2.00 to 2.15

bar, 29 to 31 psig

1100 to 1515 kPa, 11.00 to

15.15 bar, 160 to 220 psig**

-29 C (-20 F) Cool

27 to 38 C, 80

to 100 F

145 to 160 kPa, 1.45 to 1.60

bar, 21 to 23 psig

1450 to 1965 kPa, 14.50 to

19.65 bar, 210 to 285 psig**

16 to 27 C, 60

to 80 F

130 to 145 kPa, 1.30 to 1.45

bar, 19 to 21 psig

1035 to 1450 kPa, 10.35 to

14.50 bar, 150 to 210 psig**

Suction and discharge pressures vary too greatly during Modulation Cool to use for evaluating or diagnosing refrigeration

system performance. During the Modulation Cool mode, the suction pressure will vary between 100 and 450 kPa, 1.0 and 4.5

bar, 15 and 65 psig depending upon the percent (percent) cooling capacity.

**Discharge pressure is determined by condenser fan cycling.

Refrigeration System Specifications (Continued)

Page 22 of 166

Specifications

22

MP-4000 Controller Specifications

Temperature Controller:

Type

MP-4000 is a controller module for the Thermo King Magnum+

Unit. Additional requirements can be met by means of expansion

modules. The MP4000 is solely responsible for temperature

regulation of the reefer container, but other monitoring equipment

can be used in conjunction with the MP 4000 - such as a chart

recorder.

Setpoint Range -40.0 to +30.0 C (-31.0 to +86.0 F)

Digital Temperature Display -60.0 to +80.0 C (-76.0 to +176.0 F)

Controller Software (Original Equipment):

Version See controller identification decal

Defrost Initiation:

Evaporator Coil Sensor

• Manual Switch or Demand Defrost Initiation: Coil must be

below 18 C (65 F). Defrost cycle starts when technician or

controller requests defrost initiation.

• Timed Defrost Initiation: Coil must be below 4 C (41 F). Defrost

cycle starts 1 minute after the hour immediately following a

defrost timer request for defrost initiation. For example, if the

defrost timer requests a defrost cycle at 7:35, the defrost cycle

will start at 8:01. Datalogger will record a Defrost event for each

interval in which a Defrost cycle is pending or active (i.e. both the

8:00 and 9:00 data logs).

Demand Defrost

Demand defrost function initiates defrost when:

• Temperature difference between the return air sensor and

defrost (evaporator coil) sensor is too large for 90 minutes

• Temperature difference between the supply air sensors and

return air sensor is too large

Defrost Timer:

Chilled mode

Evaporator Coil Temperature must be below 5C (41 F) to activate

the defrost compressor hour timer.

There is an interval set for defrosting, however, the defrost timer is

built intelligent - it detects whether or not there is ice building up on

the coil. If there is no ice building up on the coil, it extends the

defrost interval, and if there is Ice building up earlier on the coil it

reduces the defrost interval. The maximum interval is 48 hours.

Frozen mode

Every 8 hours of compressor operation. Defrost interval increases 2

hours each timed defrost interval. Maximum time interval in Frozen

mode is 24 hours.

Reset to Base Time Defrost timer resets if the unit is off more than 12 hours, setpoint is

changed more than 5 C (9 F) or PTI pretrip test occurs.

Defrost Termination:

Defrost (Coil) Sensor

Chilled mode: Terminates defrost when coil sensor temperature

rises to 18 C (65 F).

Frozen mode: Terminates defrost when coil sensor temperature

rises to 18 C (65 F).

Termination Timer Terminates defrost after 90 minutes at 60 HZ operation if coil

sensor has not terminated defrost (120 minutes at 50 Hz operation)

Power Off Turning Unit On/Off switch Off terminates defrost

v

Page 24 of 166

Specifications

24

AMA313

Unit Dimensions:

A = Flange Width 2025.5 mm (79.74 in.)

B = Gasket Width 1935 mm (76.18 in.)

C = Unit Width 1894 mm (74.57 in.)

D = Flange Height 2235.2 mm (88.00 in.)

E = Gasket Height 2140 mm (84.25 in.)

F = Unit Height 2094 mm (82.44 in.)

G = Gasket Depth 72 mm (2.83 in.) from back of flange

H = Maximum Protrusion 37 mm (1.46 in.) from back of flange

I = MAGNUM+ 420.0 mm (16.54 in.) from back of flange

J = MANGUM+ Evaporator Access Door

Figure 1: Physical Specifications

Page 25 of 166

Unit Description, Features & Options

25

Unit Description, Features & Options

Introduction

This chapter will briefly describe the following

items:

• General Unit Description.

• Standard Component Descriptions.

• Optional Component Descriptions.

General Description

MAGNUM units are all-electric, single-piece,

refrigeration units with bottom air supply. The

unit is designed to cool and heat containers for

shipboard or overland transit. The unit mounts in

the front wall of the container. Fork lift pockets

are provided for installation and removal of the

unit.

The frame and bulkhead panels are constructed of

aluminum and are treated to resist corrosion. A

removable evaporator compartment door provides

service access. All components except the

evaporator coil and electric heaters can be

replaced from the front of the unit.

Each unit is equipped with an 18.3 m (60 ft.)

power cable for operation on 460-380V/3

Ph/60-50 Hz power. The unit power cable is

stored below the control box in the condenser

section.

Each unit is equipped with 460-380V/3 Ph/60-50

Hz electric motors. An automatic phase correction

system provides the proper electrical phase

sequence for condenser fan, evaporator fan and

compressor operation.

Figure 2: MAGNUM+ Unit

The MAGNUM+ container unit features the

following components. Each component will be

described briefly on the following pages.:

• Scroll Compressor

• Compressor Digital Control Valve

• Economizer Heat Exchange System

• Temperature Sensors

• Fresh Air Exchange System

• Receiver Tank Sight Glass

• Evaporator Fans

• Condenser Fan Control

• Suction/Discharge Pressure Sensor (Optional)

• Remote Monitoring Receptacle Option (4-pin)

(optional)

• Remote Monitoring Modem (RMM)

(Optional)

• USDA Cold Treatment Temperature

Recording (Optional)

• Advanced Fresh Air Management (AFAM) and

Advanced Fresh Air Management Plus

(AFAM+) (Optional)

BEN074

Page 26 of 166

Unit Description, Features & Options

26

Scroll Compressor

The scroll compressor features a digital port and

an intermediate suction port.

Digital Port

The digital port provides cooling capacity control.

The digital port is located at the top of the scroll

assembly on the compressor body. When

energized, the Digital Control valve disengages

the scroll set. This reduces pumping capacity to

zero.

Intermediate Suction Port

The intermediate suction port draws suction gas

from the economizer heat exchanger into the

scroll assembly of the compressor. The scroll

seals off the suction port. This prevents

economizer gas from leaking back to the main

suction port. It also prevents the economizer gas

pressure from influencing the cooling capacity of

the unit evaporator (main suction gas pressure).

Figure 3: Scroll Compressor

MP-4000 Controller

The MP-4000 is an advanced microprocessor

controller that has been specially developed for

the control and monitoring of refrigeration units.

See “Controller Description and Operating

Chapter” for more detailed information.

Compressor Digital Control

Valve

The MP-4000 controller pulses the Compressor

Digital Control solenoid valve between open and

closed positions. This provides precise cooling

capacity control. No pump down function or

warm gas bypass control is used in conjunction

with the Compressor Digital Control valve. See

the “General Theory of Operation Chapter” for

more detailed information.

Figure 5: Compressor Digital Control Solenoid

Valve

1. MP-4000 Controller

Figure 4: MP-4000 Controller

1

BEN074

AXA0428

Page 27 of 166

Unit Description, Features & Options

27

Economizer Heat Exchange

System

An economizer heat exchange system replaces the

conventional heat exchanger. The economizer

Heat Exchange system subcools the liquid

refrigerant before it reaches the evaporator

expansion valve. Subcooling liquid refrigerant

increases the cooling efficiency and capacity of

the evaporator. See the “General Theory of

Operation Chapter” for more detailed

information.

Figure 6: Economizer Heat Exchanger

Temperature Sensors

Each sensor element is connected to a cable and

packaged in a sealed stainless steel tube. The

temperature signal from the sensor is transmitted

through the cable. PT.1000 type temperature

sensors are used to sense temperatures for the:

• Supply Air

• Return Air

• Evaporator Coil

• Condenser Coil

• Ambient Air

The compressor sensor is of Thermistor type and

is located in the top cap of the compressor.

These sensors are field replaceable. Five sensor

receptacles are provided; three USDA and one

cargo temperature.

Fresh Air Exchange System

The fresh air exchange system removes harmful

gases from containers carrying sensitive

perishable commodities. The fresh air vent is

located above the control box. The fresh air vent

is adjustable to accommodate a variety of frozen

and chilled load operating conditions.

Fresh Air Exchange Recorder

(Optional)

The Fresh Air Exchange Recorder detects vent

disk movement. It automatically displays a value

on the Display.This value is also logged in the

datalogger. The entry records the time, date and

vent opening position. It mounts on the fresh air

vent door.

Figure 8: Fresh Air Exchange Recorder

AXA0427 1. Fresh Air Exchange Vent

Figure 7: Fresh Air Exchange Vent

1

BEN075

AJA1964

Page 28 of 166

Unit Description, Features & Options

28

Receiver Tank Sight Glass

The receiver tank contains a sight glass which has

three small balls that indicate the level of

refrigerant in the tank for checking the refrigerant

charge. A moisture indicator in the sight glass

changes color to indicate the level of moisture in

the system.

Evaporator Fans

MAGNUM models are equipped with either 2 or

3 evaporator fans. All models feature 2-speed

motors. The evaporator fans operate continuously

to circulate air inside the container. The

evaporator fans operate on:

• High and low speed for chilled cargo at

setpoints of -9.9 C (14.1 F) and above

• Low speed for frozen cargo at setpoints of

-10 C (14 F) and below

The evaporator fan low speed RPM is one-half the

high speed RPM.

The controller determines evaporator fan motor

speed based on the setpoint temperature and the

Economy mode setting.

NOTE: If Non-Optimised mode is on:

• Chill Loads: Evaporator fans operate on high

speed

• Frozen Loads: Evaporator fans operate on

low speed

NOTE: If optimised mode is on:

• Chill Loads: Evaporator fans operate on high

and low speed - depending on the need for

cooling.

• Frozen Loads: Evaporator fans operate on low

speed and stops when there is no need for

cooling.

Condenser Fan Control

The controller also uses a proportional-integral

derivative algorithm to control the condenser

temperature and ensure a constant liquid pressure

at the expansion valve. The condenser fan

operates continuously in high ambients. In low

ambient conditions, the controller cycles the

condenser fan on and off to maintain a minimum

condenser temperature. The controller maintains a

minimum 30 C (86 F) condenser temperature on

Chill loads and a minimum 20 C (68 F) condenser

temperature on Frozen loads.

1. Moisture Indicator:

Light Green = Dry

Yellow = Wet

2. Outer ring is color coded. Compare to

indicator.

Figure 9: Receiver Tank Sight Glass

AXA0371

Page 29 of 166

Unit Description, Features & Options

29

Unit Options

This unit is available with several options that are

listed in Figure 10. These options are specified

when placing the order. These options are briefly

described on the following pages.

Recording Thermometer (Optional)

The recording thermometer indicates and

permanently records the temperature of the air

returning to the evaporator section on a calibrated

chart.

Several models of temperature recorders are

available for mounting on the unit. Each

temperature recorder is designed to withstand

widely varying environments including low and

high ambient temperatures, salt water, humidity,

fungus, industrial pollutants, dynamic loading,

rain, sand and dust.

Remote Monitoring Modem (RMM)

(Optional)

A REFCON remote monitoring modem is

provided to permit remote monitoring via the

power cable. High speed transmission reads all

controller information. Data can also be retrieved

from the data logger via high speed transmission.

Suction and Discharge Pressure

Sensors (Optional)

Pressure sensors can be added to the unit to

display actual suction or discharge system

pressure. The display will show a reading and a

bar graph. Unit can be configured suction only,

discharge only, or suction and discharge.

Air Ventilation Logging (AVL -

Optional)

AVL is used for detecting and logging the fresh air

exchange position on the manual fresh air vent.

The opening angle of the fresh air vent is con- verted to an output signal from approximately 2-5

volts.

The opening is detected in steps of 5m3/h, from 0

to 125. When opening is greater than 125m3/h the

log will just state that the opening is greater than

125m3/h.

1. Recording Thermometer (Optional)

2. Air Ventilation Logging (AVL)

3. Water Pressure Switch (Optional)

4.

Remote Monitor Modem for Power Line

Communications (REFCON control modem

inside Control Box) (Optional)

5. USDA Sensor Receptacle (Access from Inside

Container) (Optional)

6. Suction/Discharge Pressure Transducer

(Optional)

Figure 10: Optional Components

BEN061

1

6

5

4 3

2

Page 30 of 166

Unit Description, Features & Options

30

USDA Cold Treatment Temperature

Recording (standard)

The MP-4000 controller includes provisions for

the use of three or four USDA sensors. These

sensors allow temperatures in various areas of the

load to be monitored and recorded for United

States Department of Agriculture use in

monitoring Cold Treatment shipments.

When USDA sensors are installed, the controller

will automatically detect each sensor and activate

data logging. However, the USDA Type screen in

the Configuration menu must be set to the correct

sensor setting and each USDA sensor must be

calibrated to comply with USDA temperature

recording requirements.

Figure 11: Water-Cooled Condenser/Receiver Tank

Water-Cooled Condenser/Receiver

Tank (Optional)

A water-cooled condenser/receiver provides the

unit with above and below deck operating

capabilities. Condenser fan control is provided in

software or by a Condenser Fan Selection switch

or a Water Pressure switch. Starting april 2005 we

have added a shutoff valve on the outlet tube of

the water-cooled condenser.

Condenser fan switch is a software key. This

switch is provided on the control box with the

water-cooled condenser option. Place the

Condenser Fan On/Off switch in the Water

position for water-cooled condenser operation.

Water Pressure Switch (Optional)

When water pressure greater than 117 ± 21 kPa,

1.17 ± 0.21 bar, (17 ±3 psig) is provided to the

condenser-receiver tank, the water pressure switch

closes. This causes the controller to stop

condenser fan operation. When the water pressure

decreases below 35 ± 21 kPa, 0.35 ± 0.21 bar, (5 ±

3 psig), the switch opens, causing the controller to

place the unit on air-cooled condenser fan

operation.

Water-cooled condenser requires a water flow of

19 to 38 l/min. (5 to 10 gal./min.).

Advanced Fresh Air Management

(AFAM) System (Optional)

An advanced microprocessor controlled fresh air

management system provides programmable

control of air exchange rate, programmable

delayed vent opening, automatic closure of air

exchange vent during low ambient conditions, and

data logging of air exchange rate and vent opening

delay interval.

The AFAM system includes a door control

module, vent door and vent grille. The MP-4000

controller sends a communication signal to the

door control module to position vent door to

desired position. The controller can also be set to

delay opening of fresh air vent for up to 72 hours

(in 1 hour increments). This allows faster product

temperature pull-down.

AFAM Operation

The system is pre-calibrated for air exchange rates

of 0 to 280 m3/hr. (0 to 165 ft3/min.). The actual

door position is based on the air exchange setting

and the power supply frequency.

Page 38 of 166

Unit Description, Features & Options

38

Page 39 of 166

39

Controller Description

Controller Description

The MP-4000 is an advanced microprocessor

controller. It has been specially developed for the

control and monitoring of refrigeration units. The

controller contains the following basic features:

Temperature/Message Status Display:

• Temperature area. Displays Return air sensor,

Supply air sensor, and Setpoint

• Message area. Displays Alarms, Message and

Controller menu

Keypad:

• F1 – F4 Function keys navigate within the

Status Display

• 2 Status LED indicators

• Special Function keys. ON/OFF, PTI, Defrost

Controller Back-up Battery

Every Controller has a Back-up Battery. This will

allow the controller to be energized if the unit is

not connected to shore power. The technician can

change settings in the controller - Setpoint, etc.

Press the ON/OFF key, the controller will

energize and stay energized for 25 sec, by

pressing any of the Menu keys the 25 sec timer

will reset to 20 sec.

Controller Input and Output Signals

The MP-4000 microprocessor controls all unit

functions to maintain the cargo at the proper

temperature. The controller also monitors and

records system faults and performs pretrip.

The MP-4000 controller uses advanced solid-state

integrated circuits to monitor and control unit

functions. The controller monitors inputs from:

• Return Air Sensor

• Supply Air Sensor

• Evaporator Coil Sensor

• Condenser Coil Sensor

• Ambient Sensor

• Humidity Sensor

• USDA (Spare) Sensors 1, 2 and 3

• Compressor Discharge Line Temperature

Sensor

• High Pressure Cutout Switch/Discharge

Pressure Sensor

• Low Pressure Cutout Switch/Suction Pressure

Sensor

• Phase measuring circuits

• Current measuring circuits

• Voltage measuring circuits

Output signals from the controller automatically

regulate all unit functions including:

• Compressor operation

• Condenser fan operation

• Evaporator fan motor operation

• Compressor digital valve

• Vapor injection valve

• Dehumidify valve

• Electric heaters

• Phase selection

Page 42 of 166

Controller Description

42

When the set Defrost termination temperature is

reached, the unit will return to the operation mode

depending on the setpoint.

PTI

PTI is a pretrip inspection and is used to diagnose

the condition of the unit. There are a possibility to

chose between several type of PTI ́s depending on

the test needed to secure the functionality of the

unit.

Function Keys

The function keys are the F1 - F4 keys located

below the display. They allow the operator to

move quickly to a specific area of the information

or into the controller menu.

Function keys will change based on what menu is

active in the display

Figure 21: Function Keys

• F1 ALARM key: Press to view an

explaination for the current alarms present.

• F2 C/F key: Press to view alternate

temperature scale Celsius or Fahrenheit in

display.

• F3 SETPOINT key: Press to enter Setpoint

menu. Press F2 Up or F3 Down keys to

increase or decrease the Setpoint. Press and

Hold F4 until you are returned back to the

main menu.

• F4 MENU key: Press to view the extended

Menu for the MP4000

Indicator LEDs

Two status indicator LEDs are located just under

the F1-F4 function keys

Green Led Flashing Temperature

approaching in-range

Solid Temperature

In-Range

BEN 056

Red Led Flashing Alarm present and has

not been

acknowledged

Solid Alarm present and has

been acknowledged

Page 43 of 166

Controller Description

43

Three Special Function Keys

The Special Function keys are located around the

TK Logo. These special function key allow the

operator to move quickly to perform a specific

function

Figure 22: Special Function Keys

PTI Pre-Trip Inspecion

* Defrost

ON

OFF

Unit On/OFF Control

Page 56 of 166

Main Menu

54

4. Press the F4 ENTER KEY to start the Function

test. Display shows functional test currently

being performed. Function test ends

automatically. Unit automatically returns to

normal operation.

See Figure 32 for the full Function Test

Procedure. Any alarm codes recorded during the

test can be viewed through the controller’s Alarm

List menu at the end of the test.

Manual Function Test

The Manual Function Test menu allows

technicians to perform specific diagnostic tests on

individual components or turn several

components on at the same time to perform a

system test.

Figure 31: Manual Function Test

NOTE: THE UNIT STOPS when the Manual

Function Test menu is entered. A technician can

then select the control circuit or component to be

checked/tested from the items shown in the

menu.

Complete the following steps to enter the Manual

Function Test menu.

With the unit turned on, allow Unit to start and

stabilise and the Display showing the unit status

display (setpoint):

1. Press the F4 MENU key. Press the F3 key to

scroll down to the Commands Menu.

2. Press the F4 ENTER KEY to access the

Commands menu.

3. Press the F2 OR F3 UP/DOWN key to scroll to

[MANUAL FUNCTION TEST].

SETPOINT

Commands Menu

- PTI

- Brief PTI

- Functions Test

- Manual Functions Test

- Defrost

- Trip Start

DATA

COMMAND

ALARM LIST

WARNING LIST

CONFIGURATION

DATALOGGER

STATES

NOTE: All screens are NOT

present on all units. The

screens that display on the

controller are determined by

the Controller Software

settings and the options

installed on the unit.

Page 57 of 166

Main Menu

55

4. Press the F4 ENTER KEY to enter the Manual

Function Test: [CONDENSER OFF] appears

in the Display.

To test a unit component:

1. Press the F2 OR F3 UP/DOWN key to scroll to

desired component test:

• [PHASE DIRECTION]

• [HEATER]

• [COMPRESSOR]

• [EVAPORATOR FAN HIGH]

• [EVAPORATOR FAN LOW]

• [CONDENSER FAN]

• [ECONOMIZER VALVE]

• [DIGITAL VALVE]

2. Press the F4 ENTER KEY to start the

component test. Display will change the

component state from off to on.

3. Verify component performance: Display will

show expected current and actual current on

phase 1, 2 and 3.

4. Press the F4 ENTER KEY again to stop test.

Display will change component state from on

to off.

System Test (test multiple components at the

same time):

1. Press the F2 OR F3 UP/DOWN key to scroll to

the first component.

2. Press the F4 ENTER KEY to turn the component

on.

3. Press the F3 key to scroll to select next

component. Press theF4 ENTER KEY to turn

component on.

4. Repeat step 3 until all required components

are on. For example, to operate unit in Full

Cool mode, start the following components:

• Condenser Fan

• Compressor

• Capacity 100 percent

• Evaporator High or Low

5. Observe current draw and system performance

to verify component(s) performance.

6. Press the F4 ENTER KEY again to turn off

components individually. Or press the F1 key

to exit Manual Function Test menu and turn

all components off.

Press the F1 key to exit the Manual Function Test

submenu.

Page 58 of 166

Main Menu

56

Figure 32: PTI, Brief PTI, Function Tests

Display* Description Possible

Alarms

Duration

(Time)

PTI Brief

PTI

Function

Test

PTI START

Activated

0.1A 0.0A 0.1A

Event Log for PTI begins.

Awaits phase selection, and

surveillance to start up.

All alarms are turned off. Alarm

list is cleared.

All relays are turned off and air

vent are closed.

18 1 to 100

seconds

X X X

SENSOR TEST

Activated

0.1A 0.0A 0.1A

Testing sensor interface, All

sensors must have values within

their measuring range.

00, 01, 02,

03, 04, 05,

32, 33, 34,

35, 60, 97,

98, 120,

121, 123

Instant X X X

EVAP FAN LOW

SPEED TEST

SUP RET EVA

5.1C 5.0C 5.1C

1.1A 1.0A 1.1A

With evaporator fan on low

speed, amp draw is measured

and compared to the expected

amp draw, in respect to voltage

and frequency:

• MAGNUM+ / MAGNUM+

40’SL:

1.0 Amps approx. at 50 Hz,

1.0 Amps approx. at 60 Hz

• MAGNUM+ 20’SL:

1.5 Amps approx. at 50 Hz,

1.5 Amps approx. at 60 Hz

Amperes are recorded in the PTI

log.

14, 15 5 seconds X X X

EVAP FAN HIGH

SPEED TEST

SUP RET EVA

5.1C 5.0C 5.1C

2.4A 2.3A 2.4A

With evaporator fan on high

speed, amp draw is measured

and compared to the expected

amp draw, in respect to voltage

and frequency. If the minimum

phase amp draw is less than

70% of the maximal amp draw

both alarm is set.

• MAGNUM / MAGNUM 40’SL:

2.1 Amps approx. at 50 Hz,

2.5 Amps approx. at 60 Hz

• MAGNUM 20’SL:

2.7 Amps approx. at 50 Hz,

3.2 Amps approx. at 60 Hz

Amperes are recorded in PTI log.

12, 13 5 seconds X X X

Page 59 of 166

Main Menu

57

COND FAN TEST

SUP RET EVA

5.2C 5.0C 5.1C

1.3A 1.2A 1.3A

With condenser fan on, amp

draw is measured and compared

to the expected amp draw, in

respect to voltage and frequency.

If the phase amp draw differs

more than 1,0 Amp both alarm is

set.

• MAGNUM+ Expected Power Con- sumption:

1.2 Amps approx. at 50 Hz,

1.5 Amps approx. at 60 Hz

Amperes are recorded in PTI log.

16, 17 5 seconds X X X

PROBE TEST

SUP RET EVA

5.1C 5.0C 5.1C

2.4A 2.3A 2.4A

Evaporator fans operate on high

speed for maximum 3 minutes.

Then probe test runs until

temperature difference between

sensors stops increasing.

Maximum temperature

difference allowed:

• Return/Evaporator: 1.5C (34.7F);

return air sensor temperature must

be 0.5C (32.9F) above evaporator

sensor temperature.

• Return/Supply: 0.8C (33.0F);

return air sensor temperature must

be 0.5C (32.9F) above supply air

temperature.

• LH Supply/RH Supply (if

equipped): 0.5C (32.9F).

115, 116,

117

1 minute

minimum

to

13 minutes

maximum

X X X

REVERSE PHASE

TEST

SUP RET EVA

1.3C 1.0C 1.3C

1.3A 1.2A 1.3A

With condenser fan on, reverse

phase selector relay is

energized. Condenser fan and

compressor reverse current is

measured.

58 30 seconds X X X

HEATER TEST

SUP RET EVA

1.3C 1.0C 1.3C

5.2A 5.1A 5.2A

Electric heaters are turned on.

Amp draw is measured to the

expected amp draw, in respect

to voltage and frequency

• 4.4 Amps approx. at 400V;

• 5.1 Amps approx. at 460V.

Heater amperes are recorded in

PTI log.

10, 11 5 seconds X X X

DEFROST TEST

SUP RET EVA

5.0C 12.0C 15.0C

5.2A 5.1A 5.2A

If evaporator temperature is

below +10C, heater remains on

until evaporator temperature is

above +18C.

Defrosting until Eva. > 18C/64F

20 0-90

Minutes at

voltage

above 440V

0-120

Minutes at

voltage

below 440V

X X -

Display* Description Possible

Alarms

Duration

(Time)

PTI Brief

PTI

Function

Test

Page 60 of 166

Main Menu

58

TEMPERATURE

STABILISATION With evaporator fan on high

speed awaiting the supply, return

and evaporator temperatures to

stabilize.

Delta SUP-RET and Delta

RET-EVA must be stable, within

7 seconds.

Awaiting temperature stability

None 20 to 180

seconds

X X -

PRE HEAT TEST

SUP RET EVA

5.1C 5.0C 5.1C

2.3A 2.1A 2.3A

Test is skipped if return air tem- perature is at 5degC or above.

With electric heaters turned on

and evaporator fan on high

speed, the test will end when

return air temperature is at

5degC or above.

Heating until 5C/41F

None Instant to 2

hours

X X -

PRE COOL TEST

SUP RET EVA

5.1C 5.0C 5.1C

2.3A 2.1A 2.3A

If the return air temperature is

below 15C (68F) the test is

skipped. Unit operates in cool

until the return sensor is less

then +15C (59F) or 1 hour

Cooling until 15C/59F

None Instant to 2

hours

X X -

VENTILATING If heater or compressor has been

running in the preceding test,

the unit is ventilated with

evaporator fan on high speed.

Ventilating

None 60 seconds X X X

COMPRESSOR TEST

AMB CON EVA

8.0C 15.0C 5.0C

9.1A 9.0A 9.1A

Compressor loaded, and con- denser fan activated for 10 sec.

Followed by compressor run

alone for 7 sec before the amp

draw is measured and compared

to the expected amp draw, in

respect to voltage and frequency.

Amperes are recorded in the

PTI log.

Evaluating power consumption

6, 7 18 seconds X X X

Display* Description Possible

Alarms

Duration

(Time)

PTI Brief

PTI

Function

Test

Page 61 of 166

Main Menu

59

COMPRESSOR

DIGITAL TEST

AMB CON EVA

8.0C 25.0C 2.0C

9.1A 9.0A 9.1A

Compressor running loaded,

evaporator fan at high speed,

and condenser fan maintaining

30-35degC for 15 sec.

Next the compressor is unloaded

and running for 10 sec

Amp draw difference is mea- sured and expected to be at least

0,9 Amp (Con > 35C) or 1,5 Amp

(Con < 35C).

119 25 to 35

seconds

X

X

X

COMPRESSOR

ECONOMIZER TEST

AMB CON EVA

8.0C 45.0C 1.0C

9.1A 9.0A 9.1A

With compressor on (loaded),

condenser and evaporator fans

at high speed are turned on for

30 seconds. If condenser fan

temperature is below 30C (86F)

then the test is aborted.

Vapor injection valve is turned

on. Amp draw difference is

measured and verified to be

minimum 0.4 amps.

Evaluating Power Consumption

Increase.

26 Max 90

seconds

X

X

X

Display* Description Possible

Alarms

Duration

(Time)

PTI Brief

PTI

Function

Test

Page 62 of 166

Main Menu

60

HIGH PRESSURE

CUTOUT TEST Running with compressor fully

loaded and with evaporator fan

at high speed, awaiting high

pressure cut out. The test is

ended if the condenser coil

probe reads temperature above

70oC and the HPCO does not

occurs. The time observing is

depending on the startup tem- perature and will be increased as

long as the condenser tempera- ture is increasing.

After the HPCO the compressor

signal is removed and the

condenser fan is activated to

lower the pressure in the

condenser. When the tempera- ture gets below 40oC the

compressor is also activated.

The test will then look for when

the HPCO gets back to normal in

maximal 60 seconds.

Awaiting HPCO - Compressor

stop

53, 54 Max. 200

seconds

X X -

CAPACITY TEST With compressor fully loaded con- denser fan on and evaporator

fan at high speed running for the

time period. At the end of the

test is the cooling capability

evaluated.

Evaluating cooling capability

22 180

seconds for

40’ and 240

seconds for

20’ unit.

- X -

APPROACHING 0

TEST Probe readings and time are

recorded in the pti log when

started. When supply air temper- ature is at 0 degC / 32F the test

is ended. If the test is not ended

within the time limit the alarm is

set.

Approaching 0C/32F

23 Max. 2

hours

X - -

Display* Description Possible

Alarms

Duration

(Time)

PTI Brief

PTI

Function

Test

Page 63 of 166

Main Menu

61

MAINTAINING 0C TEST With the unit running chilled –

Non-Optimised, maintaining 0 degC /

32F.

After 30 minutes the probe readings

and time are recorded in

the pti log.

Maintaining 0C/32F

None 30 Minutes X X -

DEFROST TEST Test is skipped and Fail if either of

alarm 4,5,130 is present.

Test is skipped if evaporator temper- ature is at 5degC or above.

With electric heaters turned on, the

test will pass when

evaporator temperature reach

18degC or above.

Defrosting until Eva. > 18C/64F

4, 5, 20,

130

0 to 90 min- utes at volt- age above

440V

0 to 120

minutes at

voltages

below 440V.

X X X

PULLDOWN TO -18 C

TEST With the unit running frozen,

approaching -18 degC / 0F.

Probe readings and time are

recorded in the pti log when

started and when ended. When

return air temperature is at -18

degC / 0F the test is ended. If the

test is not ended within the time

limit the alarm is set.

Approaching -18C/0F

22 Max. 3

hours

X X -

PTI END “PTI End” are recorded in PTI log

and a Trip Start is

automatically activated.

All alarms are cleared and must

be acknowledged by the user.

Unit awaits an ACCEPT of the

just ended test before returning

to normal operation.

PASSED - PASSED - PASSED

FAILED - FAILED - FAILED

26 Max 90

seconds

X X X

Display* Description Possible

Alarms

Duration

(Time)

PTI Brief

PTI

Function

Test

Display* LED

Display

Description Possible

Alarms

Duration

(Time)

Page 64 of 166

Main Menu

62

RUNNING PTI

0°C / 32°F

00:00:00

0.0C 10.0C 10.0C

Supply

temp.

Unit operates in normal mode with 0C

(32F) setpoint for 30 minutes after

previous test is completed. At the end of

30 minutes, “Chill End” temperatures are

recorded in PTI log. Sensor values for

supply, return and evaporator sensors are

recorded in the event log.

None 120 minutes

maximum

RUNNING PTI

DEFROST

00:00:00

-18.0C 10.0C 10.0C

Return

temp.

Unit operates in normal mode with -18C

(0F) setpoint and defrost activated. Defrost

terminates when evaporator temperature

increases to 18C (65F).

20 30 minutes

RUNNING PTI

-18°C / 0°F

00:00:00

-18.0C 10.0C 10.0C

Return

temp.

Unit operates in normal mode with -18C

(0F) setpoint. When return air temperature

decreases to setpoint, Frozen Arrival”

temperatures are recorded in PTI log.

“PTI End” are recorded in PTI log and a

Trip Start is automatically activated.

22, 60 90 minutes

maximum

PTI PASS – PRESS

KEY

Return

temp.

Unit will remain OFF until any key is

pressed.

If alarms occurred during PTI, Display

shows “PTI FAIL – PRESS KEY”.

None 180 minutes

maximum

* Readings may vary depending on voltage and temperature

Page 68 of 166

Main Menu

66

Warning List Menu

Alarm List Menu

Warning

Code Action

1 Power Error, Check 20A Fuses

2 High Pressure Cutout, Check Water

Cooling

3 Probe Test, Please Wait

7 High Pressure Cutout, Check

Condenser Probe

9 High Pressure Cutout, Check

Condenser Fan

11 Scroll Compressor, High Temperature

12 Scroll Compressor, Low Pressure

21 Total Current Too High

22 Total Current Too Low

23 Supply Air Temperature Too High

24 Supply Air Temperature Too Low

25 Return Air Temperature Too High

26 Evaporator Coil Temperature Too High

27 Evaporator Coil Temperature Too Low

Alarm

Code Action

00 Supply Air Sensor Open Circuit

01 Check Supply Air Sensor Short Circuit

02 Check Return Air Sensor Open Circuit

03 Check Return Air Sensor Short Circuit

04 Check Evaporator Coil Open Circuit

05 Check Evaporator Coil Sensor Short

Circuit

06 Check Compressor Current Too High

07 Check Compressor Current Too Low

10 Check Heater Current Too High

11 Check Heater Current Too Low

12 Check Evaporator Fan High Speed

Current Too High

13 Check Evaporator Fan High Speed

Current Too Low

14 Check Evaporator Fan Low Speed

Current Too High

15 Check Evaporator Fan Low Speed

Current Too Low

16 Check Condenser Fan Current Too High

17 Check Condenser Fan Current Too Low

18 Log Power Supply Phase Error

19 Check Temperature Too Far from

Setpoint

20 Check Defrost Time Too Long

22 Check Capacity Test 1 Error

26 Vapor Injection Valve Error

31 Low Pressure Cutout Error

32 Check Condenser Air Sensor Open

Circuit

33 Check Condenser Air Sensor Short

Circuit

34 Check Ambient Air Sensor Open Circuit

35 Check Ambient Air Sensor Short Circuit

43 Check Return Air Temperature

51 Check for Low Voltage

52 Check Probe Error

53 Check High Pressure Cutout Switch Off

Error

54 Check High Pressure Cutout Switch On

Error

56 Shutdown Compressor Temperature

Too High

58 Check Phase Sensor Error

59 Check Delta Current Error

60 Check Humidity Sensor Error

98 Log Compressor Sensor Short Circuit

119 Digital Valve Error

120 Check Suction Pressure Sensor

121 Check Discharge Pressure Sensor

122 Re-calibrate O2 Sensor

123 Check Datalogger Battery

124 Check Power Module Sensor

128 Check Supply Air Temperature Probe

129 Check Return Air Temperature Probe

130 Check Evaporator Coil Temperature

Probe

131 Ambient Condition Temperature Probe

Error

Alarm

Code Action

Page 110 of 166

Refrigeration Maintenance

108

Perform an Oil Acid Test

Perform an oil acid test (refer to Tool Catalog for

oil test kit) whenever a unit has a substantial

refrigerant loss, a noisy compressor or dark/dirty

oil.

Isolate the Compressor

The discharge suction and digital ball service

valves isolate the compressor from the high and

low sides of the refrigeration system.compressor

isolation is needed for system diagnosis, service

and repair.

NOTE: The valves are a permanently assembled

unit and must be replaced in total if defective.

The only maintenance possible on the discharge

or suction service valve is to periodically tighten

the packing nut or to replace the packing.

• Back Seated: Normal operation position.

• Open to Service Port: Position for servicing.

• Front Seated: To check or remove compressor.

Working with a Gauge Manifold

Using a New Gauge Manifold Set

A new gauge manifold set and gauge hoses (refer

to Tool Catalog) should be dedicated for use with

only R-404refrigerant.

Gauge Manifold Valve Positions

The gauges indicate low and high side pressures.

Operate one or both hand valves to perform the

different service operations.

WARNING: Do not start unit with

discharge valve in Front Seated position.

1. Full Counterclockwise

Figure 61: Service Valve Back Seated

1. 1/2 Turn in

Figure 62: Service Valve Open to Port

AXA0176

AXA0177

1. Full Clockwise

Figure 63: Service Valve Front Seated

1. Quick Disconnect Access Valve

2. Discharge Service Valve (DSV)

3. Suction Service Valve (SSV)

Figure 64: Balancing the Pressure

AXA0178

AXA0241