Contents
List of Figures
Fig.1 Switchyard 3
Fig.2 Transformer 5
Fig.3 Relays on Panel 9
Fig.4 Buchholz’s relay 11
Fig.5 ABCB Breaker 15
Fig.6 SF6 Breaker 16
Fig.7 Lightening Arrestor 18
Fig.8 Basic Power Line Carrier Terminal 20
Fig.9 Power Line Carrier Communication 21
Fig.10 Coupling Capacitor and Drain Coil Combination 23
Fig.11 Control panels in control room 30
INTRODUCTION
The Rajasthan state as it exist today is the result of integration of 19 former Princely States and was formed in April, 1949.At the formation of Rajasthan in April, 1949 there were 15 state owned Power Houses with a total installed capacity of 13271 KW and an aggregate maximum demand on the stations of approximately 7483 KW.
The Rajasthan State Electricity Board was constituted with effect from July 1, 1957 by Government of Rajasthan Notification No. F.11/OSD (PWD)/57 dated the 28th June, 1957 under the electricity (Supply) Act, 1948
Government of Rajasthan on July 19, 2000 issued a gazette notification unbuilding Rajasthan State Electricity Board into Rajasthan Rajya Vidyut Utpadan Nigam Ltd. which will be generation company; Rajasthan Rajya Vidut Prasarn Nigam Ltd. which will be the transmission Company and three regional distribution companies namely Jaipur Vidyut Vitaran Nigam Ltd., Ajmer Vidyut Vitaran Nigam Ltd. and Jodhpur Vidyut Vitaran Nigam Ltd.
The Generation Company will own and operate the thermal power stations at Kota and Suratghar, Gas based power station at Ramghar, Hydel power station at Mahi and mini Hydel stations in the State.
The Transmission Company will own and operate all the 400kV, 220 kV, 132kV and 66kV electricity lines and system in State and will also be responsible for procuring power.
The three Distribution Companies will operate and maintain the electricity system below 66kV in the state and their respective areas.
1.1 DETAILS OF ORGANISATION SETUP: -
GRID: Grid is a technical word used for the interconnection of power received from more than one place. It is a network of main power line for transmission of electricity.
Duties: Following are the duties of R. R. V. P. N. L.:
SWITCH YARD
So including above the yard consists of following equipment
.
Fig 1. Switch yard
TRANSFORMER
INTRODUCTION: -
It is a mutual link in power system, which makes possible to low voltage to be step up to the extra high voltage for long distance transmission and then transferred to voltage for utilization at proper load centre.
In brief, a transformer is a device that:
A high voltage is desirable for transmitting large powers in order to decrease the I2r losses and reduce the amount of conductor material.
A very much lower voltage, on the other hand, is required for distribution, for various reasons connected with safety and convenience. The transformers make this easily and economically.
Transformers are of three types
Power transformers are installed with various fittings and devices, which are necessary for their proper functioning. Some of the fittings, which are normally provided depending upon the size of transformer, are as –
`Fig 2. Transformer
PROTECTION
3.1 INTRODUCTION:-
For 400kv GSS protection for transformer, busbar and transmission line has been duplicated for fast and reliable protection. For this two sets of protection systems are used which will isolate the equipment as quickly as possible even in case of defective tripping. Thus, a local back up protection has been introduced in case there occurs a mechanical or electrical failure during isolating equipment.
Transmission line protection
There are 2 methods which uses-
System ‘A’ (first main protection)
400kv line is an extra high voltage line so phase comparison carrier current protection is used. It has advantage that it operate instantaneously and it does not need potential transformer and not sensitive phase power swings. Thus, fuse failure not occurs.
System ‘B’ (second main protection)
A twelve element scheme is used with the carrier equipment with distance protection as a unit scheme and fault occurring in the end zone of protected line that wound normally cleared in a relatively low zone 2 not greatly in excess of zone 1.
3.2 RELAYS: -
INTRODUCTION: -
In order to generate the electric power and transmit it to consumer millions of rupees must be spent on power system equipment. These equipment are to work under specified normal conditions. However, a short circuit may occur due to failure of insulation called by:
3.3 VARIOUS FAULTS:-
Phase to phase 20-25%
Single phase short circuit 50-60%
double phase S.S. 3-5% 20-25%
Three phase short circuit 3-5%
Phase to Phase and Phase to guard 10-15%
Fault may be defined as the rise of current in the several times to normal current, resulting the high temperature rise which can damage the equipment.
It reduces the voltage immediately and considerably.
Basic equipment or Requirement of Protective Relays.
Basic Requirement of protective relays are as follows:
Speed
Protective relaying should do’s connect a faulty element as quickly as possible.
Selectivity
The ability of the protective relay to determine the point of which have the fault occurs and select the nearest circuit breaker tripping of which will lead the clearing of fault with min-or so damage to the system.
Sensitivity
It is the capacity of the relaying to operate relay under the actual condition that produces the last operating condition tendency.
Depending upon the method of element connected primary relay (series element connect directly on the circuit of protective element) and secondary relay 9sensing element connected through a current and voltage transformer.
3.4 Types of Relays
These are called normally opened, normally closed in GSS control room there is panel in which the relays are set and there are many types of relays.
Over voltage relay – This protection is required to avoid damage of system in case line becomes open circuited at one end. These fault would trip the local circuit breaker thus block the local and remote ends. This relay is operated i.e., energized by CVT connected to lines.
Fig 3. Relays on panel
Fig 4. Buchholz’s relay
DETAILS OF TECHNICAL AND OTHER OBSERVATIONS
4.1 TRANSMISSION LINES
In this category the extra high voltage lines of 400kV, 220kV, 132kV and 66kV are considered/are used voltage from one grid sub-station to other through six various types conductors.
4.2 THE CONDUCTORS USED FOR
(i) For 400kV line : Taran Tulla and Marculla conductor.
(ii) For 220kV line : Zebra conductor is used composite of Aluminium strands and Steel wires.
(iii) For 132kV line : Panther conductor is used composite of Aluminium strands and Steel wires.
The material used in these conductors is generally Aluminium Conductor Steel Reinforced (ACSR). The conductors run over the towers cross arms of sufficient height with the consideration to keep safe clearance of sagged conductors from ground level and from the objects (trees, buildings etc.) either side also.
ISOLATOR
5.1 INTRODUCTION: -
When to carry out inspection or repair in the substation installation a disconnection switch is used called isolator. Its work is to disconnect the unit or section from all other line parts on installation in order to insure the complete safety of staff working. The isolator works at no load condition. They do not have any making or breaking capacity.
On fundamental basis the isolating switches can broadly divided into following categories: -
5.2 OPERATION: -
The operation of an isolator may be hand operated without using any supply or may be power operated which uses externally supplied energy switch which is in the form of electrical energy or energy stored in spring or counter weight.
In a horizontal break, center rotating double break isolator, 3 strokes are found. Poles are provided on each phase. The two strokes on side are fixed and center one is rotating. The center position can rotate about its vertical axis at an angle of 90. In closed position, the isolating stroke mounts on galvanized steel rolled frame. The three poles corresponding to 3 phases are connected by means of steel shaft.
Isolators are of two types -
CIRCUIT BREAKER
6.1 INTRODUCTION:-
The circuit breaker is one of the important equipment in power system. It protects the system by isolating the faulty section while the healthy one is keep on working. Every system is susceptible to fault or damages while can be caused due to overloading, short-circuiting, earth fault etc. thus to protect the system and isolate the faulty section C.B. are required. Apart from breaking and making contacts, a C.B. should be capable of doing.
6.2 PRINCIPLE:-
During making and breaking an arc is struck between the separating contacts which play an important role in interruption process as it provides for the gradual transition from current carrying to voltage withstanding states of contacts, but it is dangerous on account of energy generated in the form of heat which may results in explosive forces. This should be extinguished shortly.
Method of interruption are current:-
In high resistance interruption arc is controlled by subsequently increasing resistance is brought into circuit and are cooled simultaneously so that current is quickly reduced to a value insufficient to maintain the arc.
In current, zero interruption the arc resistance is kept low until the current becomes zero, where the arc extinguishes itself and is prevented from restricting in spite of high restricting voltage.
Fig 5. ABCB breaker
Fig 6.SF6 Circuit breaker
Lighting Arrestor
7.1 INTRODUCTION:-
Every instrument must be protected from the damage of lighting stroke. The three protection sin a substation is essential:
Effective protection of equipment against direct strokes requires a shield to prevent lighting from striking the electrical conductor together with adequate drainage facilities over insulated structure.
Lighting Arrestors: - Lighting arrestor is a device, which protects the overhead lines and other electrical apparatus viz., transformer from overhead voltages and lighting. When the positively charged cloud produce negative charge on the overhead line by electrostatic induction then the negative charge is however presented right under the cloud and portion of the line away from the cloud becomes positively charged. This charge on the line does not flow.
The positive charge on the far and flows to the earth through insulators, thus leaving the negative charge on the line directly under the cloud. Now assume due to the direct discharge occurring between this clouds and passing by negative charge cloud the charge in the cloud becomes neutralized, then the charge on the line is no more bound charge and is free to travel on the both directions in the form of waves. These traveling waves will be of light magnitude and have steep wave front, which can damage the unprotected equipment connected to the line. These waves are passed to the earth through the lighting arrestors.
It consist of a isolator in series and connected in such a way that long isolator is in upward and short isolator is in downward so that initially large potential up to earth is decreased to zero.
An ideal arrestor must therefore have the following properties:
Fig 7. Lightening Arrestor
POWER LINE CARRIER COMMUNICATION (PLCC)
8.1 Introduction
Power line communication or power line carrier (PLC), also known as Power line Digital Subscriber Line (PDSL), mains communication, power line telecom (PLT), or power line networking (PLN), is a system for carrying data on a conductor also used for electric power transmission. Broadband over Power Lines (BPL) uses PLC by sending and receiving information bearing signals over power lines.
Electrical power is transmitted over high voltage transmission lines, distributed over medium voltage, and used inside buildings at lower voltages. Powerline communications can be applied at each stage. Most PLC technologies limit themselves to one set of wires (for example, premises wiring), but some can cross between two levels (for example, both the distribution network and premises wiring). Typically the transformer prevents propagating the signal so multiple PLC technologies are bridged to form very large networks.
All power line communications systems operate by impressing a modulated carrier signal on the wiring system. Different types of powerline communications use different frequency bands, depending on the signal transmission characteristics of the power wiring used. Since the power wiring system was originally intended for transmission of AC power, in conventional use, the power wire circuits have only a limited ability to carry higher frequencies. The propagation problem is a limiting factor for each type of power line communications. A new discovery called E-Line that allows a single power conductor on an overhead power line to operate as a waveguide to provide low attenuation propagation of RF through microwave energy lines while providing information rate of multiple Gbps is an exception to this limitation.
Data rates over a power line communication system vary widely. Low-frequency (about 100-200 kHz) carriers impressed on high-voltage transmission lines may carry one or two analog voice circuits, or telemetry and control circuits with an equivalent data rate of a few hundred bits per second; however, these circuits may be many miles long. Higher data rates generally imply shorter ranges; a local area network operating at millions of bits per second may only cover one floor of an office building, but eliminates installation of dedicated network cabling.
8.3 MAJOR SYSTEM COMPONENTS EQUIPMENT
The major components of a PLC channel are shown in Figure. The problem associated with the PLC channel is the requirement to put the carrier signal onto the high voltage line without damaging the carrier equipment. Once the signal is on the power line it must be directed in the proper direction in order for it to be received at the remote line terminal.
Fig 8. Basic Power Line Carrier Terminal
8.4 BASIC PRINCIPLE OF PLCC
In PLCC the higher mechanical strength and insulation level of high voltage power lines result in increased reliability of communication and lower attenuation over long distances.
Since telephone communication system cannot be directly connected to the high voltage lines, suitably designed coupling devices have therefore to be employed. These usually consist of high voltage capacitors or capacitor with potential devices used in conjunction with suitable line matching units (LMU’s) for matching the impedance of line to that of the coaxial cable connecting the unit to the PLC transmit-receive equipment.
Also the carrier currents used for communication have to be prevented from entering the power equipment used in G.S.S as this would result in high attenuation or even complete loss of communication signals when earthed at isolator.. Wave traps usually have one or more suitably designed capacitors connected in parallel with the choke coils so as to resonate at carrier frequencies and thus offers even high impedance to the flow of RF currents.
Fig 9. Power Line Carrier Communication
8.5 LINE TRAPS or WAVE TRAPS:-
The carrier energy on the transmission line must be directed toward the remote line terminal and not toward the station bus, and it must be isolated from bus impedance variations. This task is performed by the line trap. The line trap is usually a form of a parallel resonant circuit which is tuned to the carrier energy frequency. A parallel resonant circuit has high impedance at its tuned frequency, and it then causes most of the carrier energy to flow toward the remote line terminal. The coil of the line trap provides a low impedance path for the flow of the power frequency energy. Since the power flow is rather large at times, the coil used in a line trap must be large in terms of physical size.
Once the carrier energy is on the power line, any control of the signal has been given over to nature until it reaches the other end. During the process of traveling to the other end the signal is attenuated, and also noise from the environment is added to the signal. At the receiving terminal the signal is decoupled from the power line in much the same way that it was coupled at the transmitting terminal. The signal is then sent to the receivers in the control house via the coaxial cable.
8.6 COUPLING CAPACITORS:-
The coupling capacitor is used as part of the tuning circuit. The coupling capacitor is the device which provides a low
impedance path for the carrier energy to the high voltage line and at the same time, it blocks the power frequency current by being a high impedance path at those frequencies. It can perform its function of dropping line voltage across its capacitance if the low voltage end is at ground potential. Since it is desirable to connect the line tuner output to this low voltage point a device must be used to provide a high impedance path to ground for the carrier signal and a low impedance path for the power frequency current. This device is an inductor and is called a drain coil. The coupling capacitor and drain coil circuit are shown in Figure.
Fig 10. Coupling Capacitor and Drain Coil Combination
It is desirable to have the coupling capacitor value as large as possible in order to lower the loss of carrier energy and keep the bandwidth of the coupling system as wide as possible. However, due to the high voltage that must be handled and financial budget limitations, the coupling capacitor values are not as high as one might desire. Technology has enabled suppliers to continually increase the capacitance of the coupling capacitor for the same price thus improving performance.
8.7 DRAINAGE COILS:-
The drainage coil has a pondered iron core that serves to ground the power frequency charging to appear in the output of the unit. The coarse voltage arrester consists of an air gap, which sparks over at about 2 KV and protects the matching unit against line surges. The grounding switch is kept open during normal operation and is closed if anything is to be done on the communication equipment without interruption to power flow on the line. The matching transformer is isolated for 7 to 10 KV between the two winding and former two functions. Firstly it isolates the communication equipment for the power line. Secondly it serves to match the characteristic impedance of the power line 400-600 ohms to that of the co-axial vacuum arrester (which sparks) is over at about 250 V is provided for giving additional protection to the communication equipment.
The LMU which consists of the matching transformer and tuning capacitors indicated above is tailor-made to suit the individual requirements of the coupling equipment and is generally tuned to a wide band of carrier frequencies-(100-450 KHz typical).
8.8 ADVANTAGES & DISADVANTAGES OF PLCC
ADVANTAGES
5. Power lines are well insulated to provide negligible leakage between conductors and ground even in adverse weather conditions.
6. Largest spacing between conductors reduces capacitance which results in smaller attenuation at high frequencies. The large spacing also reduces the cross talk to a considerable extent.
DISADVANTAGES
There are many ways in which the communication signal may have error introduced into it. Interference, cross chatter, some active devices, and some passive devices all introduce noise or attenuation into the signal. When error becomes significant the devices controlled by the unreliable signal may fail, become inoperative, or operate in an undesirable fashion.
CONTROL ROOM
9.1 Introduction
At NPH not only remote control carry the appropriate means by which circuit breaker may be open or close but also necessary indicating devices, indicating lamps, isolating switching, protective relays, secondary circuit and wires are located here and most important “No load tap changer” for transformer is available. There is a panel for synchronizing. Different panels are located at different stages and on each panel control switch is provided on the board. The control switches for each circuit breaker and isolators are provided on control panel. Colors of signals are synchronized as follows: -
Red - For circuit breaker or isolator is in closed position.
Amber - Indicates abnormal condition requiring action.
There are different relays located.
9.2 Announcing section: -This section is always checked by the shift incharge. If any fault or any relay moves from L.T., alarm swings and type of fault is indicated on the announcing box. The most important section is transformer control section, winding temperature indicator. Tap position selector is situated on control panel. A control engineer controls the loading of various lines, outgoing feeders, synchronizing the incoming lines with bus bars.
9.3 Control and relay panel: -The arrangement of control and relay power is such that the indicating apparatus is clearly visible from control place. These respective panels are provided-
The synchronization switch is put to auto position when condition of synchronizing is satisfied. The white lamp on the top indicating ”synchronizing relay operated” glow and Circuit Breaker is automatically closed. When bus bar is dead there is no need of synchronizing in that case line is connected directly to bus bar by pulling a switch bar dead bus to on position.
Event Logger- to work in control room contain work are automated with computer based control system. By facilitate the operator locating identification and reporting fault, information is received.
9.4 Supervisory Control and Data Acquire System- for power system operation and control includes-
Data collection equipment as data logger collects the primary data from source converts it into suitable form of information and then transmitting and processing data. Logger records the rating from different location in the plant. Data logger is designed for plant performance computation for logical analysis of alarm condition.
The input scanner is automatic sequence switches, which select each, signal in turn transducers are used to convert original signal in the suitable electrical form for the input of scanner.. Data logger supplies the digitalized data of microprocessor. The signal is fed to the input scanner. The input scanner selects each signal in turn.
Fig 11. Control panels in control room
9.6 CRT Display- The operation in the control room needs information regarding parameters and configuration according to feeders. It is divided in many parts-
Indicating system is used to indicate total load, bus bar voltage indication of circuit breaker, isolator position. Lever type arrangement for opening and closing of circuit breaker close or open.
Relay section indicates the position of different relay at different feeder. Fault in any feeder is denoted by corresponding relay that gives alarm signal.
Master relay gives the signal to the trip coil of circuit breaker and thus faulty feeder is disconnected from supply. Meter section includes different types of meter.
One network CRT display provides operator with following information whenever he works-
Two types of display includes
Symbolic representation of equipment states usually in the form of diagram of substation.