Published using Google Docs
Supergen Brass Instructions & Registration
Updated automatically every 5 minutes

supergen

performance shower pumps

INSTALLATION GUIDE

SUPERGEN BRASS

POSITIVE & UNIVERSAL

BRASS

           

This is a high performance, high specification pump range

with precise installation requirements.

Please pass all manuals on to the householder after installation.

It is necessary to retain proof of purchase in order to facilitate any warranty claim.

technical helpline : 01793 820142

QUALIFIED INSTALLER TO CARRY OUT INSTALLATION

All rights reserved. Updated February 2023

  1. GENERAL

Your Supergen Shower Pump has been designed and manufactured in England.

If correctly installed and not misused, it will give many years of reliable service.

Installation and operation must comply with local regulations and accepted codes of good practice. The use of this product requires experience and knowledge of the product.To ensure satisfactory operation, we ask that you read the instructions before commencing installation. Then carry out, in sequence, each step as described. The instructions MUST be followed, otherwise the pump may be damaged and your warranty invalidated.

Note: Please dispose of any packaging supplied in an environmentally friendly and legal manner.

  1. PREPARING THE PUMP

When unpacking and installing pump, ensure that no foreign particles (such as solder or dust, etc) are allowed to enter the outlets; these will cause the flow switch to malfunction and damage the pump impeller.

Do not allow any solder flux to come into contact with any part of these pumps.

  1. POSITIONING THE PUMP

Do not connect the pump directly to the water mains supply.

The pump cannot be used with combination boilers, unvented cylinders, thermal store etc.

There should be a minimum of 227 litres  (50 gallons) of stored cold water.

The pump cannot operate if the level of the water in the cold water tank is below the level of the pump.

The pump must have an inlet head of at least 1.0 m.

There must be a minimum height between the bottom of the cold water tank and the highest point of the outlet pipe or the shower outlet of at least 250 mm for positive head pumps. 

It is important to select a position for installing the pump which affords easy access for subsequent servicing and maintenance. Ensure a good flow of water, sufficient inlet head, unrestrictive pipework and provision to prevent air locks.

Supergen Positive

Inlet Head

1 - 20 m

Supergen Universal

Inlet Head

1 - 8 m

The pump must be uncovered in a well-ventilated, frost-free location.

Position the pump horizontally with the outlet ports vertically upwards to ensure correct operation. Install on a vibration-free foundation. In case of wooden floors, use a small concrete foundation of approximately 225 x 225 mm and 40 - 50 mm thick.

Keep the pump as close as possible to the source of hot and cold water.

Install the pump in accordance with the Water Supply (Water Fittings) Regulations 1999.

Ideally position the pump at the base of the hot water cylinder.

Fit a downward loop of at least 450 mm if the pump is positioned above the hot water cylinder. This will help prevent air locks.

For installation within a bathroom, locate the pump in accordance with local regulations. Position the pump at least 0.6 metres horizontally away from or 3.0 metres vertically above floor from any bath, shower tray or basin. The pump may be fitted under a bath, providing this space is only accessible through the use of a tool. For installation in the loft, ensure there is sufficient head to feed the pump. For assistance, call 01793 820142.

  1. TYPICAL LAYOUT (FIG. 1)

  1. PIPE CONNECTIONS

Use 22 mm pipes to and from the pump.

  • The expansion pipe from the hot water cylinder should always rise in order to prevent trapped air.
  • The outlet pipe from pump to shower valve should rise, where possible, to prevent trapped air.
  • Pipes from the pump to the shower valve should go up and over, rather than under floor.
  • Do not fit any other outlets in the inlet pipes to the pump.
  • Use dedicated supplies to hot and cold water.
  • Avoid blanked off pipes.
  • Avoid restrictions in the flexible hoses.
  • Secure down all pipes to minimise noise and vibration.

  1. HOT WATER CYLINDER CONNECTIONS

DO NOT USE ANY JOINTING COMPOUNDS

  • Connect the supply from the hot water cylinder to the pump with a dedicated supply.
  • Fit a surrey flange to minimise air in the hot water supply to the pump.
  • Use 22 mm pipe to ensure an adequate flow to the pump. Use of a smaller diameter may cause cavitation and/or reduce showering performance.

  1. COLD WATER SUPPLY

DO NOT CONNECT DIRECTLY TO THE WATER MAINS SUPPLY

DO NOT USE ANY JOINTING COMPOUNDS OR TAPE

  • The cold water supply to the pump must be connected directly from the cold water storage tank (do not connect to the central heating header tank), see Fig 1.
  • The cold water storage tank must be equal to or larger than 227 litres (50 gallons).
  • Position the cold water outlet at least 25 mm lower than the supply to the hot water cylinder to prevent the supply of hot water only.

Do not position outlets in the cold water storage tank directly below the inlet from the water mains supply in order to prevent air from being drawn into the pump or hot water cylinder.

  1. CONNECTING THE PUMP

DO NOT USE ANY JOINTING COMPOUNDS OR TAPE.

DO NOT ALLOW SOLDER FLUX TO COME INTO CONTACT WITH THE PUMP.

ENSURE UNRESTRICTED FLOW IN THE FLEXIBLE HOSES.

  • Do not fit non-return valves in the inlet pipework to the pump.
  • Fit full-bore isolating valves in the pump inlet and outlet ports for easy installation, servicing and cleaning of strainers. Isolating valves assist draining down, strainer cleaning and refilling.
  • Position the pump on a flat, level surface, ensuring that the outlets are vertical for correct operation of the flow switches. Position supply pipes and shower pipes accurately so that the pump is not under any mechanical strain, such as supporting weight of pipes.
  • The inlets to the pump are fitted with strainers to prevent damage to the pump from abrasive debris in the water supply. The internal strainer basket can be removed by hand or with long nosed pliers.
  • The flexible hoses supplied must be used for connecting this pump to the pipe work.

Do not connect metal (brass / iron) fittings directly onto pump inlets / outlets.

Use of these hoses will ensure strain and vibration-free watertight connections.

Care should be taken with pump positioning so that the flexible hoses are not kinked.

Max bend allowance of 45 degrees.

  • When connecting to the pump hoses, make sure the connecting pipe is fully inserted to a minimum depth of

33 mm. Failure to fully insert connections will cause leaks.

  • Ensure correct alignment to avoid cross threading.
  • Line up pipework accurately and fit hoses to pump before connecting to pipes.
  • To disconnect the push fit hose, firmly push down the retaining ring whilst pulling out the hose.

NOTE: If you are fitting a UNIVERSAL shower pump (Supergen N60TX, N80TX, N121TX, N150TX, N21SX, N37SX), please refer to section 13 UNIVERSAL HEAD PUMPS - for additional connection details.

  1. TEMPERATURE SETTING

Maximum hot water temperature at the pump must not exceed 60°C (140°F) in accordance with

        BS6700:2006, to eliminate the risk of limescale and cavitation.

  1. FLANGES

Either Surrey, York, Warix or Essex flanges can be used for the hot water cylinder, depending on the cylinder type and installation.We do not recommend that you take the hot-water supply directly from the top of the hot water cylinder, as entrapped air may cause problems such as airlocks in the supply pipe.

  1. ELECTRICAL INSTALLATION

The low voltage pump installation kits are supplied with 3 metres of connecting lead. The connecting leads between the pump and the isolating transformer can be extended up to about 15 metres.

Use min. 1.0 mm2 cable.

DANGER - ELECTRIC SHOCK - DEATH OR SERIOUS PERSONAL INJURY

ENSURE COMPLIANCE WITH IEE REGULATIONS

Before starting any work on the product, make sure that the power supply has been switched off and that it cannot be accidentally switched on.

  • Complete all pipe installation before making any electrical connections.
  • Do not allow any water to enter into the electrical terminal box.
  • Electrical hazard will result if the pump is not correctly earthed. Installation must be carried out by a competent, authorised person in accordance with local regulations. If in doubt, consult a qualified electrician or call your local electrical supplier.
  • Check that the supply voltage and frequency correspond to the values stated on the nameplate.
  • The pump must be connected to a 230 volt 50 Hz supply. The unit must be connected to a switched spur fused at 5 Amps (10 Amps on Supergen 150TX and N150TX) with a minimum contact gap of 3 mm in all poles.
  • Metal pipes must be earthed by the use of earthing clamps and 4 mm2 earthing wire (BS 951).
  • Connect the pump to a socket with earth connection.
  • We recommend that you fit the permanent installation with an earth leakage circuit breaker (ELCB) with a tripping current ≤ 30 mA.

  1. 1x 230V, 50 Hz. Strip off the insulation cap and the leads as specified for the switched spur.

Observe colour coding as follows:

  • Brown to terminal L.
  • Yellow and green to terminal E (PE).

Ensure the earth lead is at least as long as the other two leads.

  • Blue to terminal N (neutral).

  1. Insert the lead fully into the terminal connector and tighten the screw firmly.
  2. Ensure that the connection is secure.
  3. Tighten the cable restraint.

Follow procedure for startup before switching on the power supply. Comply with IEE regulations.

Fit the terminal box cover before you switch on the power supply.

The pump switch should be left in ‘on’ position at all times for normal operation of the system.

12. PUMP START UP

DO NOT START THE PUMP UNTIL IT HAS BEEN FILLED WITH LIQUID.

BEFORE STARTUP, FLUSH THE SYSTEM WITH CLEAN WATER AND DRAIN TO REMOVE POSSIBLE IMPURITIES.

  1. Turn on the water supply. Allow the system to fill.
  1. Immediately inspect for any leaks.
  1. With the pump not running, allow maximum water flow, for example remove the handset from the shower hose.
  1. Operate maximum hot and cold flows for at least two minutes to flush out all debris.
  1. Switch on the power supply, run the pump for a few minutes, switch off, drain down and clean the inlet strainers.
  1. Replace the inlet strainers and reconnect the hoses. The strainer basket can be removed by hand or with long nosed pliers.
  1. Turn on the water supply. With the power supply off, allow maximum water flow, for example remove handset from the hose.
  1. Operate maximum hot and cold flows for at least 5 minutes each to ensure air is thoroughly purged from the system.
  1. Replace handset on the shower hose.
  1. Switch on the power supply.
  1. Operate the pump in both full hot and cold modes for two minutes each while inspecting for leaks.
  1. Check that all hot water connections are tight and not leaking when the hot water has been run for several minutes.

The first few times the pump is used, the insulating varnish used on the pump motor may give off an odour. This is perfectly normal and will diminish with use.

Shaft seal run in - The seal faces are lubricated by the pumped liquid, meaning that there may be a certain amount of leakage from the shaft seal. When the pump is started for the first time, or when a new shaft seal is installed, a certain run-in period is required before the leakage is reduced to an acceptable level.  The time required for this depends on the operating conditions. Under normal conditions the leaking liquid will evaporate. As a result, no leakage will be detected.

Run the pump for five minutes or more at least once every 4 weeks in order to prevent the pump from seizing up. Scale buildup can cause the pump parts to stick.

  1. UNIVERSAL HEAD PUMPS

Automatic universal head shower pumps are designed to operate automatically in installations when the shower outlets are above the level of the cold water storage tank.

The shower pump types Supergen N60TX, N80TX, N121TX, N150TX, N21SX and N37SX feature independent pressure and flow controls, with built-in non-return valves and stainless steel expansion tanks in each pump end. This system ensures complete hot and cold water system isolation with stable control over a very wide flow range.

13. UNIVERSAL HEAD PUMPS CONTINUED

Dry running protection - avoids damage to seals caused by water starvation. This condition is possible if the water supply fails, for instance if the water storage is insufficient or the pump strainers are blocked.

If the pump runs for 60 seconds with an insufficient water supply, the pump will stop and ‘lock out’.

Resetting the “lock out” - to reset the pump, switch off the power supply for ten seconds. When the power supply is switched on again, the pump will run for a few seconds to recharge the tanks. If it continues to run and there is no demand, this would indicate that one of the following situations is still present:

  • No water in the system.
  • Blocked strainer.
  • Air which has not yet cleared.

Continued dry running will lead to overheating of the shaft seals and eventually to a water leak.

Connecting the pump - follow the general instructions in this book, but please note the following.

  • Minimum head of water to supply the pump can be found on the nameplate.
  • Maximum static head of 8 metres, ie. the highest point of the system must be less than 8 metres above the pump.
  • Connect the pump side with the larger expansion tank to cold water and the pump side with the smaller expansion tank to hot water.

Operating instructions - Taps and valves used on the ‘pressure system’ must be fully turned off when not in use to avoid that the pump runs reciprocating on and off.

Installation options - lavatory cisterns

If the pump is to supply a lavatory cistern, take the precautions below to avoid frequent starting and stopping of the pump due to low flow rates.

If possible, best practice is to supply the cistern from the mains water supply. If this is not possible, we recommend a ‘Torbeck’ or equilibrium valve. If either of these are not possible, the following instructions should be followed:

  • A. The pump is supplied with two expansion or pressure tanks. They have capacities of 500 ml and 300 ml. The larger tank must be used on the cold side of the pump.
  • B. The cistern-filling pipe must be as free-flowing as possible with all flow restrictors removed. It is possible to change the tanks from one side of the pump to the other. When doing so, take care to ensure that none of the fibre washers are lost.

Washer dryers

Only brass pumps must be used for these applications.

  1. MAINTENANCE & SERVICING

  • Inspect all flexible hoses and connections at least every six months, as water temperature and mechanical stress, can cause the hoses to deteriorate with age. Replace as necessary to prevent leaks. Only hoses designed for the pump can be used.
  • Clean strainers every 6 months, or when needed. If the flow from the shower drops below its normal performance, it may be necessary to clean the pump strainers. Blocked strainers are common on initial installation of pumps, or in new buildings where the use of jointing compounds, tapes, flux and other debris can be flushed through the system. In this event, close the isolating valves, remove and clean the strainers. See section 12 Pump Start Up.
  • Washers and seals must be replaced when necessary to prevent leaks or drips.
  • If the supply cord is damaged, contact Pump World for assistance.
  • A common cause of poor shower performance is a clogged shower head / handset, so regular cleaning and descaling is important. This applies particularly to hard water areas.
  • Tank Air Pressure Setting (universal head pumps) - the pressures are factory set. In the event of a a leak, they should be set as follows:
  • The smaller tank (300 ml) should be set at a pressure between 0.9 - 1.0 Bar.
  • The larger tank (500 ml) should be set at a pressure between 0.5 - 0.6 Bar.

In certain applications, for example steam cabinets, it may be necessary to increase the pressure. Consult the appliance manufacturer.

  1. FAULT FINDING

Before starting any work on the product, make sure that the power supply has been switched off and that it cannot be accidentally switched on.

One of the most common causes of pump problems is air in the system.

Fault

Possible Cause

Remedy

  1. The pump fails to start.
  1. The power supply is switched off.

Switch on the power supply.

  1. The fuses are blown.

Replace the blown fuses. If the new ones blow too, check the electrical installation.

  1. The built-in thermal protection has switched off the motor.

The thermal protection resets automatically within one to two hours.

  1. Pump installed with non-vertical outlet ports (flow switches)

The pump must be installed with vertical outlet ports (flow switches).

  1. Insufficient water flow, below 0.5 lpm

Increase the water flow to at least 0.5 lpm.

2. The pump runs but delivers no water.

  1. Isolating valves are closed.

Open the isolating valves.

  1. Strainers are blocked.

Close the isolating valves, clean the strainers and re-open the valves.

3. The flow from the shower drops.

  1. Strainers are blocked.

Close the isolating valves, clean the strainers and re-open the valves.

4. The pump runs continuously.

  1. A tap or outlet is open.

Ensure that there are no leaks and that all taps and appliances are closed.

  1. Air in the system.

Purge any air in the system. With the pump not running, allow maximum flow by removing the shower handset and allowing the hose to hang into the shower tray or bath. Operate maximum hot and cold flow for at least five minutes each. For fixed head showers remove the shower rose and connect a length of hose, hanging into the shower tray or bath.

  1. The float in the flow switch is stuck in the up (on) position.

Make sure that the flow switch can operate correctly and there is no debris in the flow switch.

  1. Flow switch or reed switch faulty or incorrectly set.

Adjust or replace as appropriate.

5. The pump pulses.

  1. The use of other taps in the house may cause the pumps to start momentarily.

Ensure that taps or other outlets are not causing water hammer. A low pressure non-return valve can be fitted on the outlet pipe of the pump. Contact your installer.

6. Unstable water temperature or noisy pump.

  1. Air entering the pump, most commonly from the hot water cylinder.

Fit a Surrey flange and study the pipe layout. There should be no high points where air can collect.

  1. Too high water temperature.

Reduce hot water temperature. The maximum hot water temperature at the pump is 60’C.

  1. Debris caught in the impeller casing.

Remove debris.

7. Noisy pump.

  1. Vibration through pump mounting surface.

Place the pump on a concrete slab to reduce noise.

8. Hose connection leaking.

  1. Hose connection loose.

Make sure that the hose washers and strainer washers are fitted. Check that the plastic nuts on the hoses are tight.

16. ADDITIONAL FAULT FINDING FOR UNIVERSAL MODELS

  1. The pump runs continuously.
  1. Faulty pressure switch.

Contact the helpline for adjustment or replacement details.

2. The pump pulses.

  1. The use of other taps in the house may cause the pumps to start momentarily.

Contact your installer.

  1. Leaks in the system.

Check the system for leaks.

  1. Faulty non-return valve.

Check the non-return valves and replace if necessary.

3. The pump does not run even though there is demand.

  1. Flow demand below 0.5 lpm.

Open a tap to increase the flow demand.

  1. Flow switch or reed switch faulty.

Adjust or replace as appropriate.

  1. Dry-running protection activated.

Switch off the power supply for 10 seconds to reset. See Dry Running Protection in section 13.

4. Pump hunts when shutting down.

  1. Incorrect tank air pressure setting.

Adjust the tank air pressure setting.

  1. Insufficient run-on time.

Replace the printed-circuit board (PCB)

5. Pump hunts when starting up.

  1. Flow demand below 0.5 lpm.

Open a tap to increase the flow demand.

  1. Flow switch or reed switch faulty, or incorrectly set.

Adjust or replace as appropriate.

17. TECHNICAL DATA

Operating Conditions

Relative Humidity

Maximum 95%

Storage Temperature

Minimum -20°C, Maximum 70°C

Ambient Temperature

Maximum 40°C

Liquid Temperature

See pump nameplate

Minimum Starting Flow Rate

0.5 lpm

Start / Stop Frequency

Maximum 100 per hour

Electrical Data

Rated Current

See pump nameplate

Insulation Class

155 (F)

Miscellaneous Data

Enclosure Class

IPX2

Supergen Positive

60TX, 80TX, 121TX, 150TX, 21SX, 37SX

Supergen Universal

N60TX, N80TX, N121TX, N150TX, N21SX, N37SX

Maximum System Pressure

6.0 Bar

6.0 Bar

Inlet Head

1 - 20 m

1 - 8 m

Maximum Developed Pump Head

13 - 41 m

21 - 41 m

Supply Voltage

1x 230V, 50 Hz

1x 230V, 50 Hz

Rating

Continuous Operation

Continuous Operation

18. DISPOSAL

This product or parts of it must be disposed of in an environmentally sound way:

  1. Use the public or private waste collection service.
  2. If this is not possible, contact Pump World.

The crossed-out wheelie bin symbol on a product means that it must be disposed of separately from household waste. When a product marked with this symbol reaches its end of life, take it to a collection point designated by the local waste disposal authorities. The separate collection and recycling of such products will help protect the environment and human health.

19. INSTALLER CHECKLIST

Your Supergen shower pump will only work properly if it has been installed correctly. The installer should complete the following checklist ensuring it is signed and dated. While you are installing this shower pump, tick the following important instructions to confirm installation guide has been followed. If you need assistance, please contact the Supergen Service helpline on 01793 820142.

When the installation is completed please sign and date and pass on to the customer.

  • The pump must not be connected to mains pressure water (combi, unvented, thermal store etc). There should be a minimum of 227 litres  (50 gallons) of stored cold water.

  • Dedicated independent supply from hot water cylinder and cold feed from tank.

At least 1 metre head from water level in cold water storage tank to top of pump

  • 22 mm pipes if the pump is rated 2.0 bar or greater. The flexible hoses supplied must be used to connect the pump. Do not connect any pipework directly to the pump.

  • Highest point of pipes must be at least 250 mm below the base of the cold water storage tank (not applicable for universal head pumps).

  • An air free supply of hot water is required. Do not connect directly to expansion pipe. The use of a Surrey or Essex flange is recommended.

  • Anti gravity loop if the pump is sited above the hot water cylinder.

  • Hot water temperature at the pump must not exceed 60°C (cylinder must have thermostat).

  • Do not use any jointing compounds on threads or retaining nuts.

  • When making pipe joints, do not allow any solder flux to come into contact with the pump.

  • Complete all pipework before making electrical connection - do not let any water into the terminal box.

  • Do not run the pump dry - purge with water thoroughly for 5 minutes before running pump.

  • After completing installation, the whole system must be thoroughly tested, operating both hot and cold at full flow. Check water temperature stability and that each connection is tight and not leaking.

Print Name

     Signature

Company Name

     Date

To register your Supergen shower pump, please complete and return this form via post, email or online.

Pump World, Unit 11 Woodside Road, Swindon, SN3 4WA.   enquiries@pumpworld.co.uk,   www.pumpworld.co.uk 

CONTACT DETAILS

Your Full Name

Address & Post Code

Telephone Number

Email Address

PUMP DETAILS

Supergen Model Name

Located on the pump nameplate.

Pump Serial Number

Must be included. Located on the pump nameplate, typical format: W00000 - 000 - 0000

Supplied By

Please include contact, company name and

branch location (if applicable).

Installed By

Please include installer name, company name and contact phone number.

Date of Purchase

Date of Installation

INSTALLATION DETAILS

This part should be completed with the help of your installer. All questions must be completed.

Type of Cylinder Fitting

(Essex Flange / Warix Flange / Surrey Flange / York Flange / 1st Vent Take Off) If other, please specify.

Pipe Sizes

Suction / Discharge

Do you have a Cylinder Thermostat?

Is Suction Dedicated?

ie. no draw offs prior to the pump.

If yes, confirm Thermostat Setting

The hot water temperature at the pump must not exceed 60’C.

°C

Are Flexible Hoses straight?

Flexibles must be kept straight.

If no, do you have a Temperature Regulator? If not, your warranty is invalid.

Is the pump located on the floor, by the cylinder?

If applicable, confirm Temperature Regulator Setting  

°C

If no, please advise pump location